4 | Installation of Fireplace |
|
|
|
|
|
|
| |
|
|
|
|
|
| CAUTION |
| WARNING |
|
|
|
| Fire Risk |
|
| Sharp Edges |
|
| |
|
| Asphyxiation Risk |
| |
| • Wear protective gloves and safety glasses |
|
| |
|
| Do not draw outside combustion air from: |
| |
| during installation. |
|
| |
|
| • Wall, floor or ceiling cavity. |
| |
|
|
|
| |
|
|
| • Enclosed space such as an attic or |
|
|
|
| garage. |
|
A. Install the Outside Air Kit |
| |||
| • Close proximity to exhaust vents or |
| ||
This fireplace will operate correctly only if adequate ventila- |
| chimneys. |
| |
tion is provided to allow proper draft to the fireplace system. |
| Fumes or odor may result. |
| |
See Section 2. |
|
|
| |
|
|
|
The outside air kit is supplied with this fireplace and its use is highly recommended to minimize the effects of negative pressure within the structure. We recommend you utilize the shortest duct run to optimize the performance of the outside air kit. Cold air flow can be minimized by putting a small dip in the duct creating a cold air trap. This trap can also help prevent heat
See Figure 4.3 for proper placement of outside air inlet.
The outside air kit is installed on the left hand side of the fireplace. See Figure 4.4 for handle location/operation.
CAUTION
Risk of Smoke Spillage
Outside air inlet must be located to prevent blockage from:
•Leaves
•Snow/ice
•Other debris
Blockage may cause combustion air starvation.
| Flexible Duct |
|
|
| (not supplied) |
|
|
Outside Air |
|
|
|
Shield | 2 Wire Ties | Inlet Ring |
|
Figure 4.1 Outside Air Installation |
|
| |
Heat & Glo • | 13 |