Heat & Glo LifeStyle EXCLAIM-36H-C, EXCLAIM-36T-C Chase Top, Install the Termination Cap

Page 22

Install the Chimney Air Kit (required in Canada):

When installing the chimney air kit, follow the instructions provided with this accessory.

B. Chase Top

A metal chase top is required to seal the top of the chase around the chimney pipe. The top should include a turn- down and drip edge to prevent water from seeping into the chase. Provide a 1/8 in. (3 mm) gap around the flue pipe and slope the top downward away from the penetration. See Figure 6.4.

All seams must be caulked to prevent leaks.

A chase installation must use a chase top. Chase tops are available from your Heat & Glo dealer or may be field constructed.

Attach the chase top to the top of the chase.

Termination Cap

C. Install the Termination Cap

Note: To protect against the effect of corrosion on those parts exposed to the weather, the termination cap can be painted with a rust-resistant paint.

WARNING

Fire Risk

The minimum overlap of cap to pipe MUST be met or chimney may separate from cap.

Separation allows sparks, heat and embers to escape.

Install the chimney sections up through the chase

enclosure. When using a TR444 Round Termination

Cap, the uppermost top section of pipe must extend 6 in.

(152 mm) above the top of the flashing collar to allow

Caulk

2 in. (51 mm) Collar on Chase Top

Storm Collar

Slope Downward

installation of the storm collar and termination cap. See

Figure 6.5.

Minimum 1-1/2 in. (38 mm) overlap of cap over pipe

Turn-down Drip Edge

Chase (Chimney)

.018 (26 ga) min. Galvanized Chase Top

Figure 6.4 Chase Top Construction

Storm Collar

2 in. (51 mm) min.

6 in. (152mm) min.

 

 

 

 

 

 

Flashing Collar

 

 

 

2 in. (51 mm) min. collar

 

 

Figure 6.5 Installing a TR444 Round Termination Cap

For installations utilizing a TR442 Round Telescoping Termination Cap, the uppermost chimney section must be below the top of the chase top, but not more than 14-1/2 in. (368 mm) below the top of the chase top. Minimum overlap of chimney and termination cap must be 1-1/2 in. (38 mm). See Figure 6.6.

 

 

 

Storm Collar

Flashing Collar

2 in. (51 mm) min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14-1/2 in. (368mm) max.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top of Pipe

 

 

 

1-1/2 in. (38 mm) min.

 

 

 

 

 

 

overlap

Figure 6.6 Installing a TR442 Round Telescoping Termination Cap

22

Heat & Glo • EXCLAIM-36C Woodburning Fireplace • 4013-093 Rev G • 08/06

Image 22
Contents EXCLAIM-36H-C EXCLAIM-36T-C Fire RiskGrate Listing Label Information/LocationNumber Table of Contents Appliance Certification Listing and Code ApprovalsNot intended for use as a primary heat source Negative Pressure Design and Installation ConsiderationsGetting Started Asphyxiation RiskMarginal Location Typical Fireplace System Typical Fireplace SystemInspect Fireplace and Components Tools and Supplies NeededFire Risk Explosion Risk Framing and Clearances Selecting Fireplace LocationClearances Failure to comply may cause fireSidewalls/Surrounds Frame the FireplaceConstruct the Chase Chimney RequirementsFire Risk Sharp Edges Asphyxiation Risk Installation of FireplaceInstall the Outside Air Kit Risk of Smoke SpillageFt min. from top of uppermost chimney section to air inlet Place the Protective Metal Hearth Strips Secure the FireplacePosition the Fireplace Level the FireplaceChimney Assembly Height of Chimney Components Using Offsets/Returns ¨ TableInstall the Ceiling Firestops Assemble the Chimney SectionsDouble-check the Chimney Assembly Install the Attic Insulation ShieldSecure the Chimney Complete the Enclosure Chimney TerminationInstall the Chimney Air Kit required in Canada Install the Termination CapChase Top Installing an ST475 Square Termination Cap Gas Log/Lighter Provisions AccessoriesGas Code, Ansi Z223.1 Finishing Hearth ExtensionRaised Hearth Extension Glass Doors Finishing MaterialMantel Combustible MaterialOperating Instructions General InformationFlue Damper Outside AirClear Space Near the Fireplace FirescreenFirewood GrateWood Fuel MoistureStarting a Fire Troubleshooting Understanding Vent ProblemsSolutions Diagnostics and Problem SolvingDiagnostic Questions Can’t get a good fire going. What am I doing wrong?fireplace burns the wood too fast. What can I do? Disposal of Ashes Maintenance and Servicing the FireplaceChimney Inspection/Cleaning Firebox RefractoryClean Maintenance Task ListWhen cleaning glass door Chimney FireFireplace Dimensions Reference MaterialsFireplace Components Catalog # DescriptionChimney Components Catalog #330 mm 51 mm 14-3/4 375 mm This page intentionally left blank TR442 TR442 / 444 TV Minimum Base Dimensions 28 X 28 with 32 X 32 with 23 XMinimum Base Dimensions 26.5 X 28 with 34 X 34 with 20 xService Parts EXCLAIM-36-C Series Service PartsDescription of Part EXCLAIM-36T-C EXCLAIM-36H-C Qty.req This page intentionally left blank Warranty For Heat & GLO Fireplaces Limited WarrantyContact Information Do Discardnot