Honeywell VISTA-20PSIA Various System Trouble Displays, Alpha Display Fixed Disp Meaning

Page 61

 

 

 

System Operation

 

 

Various System Trouble Displays

 

 

 

 

 

 

Alpha Display

Fixed Disp.

Meaning

 

ALARM CANCELED

CA

will appear if an exit or interior zone contained a fault during closing at the

 

 

 

time the Exit Delay ended (e.g., exit door left open), but the system was

 

 

 

disarmed during the Entry Delay time. The alarm sounder and keypad sound

 

 

 

continuously, but stop when the system is disarmed. No message will be

 

 

 

transmitted to the central station.

 

EXIT ALARM

EA

appears when Exit Delay ends if an exit or interior zone contained a fault

 

 

 

during closing. The alarm sounder and keypad sound continuously until the

 

 

 

system is disarmed (or timeout occurs). An “Exit Alarm” message is sent to the

 

 

 

central station. Also results if an alarm from an exit or interior zone occurs

 

 

 

within 2 minutes after the end of an Exit Delay.

 

CHECK

CHECK

indicates that a problem exists with the displayed zone(s) and requires

 

 

 

attention.

 

ALARM 1xx

1xx

indicates that communication between control and a zone expander or wireless

 

FAULT 1xx

1xx

receiver is interrupted, where “xx” is the device address. Check the wiring and

 

CHECK 1xx

1xx

DIP switch settings on the units.

 

 

91

If field *199 is set to “1,” all ECP module problems are displayed as “91.”

 

 

 

 

 

 

If there are wireless sensors in the system, the Check condition may also be

 

 

 

caused by some change in the environment that prevents the receiver from

 

 

 

receiving signals from a particular sensor.

 

SYSTEM LO BAT

BAT

with no zone number indicates that the system's standby battery is weak.

 

LO BAT

BAT

with a zone number and a once-per-minute beeping at the keypad indicates

 

 

 

that a low-battery condition exists in the wireless sensor displayed (zone “00”

 

 

 

indicates a wireless keypad). If the battery is not replaced within 30 days, a

 

 

 

“CHECK” display may occur.

 

 

 

NOTE: Some wireless sensors contain a non-replaceable long-life battery which

 

 

 

requires replacement of the entire unit at the end of battery life (e.g., Nos.

 

 

 

5802, 5802CP).

 

TELCO FAULT

94

Telephone Line Failure, indicates that a monitored telephone line (if

 

 

 

programmed in field *92) has been cut or disconnected. Depending on how the

 

 

 

system was programmed, the keypad may also produce a trouble sound, and

 

 

 

the external sounder may be activated. Silence by entering installer code +

 

 

 

OFF.

 

Busy-Standby

dl

If this remains displayed for more than 1 minute, the system is disabled.

 

Mode m Comm

CC

The system is in communication with the central station for change of function

 

 

 

or status verification.

 

no display

no display

Power Failure

 

 

 

If there is no keypad display at all and the LEDs are unlit, operating power

 

 

 

(AC and battery) for the system has stopped and the system is inoperative.

 

 

 

If the message “AC LOSS” (Alpha display keypads) or “NO AC” (Fixed-Word

 

 

 

display keypads) is displayed, the keypad is operating on battery power only.

 

 

 

If the battery standby capacity is used up during a prolonged AC power outage,

 

 

 

the control's power will shut down to minimize deep discharge of the battery.

 

Comm. Failure

FC

A communication failure has occurred.

 

Open Circuit

OC

The keypad is not receiving signals from the control; sees an open circuit.

 

Long Rng Trbl

bF

Backup LRR communication failure.

 

Bell Failure

70

Bell supervision failure.

 

RCVR Jam

90

RF jam detected.

 

KEYPAD LOW BAT

00 BAT

Wireless keypad low battery.

 

Phone Okay

Cd

The dialer test has been successful (CID code 601).

 

Dialer Off

dO

The dialer is disabled.

 

Test in Progress

dd

Walk test mode is active(CID code 607).

 

Upload Completed

dC

The upload or download session was completed.

 

Upload Failed

dF

The upload or download session failed before completion.

