Allied Air Enterprises A80UH, 80G1UH installation instructions Equipment In Confined Space

Page 8
EQUIPMENT IN CONFINED SPACE

When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.

EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE

(Inlet Air from Crawlspace & Outlet Air to Ventilated Attic)

NOTE: The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645 mm² per 1.17 kW) per hour of the total input rating of all equipment in the enclosure.

Figure 4

EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE

(All Air through Ventilated Attic)

NOTE: The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645 mm² per 1.17 kW) per hour of the total input rating of all equipment in the enclosure.

Figure 5

EQUIPMENT IN CONFINED SPACE

(ALL AIR FROM OUTSIDE)

NOTE: Each air duct opening shall have a free area of at least one square inch per 2,000 Btu (645 mm² per .59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645 mm² per 1.17 kW) per hour of the total input rating of all other equipment in the enclosure.

Figure 6

Page 8 of 39

Issue 1031

506526-01

Image 8
Contents TABLE OF CONTENTS INSTALLATION INSTRUCTIONSA80UH & 80G1UH Warm Air Gas FurnaceSIDE VIEW A80UH & 80G1UH Unit Dimensions - inches mmFRONT VIEW A80UH & 80G1UH 506526-01Safety Information Installed LocationsDANGER A80UH & 80G1UH Gas FurnaceInstalled in Combination with a Cooling Coil Heating Unit Installed Upstream of Cooling UnitTemperature Rise Use of Furnace as a Construction HeaterGeneral Product Contains Fiberglass WoolAllied Air Enterprises, Inc 215 Metropolitan Drive West Columbia, SCUnconfined Space Confined SpaceEquipment in Confined Space - All Air From Inside Figure Air from InsideEQUIPMENT IN CONFINED SPACE Upflow Applications Setting EquipmentUpflow Application Installation Clearances Return Air - Upflow Applications 1800 cfm 850 L/s must have one of the following3.Bottom return air 4.Return air from both sides 5.Bottom and one side return airHorizontal Application Installatioin clearances Removing the Bottom PanelRemoving the Bottom Panel Figure Horizontal ApplicationsHorizontal Application Unit installed on Platform FiltersTable Duct System Supply Air PlenumVenting Mounting Screws Location Figure UPFLOW POSITIONUPFLOW POSITION Figure UPFLOW POSITIONHorizontal Position HORIZONTAL LEFT POSITIONFigure HORIZONTAL LEFT POSITION HORIZONTAL RIGHT POSITIONVenting Using a Masonry Chimney Common Venting Using Metal Lined Masonry ChimneyVent Connection Figure IssueGeneral Venting Requirements Issue Page 17 ofServing a Single Category I Appliance IssuePage 18 of 506526-01Serving a Single Category I Appliance IssuePage 19 of 506526-01Vent Connector Capacity Serving Two or More Category I AppliancesCommon Vent Capacity Serving Two or More Category I AppliancesTable Common Vent Capacity Serving Two or more Category I Appliances TableVent Connector Capacity Serving Two or More Category I AppliancesRemoval of the Furnace from Common Vent CARBON MONOXIDE POISONING HAZARDIssue Page 22 ofGas Piping Gas SupplyGas Pipe Capacity - ft³/hr m³/hr IssuePossible Gas Piping Configurations Figure Horizontal ApplicationsIssue Page 24 ofINTERIOR MAKE-UPBOX INSTALLATION Figure Leak CheckFigure Electrical ELECTROSTATIC DISCHARGE ESD INTERIOR MAKE-UPBOX INSTALLATION FigureAccessory Terminals Generator Use - Voltage RequirementsThermostat Condensing Unit Thermostat DesignationsWiring Diagram Figure IssuePage 27 of 506526-01Automatic Hot Surface Ignition System Typical Field Wiring Diagram FigureIntegrated Control FOR YOUR SAFETY READ BEFORE LIGHTING UNIT Unit Start-UPPlacing the Furnace into Operation Gas Valve Operation FigureGas Pressure Adjustment Gas Flow Approximate Heating Sequence Of Operation FigureSupply Pressure Measurement Manifold Pressure MeasurementManifold Pressure Settings and Pressure Switch Other Unit AdjustmentsFlame Rollout Switches Pressure SwitchThermostat Heat Anticipation ElectricalBlower Speeds Electronic IgnitionService ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARDBlower Flue And ChimneyCleaning the Heat Exchanger and Burners IssuePage 34 of 506526-01Remove 5 Screws If Necessary NOx INSERTS FigurePLANNED SERVICE FAILURE CODESIssue Page 36 ofREPAIR PARTS LIST Cabinet PartsHeating Parts Control PanelSTART-UP& PERFORMANCE CHECK LIST UNIT SET UP IssuePage 38 of 506526-01Issue UNIT OPERATIONPage 39 of 506526-01