Honeywell VISTA-20PSIA, VISTA-15PSIA setup guide 4204/4229 Relay Modules, Powerline Carrier Devices

Page 17

Mounting and Wiring the Control

Connecting Relay Modules, Powerline Carrier Devices and Output Triggers

4204/4229 Relay Modules

1.Mount either remotely or in the control panel.

2.Connect each module to the control’s keypad terminals and set the device addresses as previously described in the Connecting Keypads and Other Addressable Device section. Use the connector harness supplied with the module. Use standard 4-conductor twisted cable for long wiring runs.

VISTA-20P: Up to 16 relays (if no powerline carrier devices are used)

VISTA-15P: Up to 8 relays (if no powerline carrier devices are used)

3.Connect the desired field wiring to the unit's relay contact terminals.

UL For UL installation requirements, refer to the Installation Instructions for the 4204.

4204

RELAY

 

DIP SWITCH

4

 

FOR SETTING DEVICE ADDRESS

TYPICAL

 

(SHOWN "OFF")

 

AND ENABLING/DISABLING TAMPER

 

COVER TAMPER (REED) SWITCH

4-PIN TOUCHPAD PLUG

EITHER OR BOTH

CAN BE USED

TB1

13 14 15 16

RELAY

3

RELAY

2

RELAY

1

1 2 3 4 5 6 7 8 9 10 11 12

C

NC

NO

C

NC

NO

C

NC

NO

C

NC

NO

Powerline Carrier Devices

UL Powerline Carrier devices and the 1361X10 Transformer are not UL Listed for fire or burglary functions and are intended for home automation.

 

 

 

 

YEL

DATA IN

 

 

 

TB2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

FROM CONTROL

 

 

 

 

 

 

 

 

(–) GROUND

 

 

 

 

 

 

 

 

GRN

 

 

 

 

 

 

 

 

DATA OUT

 

 

 

 

 

 

 

 

RED

TO CONTROL

 

 

 

 

 

 

 

 

(+) 12V

4204_conn-1-V0

 

 

 

 

 

Figure 13. 4204 Connections to Control

Supervision: 4204 and 4229 modules are supervised against removal. The module’s device address is displayed as follows if a module is disconnected from the control’s terminals, or if the module cover is removed and the tamper jumper is installed:

Alpha: CHECK xx Wire Expansion FAULT xx Wire Expansion ALARM xx Wire Expansion

Fixed-Glass: lxx (or 91 if field *199 set for 2-digit display) where “xx is the module’s address.

If communication/tamper failure occurs on a device with zones wired to it, all zones on the device will be displayed in their respective partitions.

1.Install the powerline carrier devices according to the instructions included with each. VISTA-20P: Up to 16 devices (if no relays are used)

VISTA-15P: Up to 8 devices (if no relays are used)

2.Use Programming Mode to enter the device house ID in data field*27, and enter the unit code using *79 Output Device menu Mode.

3.See connections diagram in the AC Wiring section for connecting the 1361X10 transformer to the triggers.

You must use a 1361X10 Transformer instead of the 1321 Transformer.

The 1361X10 Transformer provides AC power to the control panel, and also supplies signals from the control panel through the premises AC wiring to the Powerline Carrier devices (which are plugged into AC outlets). You can then make devices that are plugged into Powerline Carrier devices perform various functions in response to commands you enter at the security system keypads.

Canada: Use the PSC04 Powerline Interface as shown below.

8-PIN TRIGGER CONNECTOR

1

KEY

3

4

5

6

7

8

 

 

 

 

 

 

 

(RED)

 

(ORANGE)

(YELLOW)

(GREEN)

(BLUE)

(PURPLE)

(BLACK)

OUTPUT 17

 

+12 AUX.

GND (-)

OUTPUT 18

DATA

COM

SYNC

 

 

 

 

 

 

 

SA4120XM-1 CABLE

 

 

 

 

 

 

 

SYNC

 

 

 

 

 

 

 

BLK

 

 

 

 

 

 

 

GRN

 

 

 

 

 

 

 

COM

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

DATA

 

 

 

 

 

 

 

YEL

X-10 PSC04

POWERLINE INTERFACE

1 2 3 4

MODULAR PHONE CORD (not supplied)

