Heat & Glo LifeStyle 6000 DVTFL, 8000 DVTFL, SL-42 DVT, 6000 ARCH, 6000 XLT manual Hole and Vent Pipe

Page 24
Figure 19. Hole and Vent Pipe

21

1.Cut the hole through the wall.

2.Position the firestops.

3.Place the heat shield to the top.

4.Continue the vent run.

Position the firestops on both sides of the hole previously cut and secure the firestops with nails or screws.

The heat shields of the firestops MUST BE placed towards the top of the hole.

Continue the vent run through the firestops.

Figure 19. Hole and Vent Pipe

HEAT SHIELD

TRIM HEAT

SHIELD IF TOO

 

 

LONG, ADD TO

 

SHIELD IF TOO

 

SHORT.

 

EXTERIOR

 

FIRESTOP

INTERIOR

 

FIRESTOP

 

Figure 20. Heat Shield, Interior and Exterior Firestops

For Vertical Runs - One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes.

To install firestops for vertical runs that pass through ceilings:

Position a plumb bob directly over the center of the vertical vent component.

Mark the ceiling to establish the centerpoint of the vent.

Image 24
Contents Underwriters Laboratories Listed Installers GuideHeat-N-GloFireplace 8000 DVTFLSAFETY AND WARNING INFORMATION THIS UNIT IS NOT FOR USE WITH SOLID FUELPROHIBITED Table of Contents Approvals and Codes and CodesInstallation Codes High Altitude InstallationsPre-installationPreparation Introducing the Heat-N-Glo Gas FireplacesGetting Started ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE HAZARDFigure 1. Diagram of 8000DVTFL Page Figure 3. Diagram of SL-42DVT Installing the Fireplace Step Locating the FireplaceClearance Requirements Step Framing the Fireplace VERIFY FRAMING METHODS AND WALLCOVERING DETAILS, BEFORE FRAMING CONSTRUCTION BEGINSStep Installing the Vent System A. Vent System ApprovalsDV-90D DV-45DDV-48D DV-36D DV-12D4-inchinner pipe/6 5/8-inchouter pipe Figure 9. Vertical Venting VERTICAL VENTING V FT 40 MAX. 12.4 MNOTE MODEL 6000 ARCH Model 6000XLT & 8000DVTFL FOR SL-42DVTNOTE: IF A 90 ELBOW IS FIRST ATTACHED TO THE UNIT, THEVENTING WITH TWO 2 90 ELBOWS Figure 11. Venting with two 90 elbowsNOTE MODEL 6000 ARCH H1 V HVENTING WITH TWO 2 90 ELBOWS Figure 12. Venting with two 90 elbowsNOTE: MODEL 6000 ARCH H V1 VVENTING WITH THREE 3 90 ELBOWS Figure 13. Venting with three 90 elbowsNOTE: MODEL 6000 ARCH VENTING WITH THREE 3 90 ELBOWS Figure 14. Venting with three 90 elbowsB. Installing Vent Components ENSURE THAT THE FIBERGLASS 3. Install Support Brackets To install support brackets for horizontal runsFigure 17. Adding Venting Components •Place the pipe supports around the vent pipeFigure 18. Installing Support Brackets 4. Install FirestopsFor Horizontal Runs - Firestops are REQUIRED Model DVK-01TRDand SLK-01TRDdo not needFigure 19. Hole and Vent Pipe Figure 21. Hole and New Framing Members Figure 22. Ceiling Firestop Ceiling SideC. Vent Termination Figure 23. Attic FirestopFigure 24. Round and Trapezoid Termination Caps VINYL SIDING, IT IS NECESSARY TO INSTALL IF EXTERIOR WALLS ARE FINISHED WITHTHE VINYL PROTECTOR KIT TO THE TOP OF TERMINATION CAPSMAJOR U.S. BUILDING CODES on the outside of the buildingRoof Pitch Step Positioning Leveling, and Securing the FireplaceStep The Gas Control Systems Step The Gas Supply Line Figure 28. Gas Controls Systems13 mm hook-upat the unit DO NOT USE AN OPEN FLAME TO CHECK FOR GAS LEAKSStep Gas Pressure Requirements Figure 29. Gas Supply LinePressure Natural GasStep Wiring the Fireplace For Standing Pilot Ignition WiringElectrical wiring must be installed by a licensed LABEL ALL WIRES PRIOR TO DISCONNECTIONWHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER ANDStep Finishing Step Installing Trim Logs, and Ember Material Hearth ExtensionsPositioning the Logs Save the log instructions with this manualPlacing the Ember Material Figure 35. Glass Assembly Figure 36. Placement of the Ember Material1.Lift the trim door up and out of the unit Lighting the Fireplace After the Installation Step Before Lighting the Fireplace StepReview safety warnings and cautions Double-checkfor faulty componentsFireplace Maintenance Maintaining and Servicing Your FireplaceTURN OFF THE GAS BEFORE SERVICING YOUR FIREPLACEFigure 37. Burner Flame Patterns Figure 38. Pilot/Ignitor Flame PatternsReplacement Parts and Accessories Standing Pilot OnlyPART PART DESCRIPTIONDSI Ignition Only 8000DVTFL, 6000DVTFL, 6000ARCH, SL-42DVTPART PART DESCRIPTIONBoth Standing Pilot and DSI Ignition Accessories Both Standing Pilot and DSI Ignition ContACCESSORY PART