TROUBLESHOOTING

 

 

Continued

 

 

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

Slight smoke or odor during ini-

1.

Residues from manufactur-

1.

Problem will stop after a few

tial operation

 

ing processes and log curing

 

hours of operation

 

2.

Not enough air

2.

Check burner for dirt and de-

 

 

 

 

bris. If found, clean burner

 

 

 

 

(see Cleaning and Mainte-

 

 

 

 

nance, pages 26 and 27)

 

3.

Gas regulator defective

3.

Replace gas regulator

Fireplace produces a whistling 1. Turning control knob to HI

noise when burner is lit

position when burner is cold

2.

Air in gas line

3.

Air passageways on fireplace

 

blocked

4.

Dirty or partially clogged

 

burner orifice

1.Turn control knob to LO posi- tion and let warm up for a minute

2.Operate burner until air is re- moved from line. Have gas line checked by local natural gas company

3.Observe minimum installation clearances (see pages 10 through 12)

4.Clean burner (see Cleaning and Maintenance, pages 26 and 27) or replace burner orifice

White powder residue forming within burner box or on adjacent walls or furniture

1.When heated, vapors from furniture polish, wax, carpet cleaners, etc. may turn into white powder residue

1.Turn fireplace off when using furniture polish, wax, carpet cleaners, or similar products

Moisture/condensation noticed on

1. Not enough combustion/ven-

1. Refer to Air for Combustion

windows

tilation air

and Ventilation requirements

 

 

(page 6)

30

www.desatech.com

113110-01A

Image 30
Contents Shown with optional cabinet mantel/hearth base accessory REMOTE-READY Models VMH26PRB, VMH26NRB, EFS26NRA, EFS26PRATable of Contents Safety Information Product Identification Provide adequate clearances around air openingsAssembly Optional Remote Control AccessoriesProduct Features Local CodesAssembly AIR for Combustion Ventilation Providing Adequate VentilationUnusually Tight Construction Confined and Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Fireplace Location Determining if You Have a Confined or Unconfined SpaceVentilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Installation Installation ItemsCheck GAS Type Minimum Clearance to Combustible Materials BUILT-IN Fireplace InstallationFireplace Clearances Minimum 16 inches from Side WallRough Opening for Installing Wall Optional Mantel Installation Mantel Clearances for Built-In InstallationInstalling Optional Blower Accessory GA3450T Removing Upper Louver Assembly and Branch SupportAssemblingTrimTrimshippedwithmantel Installing Blower Accessory For Built-In Installation Test to make sure the blower is working properlyExtension Cord Connecting to GAS Supply External Regulator With Vent Pointing DownConnecting Fireplace to GAS Supply Installation Items NeededPropane/LP Pressure Testing gas Supply Piping System Checking GAS ConnectionsCorrect all leaks at once Pressure Testing Fireplace Gas Connections Installing ReceiverRemove battery cover on back of remote con- trol unit Wire harness provided in the fireplace hard- ware packInstalling 9-Volt Battery in Hand-Held Remote Control Unit Optional Wall MountedOptional Wall Switch GWMS2 Installing LOG SET and ScreenInstall the base onto the wall with the pro- vided screws Ignitor Button Flame Adjustment Knob For Your Safety Read Before LightingSelector Switch OFF Position Control Knob Operating FireplaceOptional HAND-HELD Remote Operation Manual Lighting ProcedureTo Turn OFF GAS To Appliance Shutting Off FireplaceON/OFF Series Model Ghrcb Thermostat Series Model GhrctbGWMT1 Wall Mounted Thermostat Optional GWMS2 Wall Mounted Switch OptionalInspecting Burners Operating Blower OptionalCleaning Maintenance Burner Flame PatternBurner Injector Holder and Pilot AIR Inlet Hole Cabinet Wiring DiagramLOG SET Air PassagewaysReplace pilot assembly TroubleshootingObserved Problem Possible Cause Remedy Ignitor cable dryOr improperly connected Diagram, Safety interlock system hasLow gas pressure ODS/pilot assembly PressedTial operation Bris. If found, clean burnerResidues from manufactur Hours of operationGas leak. See Warning Specifications Remote-Ready ModelsTechnical Service Replacement PartsService Hints Parts Under WarrantyIllustrated Parts Breakdown Parts List REMOTE-READY ModelsPerimeter Trim KIT GA6095 AccessoriesEquipment Shutoff Valve GA5010 THERMOSTAT-CONTROLLED Blower KIT GA3450TCabinet Mantel and Full Hearth Base Receiver and HAND-HELD Thermostat Remote Control KIT GhrctbReceiver and HAND-HELD Remote Control KIT Ghrcb Information VideoPage Page Warranty Information Keep this WarrantyLimited Warranty VENT-FREE Compact Classic Hearth Fireplace