Amana ACV9, AMV9 installation instructions Gas Piping Connections

Page 25
Gas Piping Connections
of the furnace. The rigid pipe must be long enough to reach the outside of the cabinet so as to seal the grommet cabinet penetration. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes.

shipped from the factory. Maximum torque for the gas valve connection is 375 in-lbs; excessive over-tightening may damage the gas valve.

Install a manual shutoff valve between the gas meter and unit within six feet of the unit. If a union is installed, the union must be downstream of the manual shutoff valve, between the shutoff valve and the furnace.

Tighten all joints securely.

Connect the furnace to the building piping by one of the following methods:

Rigid metallic pipe and fittings.

Semi-rigid metallic tubing and metallic fittings.

Aluminum alloy tubing must not be used in exterior locations. In order to seal the grommet cabinet penetration, rigid pipe must be used to reach the outside of the cabinet. A semi-rigid connector to the gas piping may be used from there.

Use listed gas appliance connectors in accordance with their instructions. Connectors must be fully in the same room as the furnace.

Protect connectors and semirigid tubing against physical and thermal damage when installed. Ensure aluminum- alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry, plaster, or insulation, or subjected to repeated wetting by liquids such as water (except rain water), detergents, or sewage.

Manual backgroundCAUTION

EDGES OF SHEET METAL HOLES MAY BE SHARP. USE GLOVES A PRECAUTION WHEN REMOVING HOLE PLUGS.

DIRECT/STANDARD INLET PIPING

When gas piping enters directly to the gas valve through the stan- dard inlet hole, the installer must supply straight pipe with a ground joint union to reach the exterior of the furnace. The rigid pipe must be long enough to reach the outside of the cabinet to seal the grommet cabinet penetration. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes.

INDIRECT/ALTERNATE INLET PIPING

When gas piping enters indirectly to the gas valve through the alternate gas inlet hole the following fittings (starting from the gas valve) to reach the outside of the cabinet must be supplied:

Coupling.

90 degree elbow.

2 inch close nipple.

90 degree elbow.

Straight pipe, with a ground joint union, to reach the exterior

GAS VALVE

MANIFOLD

BURNERS

ALTERNATE

GAS LINE

LOCATION

PLUG IN

ALTERNATE

GAS LINE

HOLE

GROUND JOINT

PIPE UNION

 

MANUAL

 

 

SHUT OFF VALVE

 

MANUAL

(UPSTREAM FROM

ALTERNATE

GROUND JOINT

GAS LINE

SHUT OFF VALVE

PIPE UNION)

LOCATION

(UPSTREAM FROM

 

 

GROUND JOINT

 

 

PIPE UNION)

 

 

 

HEIGHT REQUIRED

PLUG IN

 

ALTERNATE

HEIGHT REQUIRED

BY LOCAL CODE

GAS LINE

BY LOCAL CODE

 

HOLE

GROMMET

 

IN STANDARD

*

GAS LINE HOLE

 

GROMMET

GAS VALVE

 

IN STANDARD

 

GAS LINE HOLE

MANIFOLD

 

 

DRIP LEG

DRIP LEG

B URNERS

 

GROUND JOINT

 

PIPE UNION

GAS PIPING CHECKS

Before placing unit in operation, leak test the unit and gas connec- tions.

Manual backgroundWARNING

TO AVOID THE POSSIBILITY OF EXPLOSION OR FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS.

 

UPFLOW

 

COUNTERFLOW

 

MANUAL SHUT-OFF VALVE

 

MANUAL SHUT-OFF VALVE

 

(UPSTREAM FROM GROUND

 

 

JOINT PIPE UNION)

 

(UPSTREAM FROM GROUND

 

 

GROUND JOINT

JOINT PIPE UNION)

GROUND JOINT

 

PIPE UNION

 

PIPE UNION

 

 

 

 

DRIP LEG

 

DRIP LEG

GAS VALVE

GROMMET IN STANDARD

GAS VALVE

GROMMET IN STANDARD

 

GAS LINE HOLE

 

GAS LINE HOLE

BURNERS

 

BURNERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAIN TRAP

 

 

 

 

 

 

 

 

 

DRAIN TRAP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MANIFOLD

 

PLUG IN ALTERNATE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTERNATE

 

 

 

 

 

 

 

GAS LINE HOLE

 

 

 

 

 

 

MANIFOLD

 

 

 

 

PLUG IN ALTERNATE

GAS LINE LOCATION

 

 

 

 

 

ALTERNATE GAS

 

 

 

 

GAS LINE HOLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LINE LOCATION

 

 

 

 

 

 

 

 

 

 

 

HORIZONTAL[COUNTERFLOW]

 

 

 

 

HORIZONTAL [UPFLOW MODEL]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES: 1. WHEN GAS LINE IS IN THE ALTERNATE

2. DRIP LEG MAY TERMINATE WITH

 

 

 

 

 

 

 

 

 

LOCATION, SWAP THE POSITION OF

 

 

 

 

A 1/2" X 1/8" PIPE PLUG TO

 

 

 

 

 

 

 

 

 

THE PLUG AND GROMMET.

