Heat & Glo LifeStyle EXCLAIM-36T-C Finishing Material, Mantel, Glass Doors, Combustible Material

Page 27

B. Finishing Material

Combustible Material

Material which is made of or surfaced with wood, compressed paper, plant fibers, plastics, or any material capable of igniting and burning, whether flame proofed or not, plastered or not plastered.

Non-Combustible Material

Material which will not ignite and burn. Such materials are those consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof.

Materials that are reported as passing ASTM E 136,

Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750° C, shall be considered non-combustible materials.

Non-Combustible Sealant Material

Sealants which will not ignite and burn: Rutland, Inc. Fireplace Mortar #63 (or equivalent).

After completing the framing and applying the facing material (drywall) over the framing, a bead of non-combustible seal- ant must be used to close off any gaps at the top and sides between the fireplace and facing to prevent cold air leaks. Large gaps can be bridged with fiberglass rope gasket.

Only non-combustible materials may be used to cover the metal fireplace front.

WARNING

Fire Risk

Use only non-combustible material below standoffs.

Material such as cement board is acceptable.

C. Mantel

A combustible mantel may be positioned no lower than 12 in. (305 mm) above the top of the fireplace opening. The combustible mantel may have a maximum depth of 12 in. (305 mm). Combustible trim pieces that project no more than 1-1/2 in. (38 mm) from the face of the fireplace can be placed no closer than 6 in. (152 mm) from the top of the fireplace opening. See Figure 8.6. Combustible trim must not cover the metal surfaces of the fireplace. This mantel clearance is in accordance with Section 7-3.3.3 of ANSI/ NFPA211.

WARNING

Fire Risk

Do NOT obstruct air inlet or outlet grilles.

Finishing materials must not interfere with:

Air flow

Operation of doors

Access for service

D.Sidewalls/Surrounds

Adjacent combustible side walls must be located a minimum of 12 in. (305 mm) from the fireplace opening. If you are us- ing a decorative surround constructed of combustible ma- terial, it must be located within the shaded area defined in Figure 8.7. Short stub walls are also acceptable if they are contained within the shaded area.

E. Glass Doors

This fireplace has been tested and listed for use with doors as specified in Section 12.B. Fireplace Components. Please refer to the manual packed with each set of doors for instal- lation instructions.

Note: The frame of the AED door overlaps the front of the fireplace beyond the opening by 3/4 in. (19 mm) on each side and 1-1/2 in. (38 mm) above the top. This should be allowed for when applying facing to the front of the fireplace.

WARNING

Fire Risk

Finish all edges and fronts to clearances and specifications.

Metal fireplace front may be covered with non-combustible material only.

Do NOT overlap combustible materials onto fireplace front.

Install combustible materials up to specified clearances on top front and side edges.

Seal joints between the finished wall and fireplace top and sides using only a 300° F minimum sealant.

12 in. (305 mm) 1-1/2 in. (38 mm) max.

 

 

BRICK

4 in.

 

Max.

Header

 

 

 

FLUSH FRONT

FRONT

(102 mm)

Mantel

 

 

 

 

 

 

 

Standoff

 

 

 

 

12 in.

 

23-3/4 in.

36 in.

 

 

Standoff

19-3/4 in.

(305 mm)

 

(603 mm)

(914 mm)

6 in. (152 mm) Min.

(502 mm)

Min.

 

50°

 

(opening)

 

 

 

 

 

 

39°

Top of

 

 

 

 

 

45-1/2 in.

 

 

 

 

 

 

 

 

 

 

 

(1156 mm)

 

Fireplace

 

Gas Knockout

 

 

 

 

 

 

 

 

(framing)

 

Opening

 

 

 

 

12 in.

12 in.

 

 

 

 

 

 

(305 mm)

(305 mm)

 

Figure 8.6

Mantel Specifications

 

Figure 8.7

Sidewalls/Surrounds

 

 

 

Heat & Glo • EXCLAIM-36C Woodburning Fireplace • 4013-093 Rev G • 08/06

27

Image 27
Contents Fire Risk EXCLAIM-36H-C EXCLAIM-36T-CListing Label Information/Location GrateNumber Table of Contents Listing and Code Approvals Appliance CertificationNot intended for use as a primary heat source Asphyxiation Risk Design and Installation ConsiderationsGetting Started Negative PressureMarginal Location Typical Fireplace System Typical Fireplace SystemTools and Supplies Needed Inspect Fireplace and ComponentsFire Risk Explosion Risk Selecting Fireplace Location Framing and ClearancesFailure to comply may cause fire ClearancesFrame the Fireplace Sidewalls/SurroundsChimney Requirements Construct the ChaseRisk of Smoke Spillage Installation of FireplaceInstall the Outside Air Kit Fire Risk Sharp Edges Asphyxiation RiskFt min. from top of uppermost chimney section to air inlet Level the Fireplace Secure the FireplacePosition the Fireplace Place the Protective Metal Hearth StripsChimney Assembly Height of Chimney Components ¨ Table Using Offsets/ReturnsAssemble the Chimney Sections Install the Ceiling FirestopsInstall the Attic Insulation Shield Double-check the Chimney AssemblySecure the Chimney Chimney Termination Complete the EnclosureInstall the Termination Cap Install the Chimney Air Kit required in CanadaChase Top Installing an ST475 Square Termination Cap Accessories Gas Log/Lighter ProvisionsGas Code, Ansi Z223.1 Hearth Extension FinishingRaised Hearth Extension Combustible Material Finishing MaterialMantel Glass DoorsGeneral Information Operating InstructionsFirescreen Outside AirClear Space Near the Fireplace Flue DamperMoisture GrateWood Fuel FirewoodStarting a Fire Understanding Vent Problems TroubleshootingCan’t get a good fire going. What am I doing wrong? Diagnostics and Problem SolvingDiagnostic Questions Solutionsfireplace burns the wood too fast. What can I do? Firebox Refractory Maintenance and Servicing the FireplaceChimney Inspection/Cleaning Disposal of AshesChimney Fire Maintenance Task ListWhen cleaning glass door CleanReference Materials Fireplace DimensionsCatalog # Description Fireplace ComponentsCatalog # Chimney Components330 mm 51 mm 14-3/4 375 mm This page intentionally left blank 20 x Minimum Base Dimensions 28 X 28 with 32 X 32 with 23 XMinimum Base Dimensions 26.5 X 28 with 34 X 34 with TR442 TR442 / 444 TVService Parts Service Parts EXCLAIM-36-C SeriesDescription of Part EXCLAIM-36T-C EXCLAIM-36H-C Qty.req This page intentionally left blank Limited Warranty Warranty For Heat & GLO FireplacesDo Discardnot Contact Information