Continental BCDV42N, BCDV42P manual Horizontal Termination, Definitions, Elbow Vent Length Values

Page 9
DEFINITIONS

DEFINITIONS

for the following symbols used in the venting calcula- tions and examples are:

>- greater than

>- equal to or greater than < - less than

< - equal to or less than

HT - total of both horizontal vent lengths (HR) and off- sets (HO) in feet

HR - combined horizontal vent lengths in feet

HO - offset factor: .03(total degrees of offset - 135°*) in feet

VT - combined vertical vent lengths in feet

9

ELBOW VENT LENGTH VALUES

 

feet

inches

0.03

0.5

15°

0.45

6.0

30°

0.9

11.0

45°*

1.35

16.0

90°*

2.7

32.0

*the first 45º and 90° offset has a zero value and is shown in the formula as -45°and -90ºrespectively or -135ºwhen combined.

HORIZONTAL TERMINATION

when (HT) < (VT)

Simple venting configuration (only one 45º and 90° elbow)

90°

FIGURE 5

For vent configurations requiring more than one 45º and 90° elbow, the following formulas apply:

Formula 1: HT < VT

Formula 2: HT + VT < 40 feet

Example 1:

90° H2

FIGURE 6

V1

45º

45º

H1

90°

REQUIRED VERTICAL RISEINFEET (VT)

CALCULATED HORIZONTAL VENT RUN PLUS OFFSETS IN FEET (HT)

The shaded area within the lines represents acceptable values for HT and VT .

V1

=

8 ft

VT

= V1 = 8 ft

H1

=

2.5 ft

H2

=

2 ft

HR

= H1 + H2 = 2.5 + 2 = 4.5 ft

HO

= .03(one 45º elbow + two 90º elbows - 135º)

=0.3(225-135º) = 2.7ft

HT

= HR + HO = 4.5 + 2.7 = 7.2 ft

HT + VT = 7.2 +8 =15.2ft

Formula 1: HT < VT

7.2< 8

Formula 2: HT + VT < 40 feet

15.2 < 40

Since both formulas are met, this vent configuration is ac- ceptable.

W415-0385 / A / 10.02.03

Image 9
Contents DIRECT VENT MILLIVOLT SYSTEM PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE TABLE of CONTENTS13 - 18 INSTALLATION 21 OPTIONAL BLOWER INSTALLATIONAny labour related to warranty repair is not covered CONTINENTAL GAS FIREPLACE PRESIDENTS LIFETIME LIMITED WARRANTYISO 9001 2000 Quality Assurance Certificate CONDITIONS AND LIMITATIONSGENERAL INSTRUCTIONS GENERAL INFORMATIONCARE OF GLASS, AND PLATED PARTS VENTING LENGTHS VENTINGINSTALLATIONS AIR TERMINAL INSTALLATIONSA B C D E F G H I J K L M N O CANADIAN 12 INCHES 12 INCHES 12 INCHES 32 INCHES 32 INCHES 0 INCHESSPECIAL VENT INSTALLATIONS TYPICAL VENT INSTALLATIONSPERISCOPE TERMINATION FIGURES 3 a-cVENTING APPLICATION FLOW CHART HORIZONTAL TERMINATIONVERTICAL TERMINATION DEFINITIONS HORIZONTAL TERMINATIONELBOW VENT LENGTH VALUES Formula 1 HT VT Formula 2 HT + VT 40 feet ExampleFormula 1 HT 4.2 VT ExampleFormula 2 HT + VT 24.75 feet Formula 1 HT 4.2 VT Formula 2 HT + VT 24.75 feetVERTICAL TERMINATION Formula 1 HT VT Formula 2 HT + VT 40 feetFIGURE10 Formula 1 HT 3VT Formula 2 HT + VT 40 feet Example REQUIRED VERTICAL RISE IN FEET VTHORIZONTAL VENT RUN PLUS OFFSET IN FEET HT INSTALLATION WALL AND CEILING PROTECTION HORIZONTAL INSTALLATIONVERTICAL INSTALLATION HORIZONTAL AIR TERMINAL INSTALLATION USING FLEXIBLE VENT COMPONENTSVERTICAL AIR TERMINAL INSTALLATION Use only approved aluminum flexible liner kits markedUSING RIGID VENT COMPONENTS EXTENDED HORIZONTAL AIR TERMINAL INSTALLATIONFIREPLACE VENT CONNECTION GAS INSTALLATION VERTICAL VENTING INSTALLATIONProceed once the vent installation is complete 1. Move the fireplace into position and secure using theMOBILE HOME INSTALLATION FRAMINGFIGURES MANTLE INSTALLATION NAILING TAB INSTALLATIONAdditional set screws may be installed NAILINGL42 LOUVRE INSTALLATION FINISHINGLOGO PLACEMENT PORCELAIN REFLECTIVE PANELSLOG PLACEMENT #2#3CHARCOAL EMBERS VERMICULITEB AC OPTIONAL BLOWER INSTALLATIONOPTIONAL FAN INSTALLATION GD36 THERMOSTATIC SENSOR CONTROLTo safely install the fan, turn off the electricity first MAINTENANCE OPERATION / MAINTENANCEFOR YOUR SAFETY READ BEFORE LIGHTING Turn off the gas and electrical power before servicing the fireplacePILOT BURNER ADJUSTMENT ADJUSTMENTSVENTURI ADJUSTMENT Air shutter adjustment must only be done by a qualified installerACCESSORIES REPLACEMENTSREPLACEMENT PARTS GD420 5 FTW415-0385 / A SYMPTOM TROUBLE SHOOTING GUIDEPROBLEM TEST SOLUTIONTOLI