Minimum Clearances
The New Buck Corporation Model 80 must be installed in compliance with the instructions contained in this manual.
Clearance from combustible walls and ceilings. (Using single wall chimney connector)
The minimum lateral distance between any part of the room heater and combustible wall is shown in Figures 6 and 7.
FIGURE 6 | FIGURE | 7 |
FLOOR PROTECTION
If a freestanding model is to be installed on a combustible floor, a
The unit must be positioned on the pad so that there is a minimum of 16" from the front of the door opening to the front of the pad, and a minimum of 8" measured horizontally from the sides of the fuel loading and ash removal openings to the sides of the pad.
NOTE: For clearance reductions using wall protectors, refer to the
TOOLS FOR INSTALLATION
Drop Cloth
Electric Drill with 7/32" drill bit 1/2" - 9/16" combination wrench
3/8" magnetic socket chuck adapter, 3/8" wrench (box or socket) or adjustable wrench Socket Set
Tape Measure Pencil Level Screw Driver