Honeywell VISTA-15PSIA, VISTA-20PSIA setup guide Dialer Programming ∗40 ∗50

Page 26

Installation and Setup Guide

*32 Fire Alarm Sounder Timeout

0 = yes; sounder timeout after time selected in field 33 1 = no timeout; sounds until manually turned off

This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of the following: 3 pulses – pause – 3 pulses – pause – 3 pulses.

UL fire alarm installations: must be 1.

*33 Alarm Sounder Timeout

0 = No timeout; 1 = 4 min; 2 = 8 min; 3 = 12 min; 4 = 16 min This field determines whether the external sounder will shut off after time allotted, or continue until manually turned off.

UL Installations: For residential fire alarm installation, must be set for a minimum of 4 min (option 1); for UL Commercial Burglary installations, must be minimum of 16 min (option 4).

*34 Exit Delay

00 - 96 = 0 - 96 seconds; 97 = 120 seconds

V20PSIA/V15PSIA: 45 - 96 = 45 - 96 secs; 97 = 120 secs

NOTE: Entries less than 45 will result in a 45-sec delay.

The system waits the time entered before arming entry/exit zones. If the entry/exit door is left open after this time expires, an alarm will occur. Common zones use same delay as partition 1.

UL installations: For UL Commercial Burglar Alarm (Grade AA) and UL Residential Burglar Alarm installations with line security, total exit time must not exceed 60 seconds. For UL Burglar Alarm installations without line security (Grade A), total exit time must not exceed 120 seconds.

SIA Guidelines: minimum exit delay is 45 seconds

*35 Entry Delay 1 (*35), Entry Delay 2 (*36)

*36 00 - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180 secs; 99 = 240 secs

V20PSIA/V15PSIA: 30-96 = 30 - 96 secs;

97 = 120 secs; 98 = 180 secs; 99 = 240 secs

NOTE: Entries less than 30 will result in a 30-sec delay.

Upon entering, the system must be disarmed before the time entered expires, otherwise it sounds an alarm. Common zones use same delay as partition 1.

UL Installations: For UL Residential Burglary Alarm installations, must be set for a maximum of 30 seconds; entry delay plus dial delay should not exceed 1 min. For UL Commercial Burglar Alarm, total entry delay may not exceed 45 seconds.

SIA Guidelines: minimum entry delay is 30 seconds

*37 Audible Exit Warning

0 = no; 1 = yes

Warning sound consists of slow continuous beeps until the last 10 seconds, and then it changes to fast beeps. Sound ends when exit time expires.

SIA Guidelines: must be enabled (enter 1)

V20PSIA/V15PSIA: feature always enabled; field does not exist.

*38 Confirmation Of Arming Ding

0 = no ding; 1 = confirmation ding after arming system

2 = ding after arming from RF button or RF keypad only Confirmation of arming is 1/2-sec external sounder “ding.” If 1 selected, ding occurs when closing report is sent, or at the end of Exit Delay.

If 2 selected, ding occurs upon reception of the wireless arming command.

UL Installations: must be 1 for UL Commercial Burglar Alarm installations.

*39 Power-Up In Previous State

0 = always power-up in a disarmed state

1 = assume the system status prior to power down

When the system powers up armed, an alarm will occur 1 minute after arming if a zone is faulted.

Note that if the previous state was armed Away or Stay, the system will not respond to sensor changes for 1 minute, which allows sensors such as PIRs to stabilize.

UL Installations: must be 1 (power-up in previous state)

SIA Guidelines: must be 1

Dialer Programming (40 – 50)

*40 PABX Access Code or Call Waiting Disable

Enter up to 6 digits if PABX is needed to access an outside line. Do not fill unused spaces. 0–9, # + 11 for ‘’,

# + 12 for ‘#’, # + 13 for a pause (2 seconds)

To clear entries from field, press ∗40∗. If fewer than 6 digits need to be entered, exit by pressing [∗].

Call Waiting: If the subscriber’s phone service has “call waiting” (and is not using PABX), enter “*70” (“#

+11”) plus “# + 13” (pause) as the PABX entry to disable “call waiting” during control panel calls. If the subscriber does not have “call waiting” and is not using PABX, make no entry in this field.

NOTES: 1. The call waiting disable feature cannot be used on a PABX line. 2. Using Call Waiting Disable on a non-call waiting line will prevent successful communication to the central station.

V20PSIA/V15PSIA: If call waiting is used, enter call waiting disable digits as described above, and also set Call Waiting Disable option in field *91.

*41 Primary (*41) and Secondary (*42) Phone No. *42 Enter up to 20 digits. 0–9, # + 11 = ‘’, # + 12 = ‘#’,

# + 13 = pause (2 secs)

If entering fewer than 20 digits, exit by pressing [∗] + next field number. To clear entries, press ∗41∗ or *42* respectively. Do not fill unused spaces.

NOTE: Backup reporting (see field *49) is automatic only if there is a secondary phone number (field ∗42).

*43 Primary/Secondary Account Numbers

*44 Enter 4 or 10 digits, depending on selection in *45 *48 Report Format field. Enter 0–9; # + 11 = B,

*46 # + 12 = C, # + 13 = D, # + 14 = E, # + 15 = F. *43: Partition 1 primary. To clear entries: ∗43∗.

*44: Partition 1 secondary. To clear entries: ∗44∗.

*45: VISTA-20P. Part. 2 prim. To clear entries: ∗45∗.