1 - BLACK

2 - RED

3 - GREEN

4 - YELLOW

Figure 14. PSC04 Powerline Interface Connections

2-11

Image 17
Contents Ademco Vista Series Recommendations for Proper Protection Table Of Contents Table Of Contents Capabilities and Functions Features and Installation HighlightsDevice Important Installation Highlights Installer Please ReadCompatible Devices Installing the Control Cabinet and PC Board Mounting and Wiring the ControlAuxiliary Device Current Draw Worksheet Wire Run Chart AC Power, Battery, and Ground ConnectionsSounder Bell Connections Connecting the Keypads and Other Addressable DevicesBasic Connections Supervised outputKeypad Notes Table of Device AddressesLong Range Radio Connections Size MA or less 100 mA 300 mA 500 mA 600 mAHardwire Zones and Zone Expansion Zones Smoke Detector NotesCompatible Receivers Installing the RF Receiver and Wireless Transmitter ZonesRF Receiver No. of Zones Receiver ConnectionsInstalling Installing a 5800TMTransmitter Battery Life ModuleKeyswitch Connections Installing a Keyswitch4204/4229 Relay Modules Powerline Carrier DevicesWith the control as shown below On-Board TriggersPhone Line 4285/4286 Phone Module Phone Module ProblemsBank Audio Alarm Verification Connections AAV, listen-InMechanics of Programming Programming OverviewAbout Programming Zone Type Definitions Hr Silent Alarm Alarm by NightAlarm Auxiliary AlarmKeyswitch No AlarmConfigurable Response TypeData Field Programming System Setup Fields ∗20 ∗29About Data Field Programming Zone Sounds & Timing ∗31-∗39Dialer Programming ∗40 ∗50 Dynamic Signaling Delay Burglary Dialer DelayDynamic Signaling Priority Zone Programming Menu ModeSystem Status Report Codes Miscellaneous System Fields Program Mode Lockout Options Misc. Fault Delay TimeEvent Log Enables Phone Line Monitor EnablePager Programming Fields Clean Me Option 172Pager Delay Option for AlarmsPager 1 Characters Pager 1 Report OptionsConfigurable Zone Type Configurable Zone Type FieldsConfigurable Zone Type Options Zone Type 90 Report CodesZone Conditions Represented Entries Configurable Zone Type ChartsKeypad Programming Fields Touch Screen Keypad AUI EnableInstallation and Setup Guide Zone Programming Procedure Menu Mode ProgrammingZones and Partitions About Zone Programming ∗56 and ∗58 Menu ModesZone Number Hardwire TypeSummary Screen Zone Type ZTSerial number Entry and Loop Number Entry Input Device typeLoop Number Change Enroll SummaryCompleting Zone Programming ∗58 Expert Programming Mode ProceduresSerial number Zone ProgrammingTo Delete a Serial Number ConfirmTemplate Number Wireless Key Programming TemplatesTemplate Display PartitionWireless Key Transmitter Wireless Key Predefined Default Templates5804BD 2-Way Wireless Key Transmitter Not ConfirmedMenu Mode Output Device Mapping About Output Device Programming *79/*80 Menu ModeProgramming Output Devices Output IdentificationModule Addresses Output TypeRelay Position Activated By Menu Mode Defining Output FunctionsOutput Function No 01-08 = zone list ∗ to continue Output Action= off = Change Device State = Close for 2 seconds = Stay ClosedZone List Programming About Zone Lists *81 Menu ModeProgramming Function Keys About Function Keys *57 Menu ModeFunction Key Partition NumbeProgramming Zone Descriptors Menu Mode ∗82 About Descriptor Programming *82 Menu ModeSecond 3-Digit Index No Accept First WordAccept Second Word Assigning Partition/Custom Message DescriptorsFor Entering Zone Descriptors Character Ascii Chart For Adding Custom WordsStart Time Programming Installer and User SchedulesSchedule Number Randomize For events 01 Repeat Option= repeat every third week 4 = repeat every fourth week Panel Communication with Central Station System Communication and OperationReport Code Formats DigitCode for Type +1/4+1 Report Standard Expanded WhereCode Definition Ademco Contact IDSome event codes may not apply to certain control panels System Security Codes Keyfob must be enrolled in system first see Wireless KeyAttributes Values Level User No FunctionsKeypad Functions Keypad CommandsVoice Keypads Function DescriptionKeys Displayed as Zone ∗ /1 ∗ /# Setting the Real-Time ClockAlpha Display Fixed Disp Meaning Various System Trouble DisplaysInstallation and Setup Guide About Test Procedures Testing the SystemChecking Transmitter Enrollment Sniffer Mode System TestAutomatic Standby Battery Tests Go/No Go Test ModeDialer Communication Test and Periodic Test Reports Automatic Periodic Test ReportSecurity Control Specifications & AccessoriesElectrical CommunicationDetector Type Wire Smoke DetectorModel Product Input Type Description Series Transmitter Input Loop IdentificationCompatible 5800 Series Transmitters Table To be transmitted 5827 Wireless KeypadCan be used to turn the burglary protection on and off Industrie Canada Regulatory Agency StatementsUL Notices Page Installation and Setup Guide Page Installation and Setup Guide Limitations of this Alarm System Limitations and Warranty10-8 Index 10-10 Summary of Connections K5305-1V5 10/04 Rev. a Limited Warranty