Honeywell VISTA-15P Installing a 5800TM, Module, Transmitters, Transmitter Battery Life

Page 15

 

 

 

Mounting and Wiring the Control

 

 

 

 

 

 

Installing a 5800TM

• Use this module only if you are using one or more wireless bi-directional keypads or

 

Module

keyfobs with a wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g.,

 

 

 

5883).

 

 

 

 

• The 5800TM must be set to address 28 (cut red-W1 jumper).

 

 

 

• The 5800TM can be used in partition 1 only.

 

 

 

• For additional information regarding the 5800TM, refer to the 5800TM’s instructions.

 

 

 

1. Mount the 5800TM next to the RF receiver (between one and two feet from the

 

 

 

receiver’s antennas) using its accompanying mounting bracket. Do not install within

 

 

 

the control cabinet.

 

 

 

2. Connect the 5800TM to the control panel’s keypad connection terminals as shown on

 

 

 

the Summary of Connections diagram and set to address 28.

 

Installing the

• Refer to the table of compatible devices at the back of this manual.

 

Transmitters

• Supervised transmitters† send check-in signals to the receiver at 70-90 minute

 

 

 

intervals. If at least one check-in message is not received from each transmitter within

 

 

 

a 12-hour period, the “missing” transmitter number(s) and “CHECK” is displayed. (†

 

 

 

Hand-held transmitters, e.g., 5802, 5802CP, 5804, 5804BD, 5827, 5827BD, do not send

 

 

 

 

 

 

check-in signals.)

 

 

 

 

 

 

• To be sure reception of the transmitter's signal at the proposed mounting location is

 

 

 

adequate, perform a Go/No Go Test, described in the Testing the System section.

 

 

 

• Install transmitters in accordance with the instructions provided with each.

 

 

 

• Set 5827, 5827BD, 5804BD wireless keypads to the programmed House ID (field *24),

 

 

 

using its DIP switches (5827) or follow the instructions provided with the device.

 

 

 

• Use *56 or *58 Zone Programming Menu modes to program zone information and enroll

 

 

 

transmitters (VISTA-20P: zones 9-48, buttons 49-64; VISTA-15P: zones 9-34, buttons

 

 

 

49-56).

 

 

 

 

Wireless Keys: Use Wireless Key Programming Templates section of the *58 Zone

 

 

 

Programming Menu mode to program zone information and enroll each button of the

 

 

 

wireless keys used. Once a wireless key is enrolled, it must be assigned to a user before

 

 

 

it becomes active. See Adding/Deleting Security Codes section for procedure.

 

 

 

 

 

 

 

 

ULC NOTE: In accordance with ULC standards, the RF supervision period for the VISTA-20PCN

 

 

 

 

and VISTA-15PCN is three hours for Fire zones (Zone Type 9 and 16) and 12 hours for all other zone

 

 

 

 

types.

 

 

 

 

 

 

 

 

UL The following transmitters are not intended for use in UL installations: 5802MN, 5802MN2, 5804,

 

 

 

 

5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.

 

 

 

 

The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.

 

 

 

 

 

Transmitter Battery Life

• See Wireless Transmitter paragraph in the Limitations of This Alarm System

 

 

 

statement located at the end of this manual for information on transmitter battery

 

 

 

life.

 

 

 

• Some transmitters (e.g., 5802 and 5802CP) contain long-life but non-replaceable

 

 

 

batteries, and no battery installation is required. At the end of their life, the complete

 

 

 

unit must be replaced (and a new serial number enrolled by the control).

 

 

 

Button-type transmitters (such as 5801, 5802, and 5802CP) should be periodically

 

 

 

tested for battery life.

 

 

 

• The 5802MN and 5804 Button Transmitters have replaceable batteries.

 

 

 

Do not install batteries in wireless transmitters until you are ready to enroll during

 

 

 

system programming. After enrolling, batteries need not be removed.

