Honeywell VISTA-15PSIA Menu Mode Defining Output Functions, Output Function No, Activated By

Page 46

Installation and Setup Guide

*80 Menu Mode: Defining Output Functions

Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components:

Output Definition Components

Component

Description

Output Function No.

A reference number that defines an output’s characteristics.

Activated By

Determines whether the initiating event occurs on a zone, a zone list, or a zone type.

Event

Event that triggers the output action. Can be an event occurring on a specific zone number or

 

a zone list, or a specific zone type.

Partition

If the output is activated by zone type, this defines the partition in which the programmed

 

event is to cause the device action.

Output Action

Defines the action of the relay/X-10 device when the defined event occurs. Can close for 2

 

seconds, stay closed until reset, continuously pulse (1-second close-open-close-open, etc.),

 

toggle the device state, or activate for a defined duration (set in data field *177).

Output No.

Assigns this function to a specific output number (defined in *79 Menu Mode). This is the

 

output number that will perform this function upon the triggering event. Note that each

 

defined function is associated with only one output number. This means that if more than one

 

output device needs to perform this particular function, you need to define another output

 

function number with the same attributes, but assign the appropriate output number. (i.e.

 

output devices can be assigned more than one function number, but each function number can

 

only be assigned a single output number.

For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to output number 2 (as programmed in *79 Menu Mode), program the following in *80 Menu Mode:

Prompt

 

Entry

Output Funct. #

=

01

(assuming this is the first output function)

Activated By:

=

3 (zone number)

Enter Zn No.

=

04

(requires 2-digit zone numbers)

Output Action

=

3 (continuous pulse)

Output Number

=

02

(device mapped in *79 Menu Mode)

Start Output Definition mode by pressing 80 while in Data Programming mode.

80 Menu Mode

 

 

 

Output Function No.

 

Output Funct. #

 

 

 

VISTA-20P: 01-48 = output function number; VISTA-15P: 01-24 = output function number

 

(00 = Quit)

01

 

[] to continue; 00 to quit

 

 

 

Enter the output function number to be defined (or 00 to exit).

 

 

 

 

 

 

 

Summary Screen

 

01 A

E

P Trig

 

[] to continue

 

?00 0

0

– ZL=00

 

This screen displays a summary of the current output programming (for this example, Zone

 

 

 

 

 

 

 

 

List has been selected-this is the default screen).

 

 

 

 

A = Output Action; E = Triggering event; P = Partition; Trig = Trigger type

 

 

 

 

NOTE: A question mark in the summary screen indicates that the device number shown

 

 

 

 

has not been mapped. Use *79 Menu mode to map the device.

 

Activated By

01 Activated By:

0

= delete

Zone List

1 = zone list (go to “A” prompt)

 

2

= zone type (go to “B” prompt)

 

3

= zone number (go to “C” prompt;)

[] to continue

Select where the initiating event for this output definition is to occur as follows:

If you enter “0,” the following prompt appears:

Delete?

0 = NO, 1 = YES

Press 1 to delete this output definition. The system

deletes the output function and any previous programming.

