Superior DT-400CMP Table D, Vertical Vent Figures/Tables, Rear Vent - THREE ELBOWS, continued

Page 13
(continued)

VERTICAL VENT FIGURES/TABLES

(continued)

 

 

TABLE D

 

 

 

 

 

 

 

 

 

 

 

 

 

V Minimum

H Maximum

H+H1 Maximum

 

 

feet

(m)

feet

(m)

feet

 

(m)

 

 

 

 

 

 

 

 

 

 

 

1

(0.305)

2

(0.610)

5

 

(1.52)

 

 

 

 

 

 

 

 

 

 

 

2

(0.610)

4

(1.22)

10

 

(3.1)

 

 

 

 

 

 

 

 

 

 

 

3

(0.914)

6

(1.86)

15

 

(4.65)

 

 

 

 

 

 

 

 

 

 

 

4

(1.22)

8

(2.48)

20

 

(6.2)

 

 

 

 

 

 

 

 

 

 

 

V+V1+H+H1 = 40 feet (12.4 m) Max.

 

 

 

V1

 

H = 8 feet (2.48 m) Max.

 

 

H + H1 = 20 feet (6.2 m) Max.

 

 

 

 

 

 

 

 

 

 

 

 

H1

*Ceiling

Firestop/Spacer

(SV4.5BF)

**Wall

Firestop/Spacer

(SV4.5HF)

*When using Secure Flex, use Firestop/Spacer SF4.5BF

**When using Secure Flex, use Firestop/Spacer SF4.5HF

A Vent Restrictor, as shown in Figure 18, page 10, must be used in this application

*Ceiling

Firestop/Spacer

(SV4.5BF)

V

Figure 26 - Rear Vent - THREE ELBOWS

H

TABLE E

V MINIMUM

H + H1 Maximum

feet

(m)

feet

(m)

1

(0.305)

5

(1.52)

2

(0.610)

10

(3.1)

3

(0.914)

15

(4.65)

4

(1.22)

20

(6.2)

H +H1= 20 feet (6.2 m) Max.

V+V1+H+H1 = 40 feet (12.4 m) Max.

Figure 27 - Top Vent - THREE ELBOWS

 

*Ceiling

 

V1

Firestop/Spacer

**Wall

(SV4.5BF)

 

 

Firestop/Spacer

 

 

(SV4.5HF)

 

H

 

H1

V

*When using Secure Flex, use Firestop/Spacer SF4.5BF

**When using Secure Flex, use Firestop/Spacer SF4.5HF

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

13

Image 13 Superior DT-400CMP Table D, Vertical Vent Figures/Tables, Rear Vent - THREE ELBOWS, Top Vent - THREE ELBOWS, continued
Contents DIRECT VENT DT-400& DR-400 INSTALLATION INSTRUCTIONSMODELS Millivolt ElectronicPACKAGING TYPICAL INSTALLATIONINTRODUCTION GENERAL INFORMATIONMillivolt Models ÀCOTE DE LAPPAREILElectronic Models All ModelsLOCATION Typical LocationsAPPLIANCE AND VENT CLEARANCES Shelf Height inches mmDETAILED INSTALLATION STEPS TYPICAL INSTALLATION SEQUENCEVENT TERMINATION CLEARANCES Vertical Vent Termination ClearancesUS Installation Canadian Installation12 inches 30cm 12 inches 30cmAND ROUND HORIZONTAL TERMINATION SV4.5HTR framing depth dimension when the finish12¹⁄₈material drywall thickness is 1/2 in 13mmStep 3. INSTALL THE VENT SYSTEM FIREPLACE SPECIFICATIONSway. Install vent according to local codes listed for operation and installation withVERTICAL TERMINATION SYSTEMS ROOF Vertical Straight InstallationSelect Venting System - Horizontal or Vertical Vent / Appliance Collar Connection Vertical Offset InstallationC. Attach vent components to each other ConnectionPitch Framing Dimensions for Roof0/12 6/12VERTICAL VENT FIGURES/TABLES TABLE AH Maximum Figure 23 - Top Vent - STRAIGHTVERTICAL VENT FIGURES/TABLES TABLE DFigure 26 - Rear Vent - THREE ELBOWS Figure 27 - Top Vent - THREE ELBOWSTYPICAL HORIZONTAL VENT INSTALLATION F.Install firestop/spacer at ceilingHORIZONTAL OUTSIDE WALL TERMINATION SYSTEM A. Plan the vent runattach termination adapter Connecting/Recessing Long Square HorizontalSquare SV4.5HTS Short Square SV4.5HTSSHORIZONTAL VENT FIGURES/TABLES 3.Install the round termination SV4.5HTRVenting Components LONG SQUARE TERMINATIONV Minimum TABLE FH Maximum V MinimumTABLE J HORIZONTAL VENT FIGURES/TABLE CONTINUEDH + H1 Maximum termination Figure 39- Top Vent - TWO 90 DEGREE ELBOWSB. Install the Outer Flex Pipe A. Install the Inner Flex PipeC. Route Flex Vent A. SIT and Honeywell Millivolt Wiring Step 4. FIELD WIRINGB. Electronic Wiring See Figure Optional Gas Flex Line Connector Step 6. CONNECTING GAS LINEFBK-250Blower Kit See Figure Opening Control Compartment DoorStep 9. INSTALLING THE GLASS DOOR Step 7. INSTALLING LOGS AND GLOWING EMBERSAdjustment Sit and Honeywell Millivolt Gas ValveStep 11. HOOD INSTALLATION Step 10. BURNER ADJUSTMENTSBurner Adjustment FINISHING REQUIREMENTS Wall DetailsMANTEL CLEARANCES INSTALLATION ACCESSORIESInches mm COLD CLIMATE INSULATIONDescription INSTALLATION ACCESSORIES ContinuedModel No. Description GAS CONVERSION KITS AND .2 INSTALLATION CODEIn Canada Natural To Propane Gas Conversion Kit SIT SystemsPilot for SIT Millivolt Gas Valve Pilot Orifice Adjusting KnobPilot for Honeywell Millivolt Gas Valve Step 5. Millivolt Appliances Honeywell SystemsPilot PilotAssembly Orifice Ignitor Assembly Spring Adjusting ScrewAll Models Model No