 

 

 

 

ACCOMMODATE LINE GAS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE MEASUREMENT.

Gas Piping Connections

Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other approved testing methods.

NOTE: Never exceed specified pressures for testing. Higher pressure may damage the gas valve and cause subsequent overfiring, resulting in heat exchanger failure.

Disconnect this unit and shutoff valve from the gas supply piping system before pressure testing the supply piping system with pres- sures in excess of 1/2 psig (3.48 kPa).

Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping system with test pressures equal to or less than 1/2 psig (3.48 kPa).

PROPANE GAS TANKS AND PIPING

Manual backgroundWARNING

PROPANE GAS IS HEAVIER THAN AIR AND ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES. TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS DETECTION WARNING DEVICE.

A gas detecting warning system is the only reliable way to detect a propane gas leak. Rust can reduce the level of odorant in propane

25

Image 25
Contents ATTENTION INSTALLING PERSONNEL RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTIONINSTALLATION INSTRUCTIONS Installer Affix all manuals adjacent to the unitTable of Contents Table of Contents APPENDIXWHAT TO DO IF YOU SMELL GAS CARBON MONOXIDE POISONING HAZARDBURNER COMPARTMENT BLOWER COMPARTMENT BLOWER COMPARTMENT BURNER COMPARTMENTUpflow/Horizontal Counterflow/HorizontalIII.PRODUCT APPLICATION II. SAFETYIV. LOCATION REQUIREMENTS & CONSIDERATIONS Suspended Furnace V. COMBUSTION & VENTILATION AIR REQUIREMENTS Thermostat Influences5.3.1General 5.3.2Equipment Located in Unconfined SpacesBuilding. See 5.3.3-a VI. INSTALLATION POSITIONS 5.3.4Specially Engineered Installations5.3.5 Louvers and Grilles VII. HORIZONTAL APPLICATIONS & CONSIDERATIONSVIII. PROPANE GAS /HIGH ALTITUDE INSTALLATIONS Recommended Installation PositionsIX. VENT/FLUE PIPE & COMBUSTION AIR PIPE Vent Termination Clearances Counterflow units Vent/Flue Pipe Cuts2.Upflow and Counterflow units 3.Upflow and Counterflow units8.Upflow and Counterflow units 7.Upflow and Counterflow unitsCounterflow units Counterflow unitsVertical Termination Single Pipe Alternate Combustion Air Intake LocationUPFLOW Alternate Vertical Termination Single PipeHorizontal Termination Single Pipe Horizontal Termination Single PipeAlternate Horizontal Vent Termination Dual Pipe Standard Horizontal Terminations Dual PipeLevel Dual Pipe Dual PipeUpright “Standard” Connections - Right Side Hose and Tube IdentificationUpflow Shown, Counterflow Similar Upright “Standard” Connections - Left SideUpflow Shown, Counterflow Similar Upright “Alternate” Connections - Right Side OnlyHorizontal Connections - Right Side Down Upflow Shown, Counterflow SimilarUpflow Shown, Counterflow Similar Horizontal Connections - Left Side DownXI. ELECTRICAL CONNECTIONS 24 VOLT DEHUMIDISTAT WIRING 24 VOLT THERMOSTAT WIRINGTwo-StageHeating with Two-StageCooling Junction Box RelocationXII. GAS SUPPLY AND PIPING Inlet Gas Supply Pressure Gas Piping Connections Propane Gas Piping Chart Propane Gas Installation TypPropane Gas Piping Chart XIII. CIRCULATING AIR & FILTERSPermanent Minimum Filter Area sq. in Duct Flange Cut OutsBased on a 600 ft/min filter face velocity Filter Locations XIV. STARTUP PROCEDURE & ADJUSTMENTMeasuring Inlet Gas Pressure Alt. Method Temperature Rise Measurement ramping profile XV. NORMAL SEQUENCE OF OPERATION XVII. SAFETY CIRCUIT DESCRIPTION XVIII. TROUBLESHOOTINGFurnace awaits next call from thermostat XVI. OPERATIONAL CHECKSXIX. MAINTENANCE XXII. REPAIR & REPLACEMENT PARTS XXI. BEFORE LEAVING AN INSTALLATIONXX. INTERNAL FILTER REMOVAL Primary Limit Switch Rollout Limit SwitchAuxiliary Limit Switch Pressure SwitchSymptoms of Abnormal TROUBLESHOOTING CHARTFault Descriptions Possible CausesSymptoms of Abnormal TROUBLESHOOTING CHARTFault Descriptions Possible CausesWIRING DIAGRAM 2550 North Loop West, Suite Houston, TX