Roberts Gorden DAT75, DAT90 Troubleshooting for Solenoid Valves, Troubleshooting for Main Fan

Page 40

DUALAIR® HEATING AND COOLING UNITS INSTALLATION OPERATION AND SERVICE MANUAL

15.4 Troubleshooting for Solenoid Valves

START

Is 230v at the valve

terminals at the appropriate time.

Yes

Is gas pressure at inlet of the valve correct for gas type?

Note pressure found.

Yes

Does gas pressure at outlet

of the valve rise when

valve turns on?

Yes

Does gas pressure at

outlet of valve return to zero or

lower when valve turns off?

Yes

Valve Operating

TROUBLESHOOT ENDS.

No

Fault elsewhere

No

Fault elsewhere

Valve faulty.

No Replace with one of correct type.

Valve faulty.

No Replace with one of correct type.

If problems persist, contact

No

ROBERTS GORDON® at

Tel: +44(0) 190 249 8733

 

 

or www.rg-inc.com

15.5 Troubleshooting for Main Fan

START

Does fan run

automatically? No

Yes

Does fan turn on and

off while burner is firing Yes continously?

No

Fan Operating

TROUBLESHOOT ENDS. No

Is Power supply 400 V

between any two phases or 230 V between any Phase and No N at the main terminal block?

Yes

Does fan run when the white button of combination fan/limit No

thermostat is pushed in?

Yes

Use Section 5.3 & 11.3 to check

combination fan/limit

thermostat settings. Reset or

replace as necessary.

If problems persist, contact ROBERTS GORDON® at Tel: +44(0) 190 249 8733 or www.rg-inc.com

Fault elsewhere.

Check wiring.

Is there 230v between

No

Combination fan/limit

terminals 1 and N of the

thermostat faulty.

main terminal block?

 

Replace with correct type.

Yes

 

 

Fan motor or contactor faulty.

 

 

Replace with correct type.

 

 

Use Section 15.6 to

 

 

trace fault.

 

 

For your safety and optimum heater performance use only ROBERTS GORDON® replacement parts.

Conduct Commissioning procedure as shown on Page 21, Section 11

34

Image 40
Contents DualAir Page Roberts-Gordon, LLC Page Table of Figures Page Product Approval Heater Safety Installer ResponsibilityClearances to Combustibles Corrosive ChemicalsMinimum Required Installation Clearances Critical Considerations 3.1 Basic InformationLocation and Suspension All models VentilationInstallation Clearances and Clearances to Combustibles Specifications 4.1 DAT Front View Left VersionGeneral Technical Data Table Model 100 115 Fan DataModel 100 115 2 DAT100 and 115 4 kW motor Handling Heater Installation 5.1 GeneralShelf Mounting and Suspension Flue Installation 6.1 Flue Installation Type B22 ApplianceAir Intake Terminal Cover Flue ConversionControl Section & Upper Panel Vertical and Horizontal Flue Termination Type B22 Appliance Room Sealed Installation Open Flued InstallationAIR Supply Building VentilationOptional Heater Configurations 8.1 Distribution Duct Department for recommendations regardingDuct resistance and design. Tel +44 0 121 7700GAS Piping ConnectionsWiring and Electrical Information Remote ControlSee Page 17, .3 through Page 18, Section ModelsNumber DAT Wiring Diagram See Page 20, SectionSite wiring connections shown DAT Site Connections at Main Circuit Board Commissioning Automatic Burner Control Box Sequence Combustion Testing Commissioning the Gas ValvesCommissioning the Gas Valve Set Minimum PressurePressure Switch Turning Off the DualAir UnitComplete the Commissioning Instruction to the UserHeater Operation Common User Controls Combination Fan/Limit ThermostatSee Page 7, .3 and Page 8, Figure Secondary Limit ThermostatBurner Lockout Reset Button Simple Fault FindingSimple Fault Finding burner faults Cooling Section OperationIf you smell gas Burner Maintenance 13.3 Fan/Motor Assembly MaintenanceHeat Exchanger Maintenance Servicing 13.1 Servicing InstructionsGas Control Valve Maintenance Burner Conversion Conversion Between Gases 14.1 GeneralGas Valves Conduct Commissioning procedure as shown on Page 21, Section Troubleshooting For Automatic Ignition Burner Systems Result in death or electrical shockTroubleshooting for Flame Supervision System StartTroubleshooting for Solenoid Valves Troubleshooting for Main FanTroubleshooting for Fan Contactor Conduct Commissioning procedure as on Page 21, SectionRemoval and Replacement Parts Gas Valve Replacement all modelsBurner Components Gas ValveBurner Compartment Burner InjectorsIgnition Electrode and Flame Probe Remove screws securing outlet flange to the flue adapter Heater Pressure Switch See Page 21, SectionCoil Pressure Switch Pressure SwitchesFilter Pressure Switch 16.7.1 S4563C Ignition ControlFan Motor Removal Fan Removal and Replacement BREAK-OFF Link Must be Removed Page Some objects can catch fire or explode when placed
Related manuals
Manual 52 pages 20.28 Kb