Roberts Gorden DAT115, DAT75, DAT90 AIR Supply, Room Sealed Installation, Open Flued Installation

Page 19

SECTION 7: AIR SUPPLY

SECTION 7: AIR SUPPLY

7.1 Room Sealed Installation

When installed as a room sealed heater, the air for combustion is drawn in from outside the building. It is important to ensure that there is adequate ventilation to provide air for the distribution fan/s.

7.2 Open Flued Installation

Ensure adequate air supply at all times for both combustion and heating requirements in accordance with local and national codes. The air supply to the heater must be fitted with a low resistance terminal to prevent the ingress of debris. See Page 12, Figure 7.

7.2.1Heaters Installed Within the Heated Space Where the volume of the heated space is greater

than 4.7 m3 per kilowatt of total rated heat input and the air change rate is at least 0.5/h, additional high and low level ventilation will not be required.

For a building having an air change rate less than 0.5/h, ventilation will be necessary in accordance with local and national codes. Ventilation direct to outside must be provided as follows:

Heaters above 70 kW heat input = 350 cm2 + 2.5 cm2 per kW of rated heat input above 70 kW

7.3 Building Ventilation

Where ventilation is required, air must be taken from an outside point where it is not likely to be contaminated or obstructed.

Where natural ventilation is used, suitable ventilation with outside air at low level must be provided in accordance with Section 7.2.1 and local and national codes.

Where mechanical ventilation is used, extract rate must be 5% - 10% less than the inlet rate. The mechanical ventilation must be interlocked with the burner on the heater.

7.4 Isolated Equipment Rooms

Ventilation must prevent the isolated equipment room temperature from exceeding 32°C as well as prevent any negative air pressure within the room. See Page 13, Figure 9. Any isolated equipment room containing air heaters will require permanent air vents direct to outside air in compliance with local codes.

Where natural ventilation is used, suitable permanent openings at low and high level, communicating directly with the outside air, must be provided.

Where mechanical ventilation is used, extract rate must be 5% - 10% less than the inlet rate. The mechanical ventilation must be interlocked with the burner on the heater.

Figure 9: DualAir® Units Installed in Isolated Equipment Rooms

Duct distribution

system or

discharge to

heated space.

Manifold

Air Intake

Flue

High level ventilation

Return air duct from heated space or fresh air from outside

Max Temperature 32° C

Room air pressure must not be negative.

Wall

Low level ventilation

Outside

Wall

13

Image 19
Contents DualAir Page Roberts-Gordon, LLC Page Table of Figures Page Product Approval Corrosive Chemicals Heater SafetyInstaller Responsibility Clearances to CombustiblesVentilation Minimum Required Installation ClearancesCritical Considerations 3.1 Basic Information Location and Suspension All modelsInstallation Clearances and Clearances to Combustibles Front View Left Version Specifications 4.1 DATModel 100 115 Fan Data General Technical Data TableModel 100 115 2 DAT100 and 115 4 kW motor Handling Heater Installation 5.1 GeneralShelf Mounting and Suspension Flue Conversion Flue Installation 6.1 Flue Installation Type B22 Appliance Air Intake Terminal CoverControl Section & Upper Panel Vertical and Horizontal Flue Termination Type B22 Appliance Building Ventilation Room Sealed InstallationOpen Flued Installation AIR Supply7700 Optional Heater Configurations 8.1 Distribution DuctDepartment for recommendations regarding Duct resistance and design. Tel +44 0 121Connections GAS PipingModels Wiring and Electrical InformationRemote Control See Page 17, .3 through Page 18, SectionNumber See Page 20, Section DAT Wiring DiagramSite wiring connections shown DAT Site Connections at Main Circuit Board Commissioning Automatic Burner Control Box Sequence Set Minimum Pressure Combustion TestingCommissioning the Gas Valves Commissioning the Gas ValveInstruction to the User Pressure SwitchTurning Off the DualAir Unit Complete the CommissioningSecondary Limit Thermostat Heater OperationCommon User Controls Combination Fan/Limit Thermostat See Page 7, .3 and Page 8, FigureCooling Section Operation Burner Lockout Reset ButtonSimple Fault Finding Simple Fault Finding burner faultsIf you smell gas Servicing 13.1 Servicing Instructions Burner Maintenance13.3 Fan/Motor Assembly Maintenance Heat Exchanger MaintenanceGas Control Valve Maintenance Burner Conversion Conversion Between Gases 14.1 GeneralGas Valves Conduct Commissioning procedure as shown on Page 21, Section Result in death or electrical shock Troubleshooting For Automatic Ignition Burner SystemsStart Troubleshooting for Flame Supervision SystemTroubleshooting for Main Fan Troubleshooting for Solenoid ValvesConduct Commissioning procedure as on Page 21, Section Troubleshooting for Fan ContactorGas Valve Removal and Replacement PartsGas Valve Replacement all models Burner ComponentsBurner Injectors Burner CompartmentIgnition Electrode and Flame Probe Remove screws securing outlet flange to the flue adapter See Page 21, Section Heater Pressure SwitchCoil Pressure Switch Pressure SwitchesFilter Pressure Switch 16.7.1 S4563C Ignition ControlFan Motor Removal Fan Removal and Replacement BREAK-OFF Link Must be Removed Page Some objects can catch fire or explode when placed
Related manuals
Manual 52 pages 20.28 Kb