ADJUSTMENTS

24

ADJUSTMENTS

PILOT BURNER ADJUSTMENT

Adjust the pilot screw to provide properly sized flame. Turn in a clockwise direction to reduce the gas flow.

OL

 

 

 

F

HI

O

 

F

 

 

 

 

 

OL

P

 

 

 

TOLIP

PILOT SCREW

FIGURE 52

FIGURE 53

VENTURI ADJUSTMENT

Air shutters have been factory set open according to the chart below:

 

AIR SHUTTER

 

 

NG

1/4"

LP

7/16"

These settings are for the maximum horizontal vent run.- Adjustment may be required depending on fuel type, vent configuration and altitude.

Closing the air shutter will cause a more yellow flame, but can lead to carboning. Opening the air shutter will cause a more blue flame, but can cause flame lifting from the burner ports. The flame may not appear yellow immediately; allow 15 to 30 minutes for the final flame colour to be estab- lished.

FIGURE 54

Air shutter adjustment must only be done by a

qualified installer!

VENTURI

COVER

FIGURE 55

To access the air shutter, remove the two screws that se- cure the cover to the air housing, taking care not to dam- age the gasket.

W415-0385 / A / 10.02.03

Image 24
Contents DIRECT VENT MILLIVOLT SYSTEM TABLE of CONTENTS PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE13 - 18 INSTALLATION 21 OPTIONAL BLOWER INSTALLATIONCONTINENTAL GAS FIREPLACE PRESIDENTS LIFETIME LIMITED WARRANTY Any labour related to warranty repair is not coveredISO 9001 2000 Quality Assurance Certificate CONDITIONS AND LIMITATIONSGENERAL INSTRUCTIONS GENERAL INFORMATIONCARE OF GLASS, AND PLATED PARTS VENTING VENTING LENGTHSAIR TERMINAL INSTALLATIONS INSTALLATIONSA B C D E F G H I J K L M N O CANADIAN 12 INCHES 12 INCHES 12 INCHES 32 INCHES 32 INCHES 0 INCHESTYPICAL VENT INSTALLATIONS SPECIAL VENT INSTALLATIONSPERISCOPE TERMINATION FIGURES 3 a-cVENTING APPLICATION FLOW CHART HORIZONTAL TERMINATIONVERTICAL TERMINATION HORIZONTAL TERMINATION DEFINITIONSELBOW VENT LENGTH VALUES Formula 1 HT VT Formula 2 HT + VT 40 feet ExampleExample Formula 1 HT 4.2 VTFormula 2 HT + VT 24.75 feet Formula 1 HT 4.2 VT Formula 2 HT + VT 24.75 feetVERTICAL TERMINATION Formula 1 HT VT Formula 2 HT + VT 40 feetFIGURE10 Formula 1 HT 3VT Formula 2 HT + VT 40 feet Example REQUIRED VERTICAL RISE IN FEET VTHORIZONTAL VENT RUN PLUS OFFSET IN FEET HT INSTALLATION WALL AND CEILING PROTECTION HORIZONTAL INSTALLATIONVERTICAL INSTALLATION USING FLEXIBLE VENT COMPONENTS HORIZONTAL AIR TERMINAL INSTALLATIONVERTICAL AIR TERMINAL INSTALLATION Use only approved aluminum flexible liner kits markedUSING RIGID VENT COMPONENTS EXTENDED HORIZONTAL AIR TERMINAL INSTALLATIONFIREPLACE VENT CONNECTION VERTICAL VENTING INSTALLATION GAS INSTALLATIONProceed once the vent installation is complete 1. Move the fireplace into position and secure using theMOBILE HOME INSTALLATION FRAMINGFIGURES NAILING TAB INSTALLATION MANTLE INSTALLATIONAdditional set screws may be installed NAILINGFINISHING L42 LOUVRE INSTALLATIONLOGO PLACEMENT PORCELAIN REFLECTIVE PANELS#2#3 LOG PLACEMENTCHARCOAL EMBERS VERMICULITEOPTIONAL BLOWER INSTALLATION B ACOPTIONAL FAN INSTALLATION GD36 THERMOSTATIC SENSOR CONTROLTo safely install the fan, turn off the electricity first OPERATION / MAINTENANCE MAINTENANCEFOR YOUR SAFETY READ BEFORE LIGHTING Turn off the gas and electrical power before servicing the fireplaceADJUSTMENTS PILOT BURNER ADJUSTMENTVENTURI ADJUSTMENT Air shutter adjustment must only be done by a qualified installerREPLACEMENTS ACCESSORIESREPLACEMENT PARTS GD420 5 FTW415-0385 / A TROUBLE SHOOTING GUIDE SYMPTOMPROBLEM TEST SOLUTIONTOLI