Enviro DV50DX owner manual Troubleshooting, Problem, Possible Cause, Solution

Page 31
Troubleshooting

Troubleshooting

Problem

Possible Cause

Solution

Spark will not light the

Defective piezo ignitor

• Check connections to ignitor.

pilot after repeatedly

 

• If ignitor connections are good but no spark, replace

pressing the spark ignitor

 

ignitor.

 

 

 

 

Broken spark electrode

• Check for broken ceramic insulation, replace

 

 

electrode if broken.

 

 

 

 

Misaligned spark electrode

• If spark is not arcing from electrode to pilot, adjust

 

 

by loosening the screws on the pilot base. Adjust and

 

 

tighten.

 

 

 

Pilot will not remain lit

Problem with thermocouple

• Check for proper connection of the thermocouple to

 

circuit

the rear of the valve; if loose fully tighten.

 

 

• Check pilot for full flame impingement around

 

 

thermocouple. If flame is too small, check gas

 

 

pressure, adjust pilot rate screw, check pilot head for

 

 

damage.

 

 

• Check thermocouple voltage at valve. It must be

 

 

greater than 5mV. If low, replace thermocouple.

 

 

 

 

Air in gas line (pilot dies

• Bleed line.

 

while knob is depressed)

• Check gas line pressure.

 

 

• Contact dealer.

Burners will not remain

Problem with thermopile

• Check gas line pressure .

lit

circuit

• Check for flame impingement in thermopile. If low,

 

 

see “Pilot will not remain lit”.

 

 

• Check thermopile for minimum of 300mV when

 

 

burner is switched on.

 

 

• Check wiring to thermostat for breaks.

 

 

 

Flame lifting

Leak in vent pipe

• Check for leaks in vent connections.

 

 

 

 

Improper vent configuration

• Check vent configuration with manual.

 

 

 

 

Terminal may be

• Check to see if terminal is on correctly.

 

recirculating flue gases

• May need to install high wind termination cap.

 

 

• Contact dealer.

 

 

 

Glass fogs up

Normal Condition: after the appliance warms up the glass will clear.

 

**Due to additives in gas, glass may get hazy during operation** Clean as needed.

 

 

 

Blue Flames

Normal during start up: flames will yellow as the fireplace heats up.

 

 

 

Flames are burning

Flame impingement

• Check log positioning.

“dirty” or sooting

 

• Increase primary air by opening the venturi shutter

 

 

and/or by opening the vent restrictor.

 

 

See also “Burners will not stay lit”.

 

 

 

Remote control doesn’t

Problem with the remote

• One or more of the batteries are dead. See remote

work

 

control instructions.

 

Problem with fireplace

• The on/off switch is turned to OFF.

 

 

• The gas control valve is turned to PILOT or OFF.

 

 

• The pilot has gone out.

31

Image 31
Contents Do not try to light any appliance WHAT TO DO IF YOU SMELL GASDV50DX Open windows/extinguish any open flameFOR YOUR SAFETY Safety PrecautionsGENERAL Table of Contents VENTED GAS FIREPLACE HEATER DV50DX NG/LPG Codes And ApprovalsThis ENVIRO DV50DX Fireplace INSTALLATION OPTIONS SpecificationsPILOT LIGHTING INSTRUCTIONS Operating InstructionsFOR YOUR SAFETY READ BEFORE LIGHTING INSTRUCTIONSOperating Instructions NEVER USE AN OPEN FLAME FOR LEAK TESTINGTO TURN GAS FIREPLACE OFF Operating InstructionsCLEANING THE FIREBOX Maintenance And ServiceROUTINE MAINTENANCE CLEANING THE GLASSFigure 8. Glass Removal Handle Maintenance And ServiceCLEANING DECORATIVE SURFACES GLASS DOOR REMOVALStep Maintenance And ServiceStep StepQUALIFIED INSTALLERS ONLY Initial InstallationFigure 11. Dimensions for a corner installation Initial InstallationQUALIFIED INSTALLERS ONLY CORNER INSTALLATIONFigure 14. Raised Fireplace with Raised Hearth Initial InstallationQUALIFIED INSTALLERS ONLY FIREPLACE SURROUNDQUALIFIED INSTALLERS ONLY Initial InstallationTop of unit to horizontal framing 12 5/16” 313 mm QUALIFIED INSTALLERS ONLY Initial InstallationQUALIFIED INSTALLERS ONLY Initial Installationmm of clearance are necessary. See Figure Figure 20. Possible Vent Configurations Initial InstallationQUALIFIED INSTALLERS ONLY VENT CONFIGURATIONS AND RESTRICTOR SETTINGSQUALIFIED INSTALLERS ONLY Initial Installationthe possibility of a fire QUALIFIED INSTALLERS ONLY Initial InstallationStep 4. Assemble QUALIFIED INSTALLERS ONLY Initial InstallationSTEP 10. Twist-lockthe vent cap Figure 25 Use of Wall Straps Initial InstallationQUALIFIED INSTALLERS ONLY Figure 26 Multi-StoryVent Pipe InstallationFigure 27. Heat Dumping Options Initial InstallationQUALIFIED INSTALLERS ONLY DUCTINGQUALIFIED INSTALLERS ONLY Initial InstallationELECTRICAL REQUIREMENTS TO TEST VALVE PRESSURES NEVER USE AN OPEN FLAME FOR LEAK TESTINGInitial Installation GAS LINE CONNECTIONWARNING DO NOT INSTALL LINER IF UNIT IS HOT Secondary InstallationImportant installation notes Figure 36. Second Stage Log Set Installation Secondary InstallationLOG SET ASSEMBLY Figure 35. First Stage Log Set InstallationFigure 40. Final Log Set Arrangement Secondary InstallationFigure 38. Fourth Stage Log Set Installation Figure 39. Fifth Stage Log Set InstallationFigure 42 The DV50DX burning with a good flame Secondary Installationscrews and the control panel Secondary InstallationPossible Cause TroubleshootingProblem SolutionPart Parts List - ComponentsReference DescriptionDV50DX - Components Parts DiagramNovember Options Parts List- OptionsPart Number TO THE DEALER WarrantyTO THE DISTRIBUTOR Installation Data Sheet