Continental BCDV42P Venting Application Flow Chart, Horizontal Termination, Vertical Termination

Page 8
VENTING APPLICATION FLOW CHART

8

VENTING APPLICATION FLOW CHART

HORIZONTAL TERMINATION

VERTICAL

TERMINATION

vertical rise is equal to or greater than the horizontal run

horizontal run + verti- cal rise to m a x i m u m of 40 feet

vertical rise is less than horizontal run

horizontal run + verti- cal rise to maximum of 24.75 feet

4.2times the vertical rise equal to or greater than the horizontal run

vertical rise is equal to or greater than the horizontal run

horizontal run + verti- cal rise to m a x i m u m of 40 feet

v e r t i c a l rise is less than hori- zontal run

horizontal run + verti- cal rise to m a x i m u m of 40 feet

3 times the vertical rise equal to or g r e a t e r than the horizontal run

W415-0385 / A / 10.02.03

Image 8
Contents DIRECT VENT MILLIVOLT SYSTEM TABLE of CONTENTS PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE13 - 18 INSTALLATION 21 OPTIONAL BLOWER INSTALLATIONCONTINENTAL GAS FIREPLACE PRESIDENTS LIFETIME LIMITED WARRANTY Any labour related to warranty repair is not coveredISO 9001 2000 Quality Assurance Certificate CONDITIONS AND LIMITATIONSCARE OF GLASS, AND PLATED PARTS GENERAL INSTRUCTIONSGENERAL INFORMATION VENTING VENTING LENGTHSAIR TERMINAL INSTALLATIONS INSTALLATIONSA B C D E F G H I J K L M N O CANADIAN 12 INCHES 12 INCHES 12 INCHES 32 INCHES 32 INCHES 0 INCHESTYPICAL VENT INSTALLATIONS SPECIAL VENT INSTALLATIONSPERISCOPE TERMINATION FIGURES 3 a-cVERTICAL TERMINATION VENTING APPLICATION FLOW CHARTHORIZONTAL TERMINATION HORIZONTAL TERMINATION DEFINITIONSELBOW VENT LENGTH VALUES Formula 1 HT VT Formula 2 HT + VT 40 feet ExampleExample Formula 1 HT 4.2 VTFormula 2 HT + VT 24.75 feet Formula 1 HT 4.2 VT Formula 2 HT + VT 24.75 feetFIGURE10 VERTICAL TERMINATIONFormula 1 HT VT Formula 2 HT + VT 40 feet HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT Formula 1 HT 3VT Formula 2 HT + VT 40 feet ExampleREQUIRED VERTICAL RISE IN FEET VT VERTICAL INSTALLATION INSTALLATION WALL AND CEILING PROTECTIONHORIZONTAL INSTALLATION USING FLEXIBLE VENT COMPONENTS HORIZONTAL AIR TERMINAL INSTALLATIONVERTICAL AIR TERMINAL INSTALLATION Use only approved aluminum flexible liner kits markedFIREPLACE VENT CONNECTION USING RIGID VENT COMPONENTSEXTENDED HORIZONTAL AIR TERMINAL INSTALLATION VERTICAL VENTING INSTALLATION GAS INSTALLATIONProceed once the vent installation is complete 1. Move the fireplace into position and secure using theFIGURES MOBILE HOME INSTALLATIONFRAMING NAILING TAB INSTALLATION MANTLE INSTALLATIONAdditional set screws may be installed NAILINGFINISHING L42 LOUVRE INSTALLATIONLOGO PLACEMENT PORCELAIN REFLECTIVE PANELS#2#3 LOG PLACEMENTCHARCOAL EMBERS VERMICULITEOPTIONAL BLOWER INSTALLATION B ACTo safely install the fan, turn off the electricity first OPTIONAL FAN INSTALLATIONGD36 THERMOSTATIC SENSOR CONTROL OPERATION / MAINTENANCE MAINTENANCEFOR YOUR SAFETY READ BEFORE LIGHTING Turn off the gas and electrical power before servicing the fireplaceADJUSTMENTS PILOT BURNER ADJUSTMENTVENTURI ADJUSTMENT Air shutter adjustment must only be done by a qualified installerREPLACEMENTS ACCESSORIESREPLACEMENT PARTS GD420 5 FTW415-0385 / A TROUBLE SHOOTING GUIDE SYMPTOMPROBLEM TEST SOLUTIONTOLI