Venting Installation

Instructions

Continued

2. Rigid vent pipes and fittings have special

twist-lock connections. Assemble the desired

combination of pipe and elbows to the appli-

ance adaptor with pipe seams oriented towards

the wall or floor.

 

 

 

 

Twist-lock Procedure: The female ends of the

pipes and fittings have four locking lugs (in-

dentations). These lugs will slide straight into

matching slots on the male ends of adjacent

pipes and fittings. (All connections must be

sealed with high temperature silicone sealant

as specified in the second warning statement

on page 11.) Push the pipe sections together

and twist one section clockwise approximately

one-quarter turn until the sections are fully

locked. See Figure 17. Note: Horizontal runs

of vent must be supported every three feet. Use

wall straps for this purpose.

 

 

 

 

3. Attach vent pipe assembly to the fireplace using

twist lock connections for rigid pipe or clamp

method for flex pipe. Set fireplace in front of

its permanent location to insure minimum

clearances. Mark the wall for a 10 3/4" square

hole (for noncombustible material such as

masonry block or concrete, a 8

1

2

 

 

/ " diameter

hole is acceptable). See Figure 18. The center

of the hole should line up with the centerline of

3

4

 

3

4

the rigid vent pipe. Cut a 10 / " x 10 / " square

hole through combustible exterior wall (8 1/2"

diameter hole if noncombustible). Frame as

necessary.

 

 

 

 

4.Three types of vent caps are available for horizontal terminations. Two square terminals are available; one for rigid pipe applications and one for flex pipe applications. A round vent termination with a slip fit connection is also provided for rigid pipe applications to be used when a wall thickness or off spac- ing must be accommodated. Each may be purchased as a kit that includes a 45° elbow and a firestop that accommodates a square or round termination (see Parts List for Venting Kits and Components, page 19).

Noncombustible Exterior Wall: Apply a bead of non-hardening mastic around the outside edge of the vent cap. Position the vent cap in the center of the on the exterior wall with the arrow on the vent cap pointing up. Attach the vent cap with four wood screws provided (see Figure 19). Note: Replace the wood screws with appropriate fasteners for stucco, brick, concrete, or other types of siding.

WARNING: Do not recess vent termination in to any wall. This will cause a fire hazard.

Vent Opening

Combustible Wall

10 3/4" Inside Framing

10 3/4"

 

103/4"

(Framing

Vent Opening

Detail)

Male

Slots

Female

Locking

Lugs

Rigid Vent

Pipe

Figure 17 - Vent Pipe Connections

Noncombustible Wall

8 1/2"

Figure 18 - Vent Opening Requirements

Vent Cap

Wood Screw

Figure 19 - Installing Horizontal Vent

Cap (Noncombustible Exterior)

56131-F

www.desatech.com

13

Image 13
Contents Peninsula Model Shown Peninsula Models VDVF36Safety Information Table of ContentsSafety Information High traffic areas Right Side Front View DimensionsLocation and space requirements Pre-Installation PreparationClearances Mantel ClearancesFraming Rough Opening for Installing Vent Termination Clearances General VentingMinimum Clearances for Vent Terminations Installation Precautions Venting Installation InstructionsInstallation Planning Installing Vent System in a Chase Installation for horizontal terminationSnorkel 90º Minimum 12 Minimum 45º SnorkelVent Cap Wood Screw Male Slots Female Locking Lugs Rigid Vent PipeConnecting Vent Cap with Horizontal Vent Pipe Venting with Two 90 Elbows Installation for vertical TerminationHorizontal Venting Lowest Listed Discharge Vent Cap Opening Minimum Gas Flat Ceiling InstallationClearance Min. Height from RoofCathedral Ceiling Support Box Installation Cathedral Ceiling InstallationMin Max 20 max Starter Elbow Vertical V Horizontal H 1 +Venting with One 90 Elbow Vertical V Horizontal H Min Max 20 max Starter ElbowParts list for Desa venting kits and components High altitude installationVertical Venting Desa 5/8 Pipe & Vent Kits Number Description01492 Dura Vent 5/8 Pipe & Vent Kits Number DescriptionScrews Wall Switch Installation InstallationElectrical Hookup for optional blower accessory For Optional Fan Kit From Blower Assembly Optional Wireless hand-held Remote Control InstallationRed White To ThermopoileGAS Line HOOK-UP Installing Log Set Gas Supply TestingLeft Back Front Right Open CloseBurner Flame Adjustment Pilot/Electrode Assembly AdjustmentDecorative Facing Burner RemovalLouver Assembly Operating Guidlines Maintenance InstructionsGlass Door Hearth Pan LogsFor Your Safety Read Before Lighting Cleaning and Replacing Glass DoorGlass Assembly Frame Retainer Screws Louver Assembly Operating FireplaceLighting Instructions Position Indicator Flame Adjustment KnobTo Turn OFF GAS To Appliance Gas Control KnobService Hints SpecificationsTechnical Service Parts Under WarrantyParts Not Under Warranty TroubleshootingProblem Possible Cause Remedy Millivolt systemElectronic ignition system TroubleshootingGAS Valve Wiring DiagramsSkytech Remote Control KIT Pilot AssemblyReceiver and HAND-HELD High Voltage Cable Replacement Parts AccessoriesKeep this Warranty Warranty InformationLimited Warranty DIRECT-VENT Fireplace