*46: VISTA-20P. Part. 2 second. To clear entries: ∗46∗.

4-2

Image 26
Contents Ademco Vista Series Recommendations for Proper Protection Table Of Contents Table Of Contents Features and Installation Highlights Capabilities and FunctionsDevice Important Installation Highlights Installer Please ReadCompatible Devices Mounting and Wiring the Control Installing the Control Cabinet and PC BoardAuxiliary Device Current Draw Worksheet AC Power, Battery, and Ground Connections Wire Run ChartBasic Connections Connecting the Keypads and Other Addressable DevicesSounder Bell Connections Supervised outputLong Range Radio Connections Table of Device AddressesKeypad Notes Size MA or less 100 mA 300 mA 500 mA 600 mAHardwire Zones and Zone Expansion Smoke Detector Notes ZonesRF Receiver No. of Zones Installing the RF Receiver and Wireless Transmitter ZonesCompatible Receivers Receiver ConnectionsTransmitter Battery Life Installing a 5800TMInstalling ModuleInstalling a Keyswitch Keyswitch ConnectionsPowerline Carrier Devices 4204/4229 Relay ModulesOn-Board Triggers With the control as shown belowPhone Module Problems Phone Line 4285/4286 Phone ModuleAudio Alarm Verification Connections AAV, listen-In BankMechanics of Programming Programming OverviewAbout Programming Zone Type Definitions Alarm Alarm by NightHr Silent Alarm Auxiliary AlarmConfigurable No AlarmKeyswitch Response TypeAbout Data Field Programming System Setup Fields ∗20 ∗29Data Field Programming Zone Sounds & Timing ∗31-∗39Dialer Programming ∗40 ∗50 Dynamic Signaling Priority Burglary Dialer DelayDynamic Signaling Delay Zone Programming Menu ModeSystem Status Report Codes Miscellaneous System Fields Event Log Enables Misc. Fault Delay TimeProgram Mode Lockout Options Phone Line Monitor EnablePager Programming Fields Pager 1 Characters 172Pager Delay Option for AlarmsClean Me Option Pager 1 Report OptionsConfigurable Zone Type Options Configurable Zone Type FieldsConfigurable Zone Type Zone Type 90 Report CodesConfigurable Zone Type Charts Zone Conditions Represented EntriesTouch Screen Keypad AUI Enable Keypad Programming FieldsInstallation and Setup Guide Zones and Partitions Menu Mode ProgrammingZone Programming Procedure About Zone Programming ∗56 and ∗58 Menu ModesSummary Screen Hardwire TypeZone Number Zone Type ZTLoop Number Change Input Device typeSerial number Entry and Loop Number Entry Enroll Summary∗58 Expert Programming Mode Procedures Completing Zone ProgrammingTo Delete a Serial Number Zone ProgrammingSerial number ConfirmTemplate Display Wireless Key Programming TemplatesTemplate Number Partition5804BD 2-Way Wireless Key Transmitter Wireless Key Predefined Default TemplatesWireless Key Transmitter Not ConfirmedProgramming Output Devices About Output Device Programming *79/*80 Menu ModeMenu Mode Output Device Mapping Output IdentificationModule Addresses Output TypeRelay Position Activated By Menu Mode Defining Output FunctionsOutput Function No = off = Change Device State = Close for 2 seconds Output Action01-08 = zone list ∗ to continue = Stay ClosedAbout Zone Lists *81 Menu Mode Zone List ProgrammingFunction Key About Function Keys *57 Menu ModeProgramming Function Keys Partition NumbeAbout Descriptor Programming *82 Menu Mode Programming Zone Descriptors Menu Mode ∗82Accept Second Word Accept First WordSecond 3-Digit Index No Assigning Partition/Custom Message DescriptorsCharacter Ascii Chart For Adding Custom Words For Entering Zone DescriptorsStart Time Programming Installer and User SchedulesSchedule Number Randomize For events 01 Repeat Option= repeat every third week 4 = repeat every fourth week Report Code Formats System Communication and OperationPanel Communication with Central Station DigitWhere Code for Type +1/4+1 Report Standard ExpandedCode Definition Ademco Contact IDSome event codes may not apply to certain control panels Attributes Values Keyfob must be enrolled in system first see Wireless KeySystem Security Codes Level User No FunctionsVoice Keypads Keypad CommandsKeypad Functions Function DescriptionSetting the Real-Time Clock Keys Displayed as Zone ∗ /1 ∗ /#Various System Trouble Displays Alpha Display Fixed Disp MeaningInstallation and Setup Guide Checking Transmitter Enrollment Sniffer Mode Testing the SystemAbout Test Procedures System TestDialer Communication Test and Periodic Test Reports Go/No Go Test ModeAutomatic Standby Battery Tests Automatic Periodic Test ReportElectrical Specifications & AccessoriesSecurity Control CommunicationWire Smoke Detector Detector TypeModel Product Input Type Description Series Transmitter Input Loop IdentificationCompatible 5800 Series Transmitters Table To be transmitted 5827 Wireless KeypadCan be used to turn the burglary protection on and off Regulatory Agency Statements Industrie CanadaUL Notices Page Installation and Setup Guide Page Installation and Setup Guide Limitations and Warranty Limitations of this Alarm System10-8 Index 10-10 Summary of Connections Limited Warranty K5305-1V5 10/04 Rev. a