2-9

Image 15
Contents Ademco Vista Series Recommendations for Proper Protection Table Of Contents Table Of Contents Capabilities and Functions Features and Installation HighlightsImportant Installation Highlights Installer Please Read Compatible DevicesDevice Installing the Control Cabinet and PC Board Mounting and Wiring the ControlAuxiliary Device Current Draw Worksheet Wire Run Chart AC Power, Battery, and Ground ConnectionsSupervised output Connecting the Keypads and Other Addressable DevicesSounder Bell Connections Basic ConnectionsSize MA or less 100 mA 300 mA 500 mA 600 mA Table of Device AddressesKeypad Notes Long Range Radio ConnectionsHardwire Zones and Zone Expansion Zones Smoke Detector NotesReceiver Connections Installing the RF Receiver and Wireless Transmitter ZonesCompatible Receivers RF Receiver No. of ZonesModule Installing a 5800TMInstalling Transmitter Battery LifeKeyswitch Connections Installing a Keyswitch4204/4229 Relay Modules Powerline Carrier DevicesWith the control as shown below On-Board TriggersPhone Line 4285/4286 Phone Module Phone Module ProblemsBank Audio Alarm Verification Connections AAV, listen-InProgramming Overview About ProgrammingMechanics of Programming Zone Type Definitions Auxiliary Alarm Alarm by NightHr Silent Alarm AlarmResponse Type No AlarmKeyswitch ConfigurableZone Sounds & Timing ∗31-∗39 System Setup Fields ∗20 ∗29Data Field Programming About Data Field ProgrammingDialer Programming ∗40 ∗50 Zone Programming Menu Mode Burglary Dialer DelayDynamic Signaling Delay Dynamic Signaling PrioritySystem Status Report Codes Miscellaneous System Fields Phone Line Monitor Enable Misc. Fault Delay TimeProgram Mode Lockout Options Event Log EnablesPager Programming Fields Pager 1 Report Options 172Pager Delay Option for AlarmsClean Me Option Pager 1 CharactersZone Type 90 Report Codes Configurable Zone Type FieldsConfigurable Zone Type Configurable Zone Type OptionsZone Conditions Represented Entries Configurable Zone Type ChartsKeypad Programming Fields Touch Screen Keypad AUI EnableInstallation and Setup Guide About Zone Programming ∗56 and ∗58 Menu Modes Menu Mode ProgrammingZone Programming Procedure Zones and PartitionsZone Type ZT Hardwire TypeZone Number Summary ScreenEnroll Summary Input Device typeSerial number Entry and Loop Number Entry Loop Number ChangeCompleting Zone Programming ∗58 Expert Programming Mode ProceduresConfirm Zone ProgrammingSerial number To Delete a Serial NumberPartition Wireless Key Programming TemplatesTemplate Number Template DisplayNot Confirmed Wireless Key Predefined Default TemplatesWireless Key Transmitter 5804BD 2-Way Wireless Key TransmitterOutput Identification About Output Device Programming *79/*80 Menu ModeMenu Mode Output Device Mapping Programming Output DevicesOutput Type Relay PositionModule Addresses Menu Mode Defining Output Functions Output Function NoActivated By = Stay Closed Output Action01-08 = zone list ∗ to continue = off = Change Device State = Close for 2 secondsZone List Programming About Zone Lists *81 Menu ModePartition Numbe About Function Keys *57 Menu ModeProgramming Function Keys Function KeyProgramming Zone Descriptors Menu Mode ∗82 About Descriptor Programming *82 Menu ModeAssigning Partition/Custom Message Descriptors Accept First WordSecond 3-Digit Index No Accept Second WordFor Entering Zone Descriptors Character Ascii Chart For Adding Custom WordsProgramming Installer and User Schedules Schedule NumberStart Time Repeat Option = repeat every third week 4 = repeat every fourth weekRandomize For events 01 Digit System Communication and OperationPanel Communication with Central Station Report Code FormatsCode for Type +1/4+1 Report Standard Expanded WhereAdemco Contact ID Some event codes may not apply to certain control panelsCode Definition Level User No Functions Keyfob must be enrolled in system first see Wireless KeySystem Security Codes Attributes ValuesFunction Description Keypad CommandsKeypad Functions Voice KeypadsKeys Displayed as Zone ∗ /1 ∗ /# Setting the Real-Time ClockAlpha Display Fixed Disp Meaning Various System Trouble DisplaysInstallation and Setup Guide System Test Testing the SystemAbout Test Procedures Checking Transmitter Enrollment Sniffer ModeAutomatic Periodic Test Report Go/No Go Test ModeAutomatic Standby Battery Tests Dialer Communication Test and Periodic Test ReportsCommunication Specifications & AccessoriesSecurity Control ElectricalDetector Type Wire Smoke DetectorSeries Transmitter Input Loop Identification Compatible 5800 Series Transmitters TableModel Product Input Type Description 5827 Wireless Keypad Can be used to turn the burglary protection on and offTo be transmitted Industrie Canada Regulatory Agency StatementsUL Notices Page Installation and Setup Guide Page Installation and Setup Guide Limitations of this Alarm System Limitations and Warranty10-8 Index 10-10 Summary of Connections K5305-1V5 10/04 Rev. a Limited Warranty