6-7

Image 61
Contents Ademco Vista Series Recommendations for Proper Protection Table Of Contents Table Of Contents Capabilities and Functions Features and Installation HighlightsCompatible Devices Important Installation Highlights Installer Please ReadDevice Installing the Control Cabinet and PC Board Mounting and Wiring the ControlAuxiliary Device Current Draw Worksheet Wire Run Chart AC Power, Battery, and Ground ConnectionsSounder Bell Connections Connecting the Keypads and Other Addressable DevicesBasic Connections Supervised outputKeypad Notes Table of Device AddressesLong Range Radio Connections Size MA or less 100 mA 300 mA 500 mA 600 mAHardwire Zones and Zone Expansion Zones Smoke Detector NotesCompatible Receivers Installing the RF Receiver and Wireless Transmitter ZonesRF Receiver No. of Zones Receiver ConnectionsInstalling Installing a 5800TMTransmitter Battery Life ModuleKeyswitch Connections Installing a Keyswitch4204/4229 Relay Modules Powerline Carrier DevicesWith the control as shown below On-Board TriggersPhone Line 4285/4286 Phone Module Phone Module ProblemsBank Audio Alarm Verification Connections AAV, listen-InAbout Programming Programming OverviewMechanics of Programming Zone Type Definitions Hr Silent Alarm Alarm by NightAlarm Auxiliary AlarmKeyswitch No AlarmConfigurable Response TypeData Field Programming System Setup Fields ∗20 ∗29About Data Field Programming Zone Sounds & Timing ∗31-∗39Dialer Programming ∗40 ∗50 Dynamic Signaling Delay Burglary Dialer DelayDynamic Signaling Priority Zone Programming Menu ModeSystem Status Report Codes Miscellaneous System Fields Program Mode Lockout Options Misc. Fault Delay TimeEvent Log Enables Phone Line Monitor EnablePager Programming Fields Clean Me Option 172Pager Delay Option for AlarmsPager 1 Characters Pager 1 Report OptionsConfigurable Zone Type Configurable Zone Type FieldsConfigurable Zone Type Options Zone Type 90 Report CodesZone Conditions Represented Entries Configurable Zone Type ChartsKeypad Programming Fields Touch Screen Keypad AUI EnableInstallation and Setup Guide Zone Programming Procedure Menu Mode ProgrammingZones and Partitions About Zone Programming ∗56 and ∗58 Menu ModesZone Number Hardwire TypeSummary Screen Zone Type ZTSerial number Entry and Loop Number Entry Input Device typeLoop Number Change Enroll SummaryCompleting Zone Programming ∗58 Expert Programming Mode ProceduresSerial number Zone ProgrammingTo Delete a Serial Number ConfirmTemplate Number Wireless Key Programming TemplatesTemplate Display PartitionWireless Key Transmitter Wireless Key Predefined Default Templates5804BD 2-Way Wireless Key Transmitter Not ConfirmedMenu Mode Output Device Mapping About Output Device Programming *79/*80 Menu ModeProgramming Output Devices Output IdentificationRelay Position Output TypeModule Addresses Output Function No Menu Mode Defining Output FunctionsActivated By 01-08 = zone list ∗ to continue Output Action= off = Change Device State = Close for 2 seconds = Stay ClosedZone List Programming About Zone Lists *81 Menu ModeProgramming Function Keys About Function Keys *57 Menu ModeFunction Key Partition NumbeProgramming Zone Descriptors Menu Mode ∗82 About Descriptor Programming *82 Menu ModeSecond 3-Digit Index No Accept First WordAccept Second Word Assigning Partition/Custom Message DescriptorsFor Entering Zone Descriptors Character Ascii Chart For Adding Custom WordsSchedule Number Programming Installer and User SchedulesStart Time = repeat every third week 4 = repeat every fourth week Repeat OptionRandomize For events 01 Panel Communication with Central Station System Communication and OperationReport Code Formats DigitCode for Type +1/4+1 Report Standard Expanded WhereSome event codes may not apply to certain control panels Ademco Contact IDCode Definition System Security Codes Keyfob must be enrolled in system first see Wireless KeyAttributes Values Level User No FunctionsKeypad Functions Keypad CommandsVoice Keypads Function DescriptionKeys Displayed as Zone ∗ /1 ∗ /# Setting the Real-Time ClockAlpha Display Fixed Disp Meaning Various System Trouble DisplaysInstallation and Setup Guide About Test Procedures Testing the SystemChecking Transmitter Enrollment Sniffer Mode System TestAutomatic Standby Battery Tests Go/No Go Test ModeDialer Communication Test and Periodic Test Reports Automatic Periodic Test ReportSecurity Control Specifications & AccessoriesElectrical CommunicationDetector Type Wire Smoke DetectorCompatible 5800 Series Transmitters Table Series Transmitter Input Loop IdentificationModel Product Input Type Description Can be used to turn the burglary protection on and off 5827 Wireless KeypadTo be transmitted Industrie Canada Regulatory Agency StatementsUL Notices Page Installation and Setup Guide Page Installation and Setup Guide Limitations of this Alarm System Limitations and Warranty10-8 Index 10-10 Summary of Connections K5305-1V5 10/04 Rev. a Limited Warranty