5-10

Image 46
Contents Ademco Vista Series Recommendations for Proper Protection Table Of Contents Table Of Contents Features and Installation Highlights Capabilities and FunctionsCompatible Devices Important Installation Highlights Installer Please ReadDevice Mounting and Wiring the Control Installing the Control Cabinet and PC BoardAuxiliary Device Current Draw Worksheet AC Power, Battery, and Ground Connections Wire Run ChartBasic Connections Connecting the Keypads and Other Addressable DevicesSounder Bell Connections Supervised outputLong Range Radio Connections Table of Device AddressesKeypad Notes Size MA or less 100 mA 300 mA 500 mA 600 mAHardwire Zones and Zone Expansion Smoke Detector Notes ZonesRF Receiver No. of Zones Installing the RF Receiver and Wireless Transmitter ZonesCompatible Receivers Receiver ConnectionsTransmitter Battery Life Installing a 5800TMInstalling ModuleInstalling a Keyswitch Keyswitch ConnectionsPowerline Carrier Devices 4204/4229 Relay ModulesOn-Board Triggers With the control as shown belowPhone Module Problems Phone Line 4285/4286 Phone ModuleAudio Alarm Verification Connections AAV, listen-In BankAbout Programming Programming OverviewMechanics of Programming Zone Type Definitions Alarm Alarm by NightHr Silent Alarm Auxiliary AlarmConfigurable No AlarmKeyswitch Response TypeAbout Data Field Programming System Setup Fields ∗20 ∗29Data Field Programming Zone Sounds & Timing ∗31-∗39Dialer Programming ∗40 ∗50 Dynamic Signaling Priority Burglary Dialer DelayDynamic Signaling Delay Zone Programming Menu ModeSystem Status Report Codes Miscellaneous System Fields Event Log Enables Misc. Fault Delay TimeProgram Mode Lockout Options Phone Line Monitor EnablePager Programming Fields Pager 1 Characters 172Pager Delay Option for AlarmsClean Me Option Pager 1 Report OptionsConfigurable Zone Type Options Configurable Zone Type FieldsConfigurable Zone Type Zone Type 90 Report CodesConfigurable Zone Type Charts Zone Conditions Represented EntriesTouch Screen Keypad AUI Enable Keypad Programming FieldsInstallation and Setup Guide Zones and Partitions Menu Mode ProgrammingZone Programming Procedure About Zone Programming ∗56 and ∗58 Menu ModesSummary Screen Hardwire TypeZone Number Zone Type ZTLoop Number Change Input Device typeSerial number Entry and Loop Number Entry Enroll Summary∗58 Expert Programming Mode Procedures Completing Zone ProgrammingTo Delete a Serial Number Zone ProgrammingSerial number ConfirmTemplate Display Wireless Key Programming TemplatesTemplate Number Partition5804BD 2-Way Wireless Key Transmitter Wireless Key Predefined Default TemplatesWireless Key Transmitter Not ConfirmedProgramming Output Devices About Output Device Programming *79/*80 Menu ModeMenu Mode Output Device Mapping Output IdentificationRelay Position Output TypeModule Addresses Output Function No Menu Mode Defining Output FunctionsActivated By = off = Change Device State = Close for 2 seconds Output Action01-08 = zone list ∗ to continue = Stay ClosedAbout Zone Lists *81 Menu Mode Zone List ProgrammingFunction Key About Function Keys *57 Menu ModeProgramming Function Keys Partition NumbeAbout Descriptor Programming *82 Menu Mode Programming Zone Descriptors Menu Mode ∗82Accept Second Word Accept First WordSecond 3-Digit Index No Assigning Partition/Custom Message DescriptorsCharacter Ascii Chart For Adding Custom Words For Entering Zone DescriptorsSchedule Number Programming Installer and User SchedulesStart Time = repeat every third week 4 = repeat every fourth week Repeat OptionRandomize For events 01 Report Code Formats System Communication and OperationPanel Communication with Central Station DigitWhere Code for Type +1/4+1 Report Standard ExpandedSome event codes may not apply to certain control panels Ademco Contact IDCode Definition Attributes Values Keyfob must be enrolled in system first see Wireless KeySystem Security Codes Level User No FunctionsVoice Keypads Keypad CommandsKeypad Functions Function DescriptionSetting the Real-Time Clock Keys Displayed as Zone ∗ /1 ∗ /#Various System Trouble Displays Alpha Display Fixed Disp MeaningInstallation and Setup Guide Checking Transmitter Enrollment Sniffer Mode Testing the SystemAbout Test Procedures System TestDialer Communication Test and Periodic Test Reports Go/No Go Test ModeAutomatic Standby Battery Tests Automatic Periodic Test ReportElectrical Specifications & AccessoriesSecurity Control CommunicationWire Smoke Detector Detector TypeCompatible 5800 Series Transmitters Table Series Transmitter Input Loop IdentificationModel Product Input Type Description Can be used to turn the burglary protection on and off 5827 Wireless KeypadTo be transmitted Regulatory Agency Statements Industrie CanadaUL Notices Page Installation and Setup Guide Page Installation and Setup Guide Limitations and Warranty Limitations of this Alarm System10-8 Index 10-10 Summary of Connections Limited Warranty K5305-1V5 10/04 Rev. a