Roberts Gorden DAT100, DAT75, DAT90 Servicing 13.1 Servicing Instructions, Cooling Equipment

Page 34

DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 13: SERVICING 13.1 Servicing Instructions

After commissioning, the DualAir® unit will require maintenance to be carried out annually. If the DualAir® unit is used in a dirty or dusty area, more frequent maintenance may be necessary.

Installation, service and annual inspection of heater must be done by a contractor qualified in the installation and service of gas-fired heating equipment.

WARNING

Cut Hazard

Turn off gas and electrical supply before maintenance. Fan can start automatically at any time.

Failure to follow these instructions can result in severe injury or product damage.

NOTE 1: After any maintenance or repair work always test fire the heater in accordance with the commissioning instructions on Page 21, Section 11

through Page 24, Section 11.9 to ensure all safety

systems are in working order before leaving the heater to operate. Minor faults may be traced by using the troubleshooting charts on Page 31,

Section 15 through Page 34, Section 15.5.

NOTE 2: Check all gas pipes and pipe joints to ensure there are no cracks or gas leaks.

NOTE 3: Inspect all suspended components and hardware. Insure that they are in good condition, properly tightened, and corrosion free.

13.1.1 Cooling Equipment

The cooling coil does not require maintenance except that during filter replacement it is recommended to clean the surface of the coil with a soft brush and vacuum cleaner. Carry out any maintenance recommended by the condenser manufacturer.

13.1.2 Filters

The air filters should be inspected regularly to ensure that no excessive build up of deposit is being experienced. If heavy deposit is being formed, then the filters may be cleaned using a vacuum cleaner. Filters should be replaced at least every four months

to ensure that adequate air flow.

The cooling equipment will automatically turn off should the air flow drop to a preset low value even though the fan will still run. The maximum resistance across a dirty filter should be no more than 150 Pa (1.5 mbar) and the dirty filter warning light will be on. A resistance higher than this indicates that the filters must be replaced.

13.2 Burner Maintenance

1.Open the hinged door and remove the burner compartment cover. See Page 37, Section 16.2.

2.Clean any deposits from the main burner which may have formed in the injectors or venturi of the burner. See Page 37, Section 16.2.

3.Remove the ignition electrode and flame probe. Check condition of ignition electrode and flame probe. Clean off any deposits which may have been formed, check condition of ceramic insulators. Replace as necessary.

13.3 Fan/Motor Assembly Maintenance

The main fan bearings are permanently sealed and do not need lubrication. Before cleaning, turn off gas and electrical supply. Remove the fan compartment covers and use a small brush or duster to clean the fan blades from each side. Replace fan(s) when done.

Figure 16: Belt Tension

8 mm to 10 mm

Fan

MotorPulley

Pulley

Check the condition and tension of the drive belts. The condition is best inspected with the belts removed. Check for chaffing or lateral cracks. Replace belts as a matched pair as necessary.

Do not over-tighten belts, as this may cause bearing damage.

13.4 Heat Exchanger Maintenance

The heat exchanger will remain clean unless a problem has developed with combustion. Inspect the heat exchanger. Look for signs of overheating at the front tubes which may indicate burner over firing or persistently low air flows.

28

Image 34
Contents DualAir Page Roberts-Gordon, LLC Page Table of Figures Page Product Approval Clearances to Combustibles Heater SafetyInstaller Responsibility Corrosive ChemicalsLocation and Suspension All models Minimum Required Installation ClearancesCritical Considerations 3.1 Basic Information VentilationInstallation Clearances and Clearances to Combustibles Specifications 4.1 DAT Front View Left VersionGeneral Technical Data Table Model 100 115 Fan DataModel 100 115 2 DAT100 and 115 4 kW motor Handling Heater Installation 5.1 GeneralShelf Mounting and Suspension Air Intake Terminal Cover Flue Installation 6.1 Flue InstallationType B22 Appliance Flue ConversionControl Section & Upper Panel Vertical and Horizontal Flue Termination Type B22 Appliance AIR Supply Room Sealed InstallationOpen Flued Installation Building VentilationDuct resistance and design. Tel +44 0 121 Optional Heater Configurations 8.1 Distribution DuctDepartment for recommendations regarding 7700GAS Piping ConnectionsSee Page 17, .3 through Page 18, Section Wiring and Electrical InformationRemote Control ModelsNumber DAT Wiring Diagram See Page 20, SectionSite wiring connections shown DAT Site Connections at Main Circuit Board Commissioning Automatic Burner Control Box Sequence Commissioning the Gas Valve Combustion TestingCommissioning the Gas Valves Set Minimum PressureComplete the Commissioning Pressure SwitchTurning Off the DualAir Unit Instruction to the UserSee Page 7, .3 and Page 8, Figure Heater OperationCommon User Controls Combination Fan/Limit Thermostat Secondary Limit ThermostatSimple Fault Finding burner faults Burner Lockout Reset ButtonSimple Fault Finding Cooling Section OperationIf you smell gas Heat Exchanger Maintenance Burner Maintenance13.3 Fan/Motor Assembly Maintenance Servicing 13.1 Servicing InstructionsGas Control Valve Maintenance Burner Conversion Conversion Between Gases 14.1 GeneralGas Valves Conduct Commissioning procedure as shown on Page 21, Section Troubleshooting For Automatic Ignition Burner Systems Result in death or electrical shockTroubleshooting for Flame Supervision System StartTroubleshooting for Solenoid Valves Troubleshooting for Main FanTroubleshooting for Fan Contactor Conduct Commissioning procedure as on Page 21, SectionBurner Components Removal and Replacement PartsGas Valve Replacement all models Gas ValveBurner Compartment Burner InjectorsIgnition Electrode and Flame Probe Remove screws securing outlet flange to the flue adapter Heater Pressure Switch See Page 21, SectionCoil Pressure Switch Pressure SwitchesFilter Pressure Switch 16.7.1 S4563C Ignition ControlFan Motor Removal Fan Removal and Replacement BREAK-OFF Link Must be Removed Page Some objects can catch fire or explode when placed
Related manuals
Manual 52 pages 20.28 Kb