Heat & Glo LifeStyle EXCLAIM-36T-C, EXCLAIM-36H-C owner manual Height of Chimney Components

Page 17

A. Chimney Requirements

Vertical distances are measured from the base of the fire- place as shown in Figure 5.2.

 

ft

m

• Minimum overall straight height

18

5.49

• Minimum height with offset/return

18.5

5.64

• Maximum height

90

27.43

• Maximum chimney length between an

20

6.10

offset and return

 

 

• Maximum distance between chimney

35

10.67

stabilizers`

 

 

• Double offset/return minimum height

24

7.32

• Maximum unsupported chimney length

6

1.83

between the offset and return

 

 

• Maximum unsupported chimney height

35

10.67

above the fireplace

 

 

• Maximum unsupported chimney above

6

1.83

roof

 

 

To determine the chimney components needed to complete your particular installation, follow the steps below:

Determine the total vertical height of the fireplace installation. This dimension is measured from the base of the fireplace assembly to the point where the smoke exits the termination cap.

Subtract the effective height of the fireplace assembly from the overall height of the fireplace installation (measured from the base of the fireplace to the bottom of the termination cap).

Refer to Table 5.1 to determine what components must be selected to complete the fireplace installation.

Determine the number of ceiling firestops, stabilizers, roof flashing, etc. required to complete the fireplace installation.

Note: A maximum of two pairs of offsets and returns may be used.

WARNING

Fire Risk

Must maintain 2 in. (51 mm) air clearance to insulation and other combustible materials.

Table 5.1

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

 

 

 

SL4

4-3/4

121

Ceiling Firestops

 

 

 

FS538

0

0

 

 

 

 

 

FS540

0

0

Offsets/Returns

 

 

 

SL430

14-1/2

368

Roof Flashing

 

 

6 ft (1.8 m) max. unsupported run

20 ft (6 m) max. pipe between an offset & return

Ceiling Firestop

71-3/4 in.

(1822 mm)

Effective Height

(bottom of fireplace

to top of starter collar)

6 ft (1.8 m) max. unsupported chimney above roof

35 ft (10.7 m) max. straight unsupported chimney height

18.5ft (5.6 m) min. height/single offset-return 24 ft. (7.3 m) min. height/double offset-return

90 ft (27.4 m) max. height

 

RF570

0

0

 

 

 

 

 

RF571

0

0

Chimney Sections*

 

 

 

SL406

4-3/4

121

 

SL412

10-3/4

273

 

SL418

16-3/4

425

 

 

 

 

 

SL436

34-3/4

883

 

SL448

46-3/4

1187

* Dimensions reflect effective height.

 

 

Figure 5.2 Chimney Requirements

CAUTION

Do NOT connect this fireplace to a chimney flue servicing another appliance.

Do NOT connect to any air distribution duct or system.

Heat & Glo • EXCLAIM-36C Woodburning Fireplace • 4013-093 Rev G • 08/06

17

Image 17
Contents Fire Risk EXCLAIM-36H-C EXCLAIM-36T-CNumber Listing Label Information/LocationGrate Table of Contents Not intended for use as a primary heat source Listing and Code ApprovalsAppliance Certification Getting Started Design and Installation ConsiderationsNegative Pressure Asphyxiation RiskMarginal Location Typical Fireplace System Typical Fireplace SystemFire Risk Explosion Risk Tools and Supplies NeededInspect Fireplace and Components Selecting Fireplace Location Framing and ClearancesFailure to comply may cause fire ClearancesFrame the Fireplace Sidewalls/SurroundsChimney Requirements Construct the ChaseInstall the Outside Air Kit Installation of FireplaceFire Risk Sharp Edges Asphyxiation Risk Risk of Smoke SpillageFt min. from top of uppermost chimney section to air inlet Position the Fireplace Secure the FireplacePlace the Protective Metal Hearth Strips Level the FireplaceChimney Assembly Height of Chimney Components ¨ Table Using Offsets/ReturnsAssemble the Chimney Sections Install the Ceiling FirestopsSecure the Chimney Install the Attic Insulation ShieldDouble-check the Chimney Assembly Chimney Termination Complete the EnclosureChase Top Install the Termination CapInstall the Chimney Air Kit required in Canada Installing an ST475 Square Termination Cap Gas Code, Ansi Z223.1 AccessoriesGas Log/Lighter Provisions Hearth Extension FinishingRaised Hearth Extension Mantel Finishing MaterialGlass Doors Combustible MaterialGeneral Information Operating InstructionsClear Space Near the Fireplace Outside AirFlue Damper FirescreenWood Fuel GrateFirewood MoistureStarting a Fire Understanding Vent Problems TroubleshootingDiagnostic Questions Diagnostics and Problem SolvingSolutions Can’t get a good fire going. What am I doing wrong?fireplace burns the wood too fast. What can I do? Chimney Inspection/Cleaning Maintenance and Servicing the FireplaceDisposal of Ashes Firebox RefractoryWhen cleaning glass door Maintenance Task ListClean Chimney FireReference Materials Fireplace DimensionsCatalog # Description Fireplace ComponentsCatalog # Chimney Components330 mm 51 mm 14-3/4 375 mm This page intentionally left blank Minimum Base Dimensions 26.5 X 28 with 34 X 34 with Minimum Base Dimensions 28 X 28 with 32 X 32 with 23 XTR442 TR442 / 444 TV 20 xService Parts Service Parts EXCLAIM-36-C SeriesDescription of Part EXCLAIM-36T-C EXCLAIM-36H-C Qty.req This page intentionally left blank Limited Warranty Warranty For Heat & GLO FireplacesDo Discardnot Contact Information