Allied Air Enterprises A80UH, 80G1UH installation instructions General Venting Requirements

Page 16
General Venting Requirements

Common Venting Using Tile Lined Interior Masonry Chimney and Combined Vent Connector

NOTE: Refer to provided venting tables for installations.

NOTE: The chimney must be properly sized per provided venting tables or lined with listed metal lining system.

Figure 25

DO NOT insulate the space between the liner and the chimney wall with puffed mica or any other loose granular insulating material.

Manual backgroundManual background IMPORTANT

SINGLE appliance venting of a fan assisted furnace into a tile lined masonry chimney (interior or outside wall) is prohibited. The chimney must first be lined with either type B1 vent or an insulated single wall flexible vent lining system which has been sized according to the provided venting tables and the vent pipe manufacturer’s instructions.

A fan assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met:

The chimney is currently serving at least one drafthood equipped appliance.

The vent connectors and chimney are sized according to the provided venting tables.

If type B1 double wall vent is used inside a chimney, no other appliance can be vented into the chimney. The outer wall of type B1 vent pipe must not be exposed to flue products. A type B1 vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a’iisted roof assembly according to the terms of their respective listings and the vent manufacturer’s instructions.

When inspection reveals that an existing chimney is not safe for the intended purpose, it shall be rebuilt to conform to nationally recognized standards, lined or relined with suitable materials, or replaced with a gas vent or chimney suitable for venting. The chimney passageway must be checked periodically to ensure that it is clear and free of obstructions.

Do not install a manual damper, barometric draft regulator, or flue restrictor between the furnace and the chimney.

Never connect a Category I appliance to a chimney that is servicing a solid fuel appliance. If a fireplace chimney flue is used to vent this appliance, the fireplace opening must be permanently sealed.

A type B or listed chimney lining system that passes through an unused masonry chimney flue is not considered to be exposed to the outdoors.

General Venting Requirements

Vent all furnaces according to these instructions:

1.Vent diameter recommendations and maximum allowable piping runs are found in the provided venting tables.

2.In no case should the vent or vent connector diameter be less than the diameter specified in the provided venting tables.

3.The minimum vent capacity determined by the sizing tables must be less than the low fire input rating and the maximum vent capacity must be greater than the high fire input rating.

4 . Single appliance vents - If the vertical vent or tile lined chimney has a larger diameter or flow area than the vent connector, use the vertical vent diameter to determine the minimum vent capacity and the vent connector diameter to determine the maximum vent capacity. The flow area of the vertical vent, however, shall not exceed 7 times the flow area of the listed appliance categorized vent area, drafthood outlet area or flue collar area unless designed according to approved engineering methods.

5.Multiple appliance vents - The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area, drafthood outlet area or flue collar area unless designed according to approved engineering methods.

Page 16 of 39

Issue 1031

506526-01

Image 16
Contents TABLE OF CONTENTS INSTALLATION INSTRUCTIONSA80UH & 80G1UH Warm Air Gas FurnaceFRONT VIEW A80UH & 80G1UH Unit Dimensions - inches mmSIDE VIEW A80UH & 80G1UH 506526-01Safety Information Installed LocationsDANGER A80UH & 80G1UH Gas FurnaceInstalled in Combination with a Cooling Coil Heating Unit Installed Upstream of Cooling UnitTemperature Rise Use of Furnace as a Construction HeaterGeneral Product Contains Fiberglass WoolAllied Air Enterprises, Inc 215 Metropolitan Drive West Columbia, SCUnconfined Space Confined SpaceEquipment in Confined Space - All Air From Inside Figure Air from InsideEQUIPMENT IN CONFINED SPACE Upflow Application Installation Clearances Setting EquipmentUpflow Applications Return Air - Upflow Applications 1800 cfm 850 L/s must have one of the following3.Bottom return air 4.Return air from both sides 5.Bottom and one side return airHorizontal Application Installatioin clearances Removing the Bottom PanelRemoving the Bottom Panel Figure Horizontal ApplicationsHorizontal Application Unit installed on Platform FiltersTable Duct System Supply Air PlenumVenting Mounting Screws Location Figure UPFLOW POSITIONUPFLOW POSITION Figure UPFLOW POSITIONHorizontal Position HORIZONTAL LEFT POSITIONFigure HORIZONTAL LEFT POSITION HORIZONTAL RIGHT POSITIONVenting Using a Masonry Chimney Common Venting Using Metal Lined Masonry ChimneyVent Connection Figure IssueGeneral Venting Requirements Issue Page 17 ofServing a Single Category I Appliance IssuePage 18 of 506526-01Serving a Single Category I Appliance IssuePage 19 of 506526-01Vent Connector Capacity Serving Two or More Category I AppliancesCommon Vent Capacity Serving Two or More Category I AppliancesTable Common Vent Capacity Serving Two or more Category I Appliances TableVent Connector Capacity Serving Two or More Category I AppliancesRemoval of the Furnace from Common Vent CARBON MONOXIDE POISONING HAZARDIssue Page 22 ofGas Piping Gas SupplyGas Pipe Capacity - ft³/hr m³/hr IssuePossible Gas Piping Configurations Figure Horizontal ApplicationsIssue Page 24 ofINTERIOR MAKE-UPBOX INSTALLATION Figure Leak CheckFigure Electrical ELECTROSTATIC DISCHARGE ESD INTERIOR MAKE-UPBOX INSTALLATION FigureAccessory Terminals Generator Use - Voltage RequirementsThermostat Condensing Unit Thermostat DesignationsWiring Diagram Figure IssuePage 27 of 506526-01Integrated Control Typical Field Wiring Diagram FigureAutomatic Hot Surface Ignition System FOR YOUR SAFETY READ BEFORE LIGHTING UNIT Unit Start-UPPlacing the Furnace into Operation Gas Valve Operation FigureGas Pressure Adjustment Gas Flow Approximate Heating Sequence Of Operation FigureSupply Pressure Measurement Manifold Pressure MeasurementManifold Pressure Settings and Pressure Switch Other Unit AdjustmentsFlame Rollout Switches Pressure SwitchThermostat Heat Anticipation ElectricalBlower Speeds Electronic IgnitionService ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARDBlower Flue And ChimneyCleaning the Heat Exchanger and Burners IssuePage 34 of 506526-01Remove 5 Screws If Necessary NOx INSERTS FigurePLANNED SERVICE FAILURE CODESIssue Page 36 ofREPAIR PARTS LIST Cabinet PartsHeating Parts Control PanelSTART-UP& PERFORMANCE CHECK LIST UNIT SET UP IssuePage 38 of 506526-01Issue UNIT OPERATIONPage 39 of 506526-01