GAS LINE CONNECTION

Initial Installation

GAS LINE CONNECTION AND TESTING:

WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.

GAS LINE CONNECTION

This stove is equipped with a certified flexible pipe located on the right side of the unit terminating in a 3⁄8” male NPT fitting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation code in Canada, or in the USA gas installations follow either local codes or the current edition of the National Fuel Gas Code ANSI Z223.1.

The efficiency rating of this appliance is a product thermal efficiency rating determined under continuous operating conditions and was determined independently of any installed system.

The appliance and its shutoff valves must be disconnected from the gas supply piping system during any pressure testing where the pressure exceeds 1⁄2 PSIG (3.45 KPa) or damage will occur to the valve.

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1⁄2 psig (3.45 KPa).

Always check for gas leaks with a soap and water solution after completing the required pressure test.

 

 

��������

 

�����

 

 

 

�������� ���

 

 

�������� ���

 

 

 

 

 

TP TH

 

OUT

IN

 

 

 

 

 

TP

H

O

 

 

I

L

OF

 

 

 

 

 

 

 

F

 

 

 

 

P

TH

 

 

I

 

 

L

 

 

T

O

 

 

 

 

 

 

NO

 

T

P

 

 

 

I

 

 

 

OL

 

 

 

 

����� ����������

������

 

��� �������

�����

����

 

����

Figure 32: Fully Labeled Gas Valve.

TO TEST VALVE PRESSURES

The pressure taps are located on the left side of the valve

Turn set screw 1 turn counter clockwise to loosen,

Place 5/16” (8 mm) I.D. hose over pressure tap system.

Check pressures using a manometer.

When finished, release pressure, remove hose & tighten set screw.

Table 5: Pressure and BTU Information.

 

Natural Gas

Propane

Orifice

#30 DMS

#47 DMS

 

 

 

Manifold Pressure

3.8” W.C. (0.95 KPa)

11.0” W.C. (2.74 KPa)

 

 

 

Min. Manifold Pressure

1.1” W.C. (0.27 KPa)

2.7” W.C. (0.67 KPa)

 

 

 

Max Supply Pressure

7.0” W.C. (1.74 KPa)

13.0” W.C. (3.28 KPa)

 

 

 

Min. Supply Pressure

5.0” W.C. (1.25 KPa)

12.0” W.C. (2.98 KPa)

 

 

 

Max BTU/hr Input

50,000 BTU/hr (14.65 KW)

46,650 BTU/hr (13.67 KW)

 

 

 

Min. BTU/hr Input

27,000 BTU/hr (7.91 KW)

23,750 BTU/hr (6.96 KW)

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

25

Image 25
Contents DV50DX WHAT TO DO IF YOU SMELL GASOpen windows/extinguish any open flame Do not try to light any applianceFOR YOUR SAFETY Safety PrecautionsGENERAL Table of Contents VENTED GAS FIREPLACE HEATER DV50DX NG/LPG Codes And ApprovalsThis ENVIRO DV50DX Fireplace INSTALLATION OPTIONS SpecificationsFOR YOUR SAFETY READ BEFORE Operating InstructionsLIGHTING INSTRUCTIONS PILOT LIGHTING INSTRUCTIONSOperating Instructions NEVER USE AN OPEN FLAME FOR LEAK TESTINGTO TURN GAS FIREPLACE OFF Operating InstructionsROUTINE MAINTENANCE Maintenance And ServiceCLEANING THE GLASS CLEANING THE FIREBOXCLEANING DECORATIVE SURFACES Maintenance And ServiceGLASS DOOR REMOVAL Figure 8. Glass Removal HandleStep Maintenance And ServiceStep StepQUALIFIED INSTALLERS ONLY Initial InstallationQUALIFIED INSTALLERS ONLY Initial InstallationCORNER INSTALLATION Figure 11. Dimensions for a corner installationQUALIFIED INSTALLERS ONLY Initial InstallationFIREPLACE SURROUND Figure 14. Raised Fireplace with Raised HearthQUALIFIED INSTALLERS ONLY Initial InstallationTop of unit to horizontal framing 12 5/16” 313 mm QUALIFIED INSTALLERS ONLY Initial InstallationQUALIFIED INSTALLERS ONLY Initial Installationmm of clearance are necessary. See Figure QUALIFIED INSTALLERS ONLY Initial InstallationVENT CONFIGURATIONS AND RESTRICTOR SETTINGS Figure 20. Possible Vent ConfigurationsQUALIFIED INSTALLERS ONLY Initial Installationthe possibility of a fire QUALIFIED INSTALLERS ONLY Initial InstallationStep 4. Assemble QUALIFIED INSTALLERS ONLY Initial InstallationSTEP 10. Twist-lockthe vent cap QUALIFIED INSTALLERS ONLY Initial InstallationFigure 26 Multi-StoryVent Pipe Installation Figure 25 Use of Wall StrapsQUALIFIED INSTALLERS ONLY Initial InstallationDUCTING Figure 27. Heat Dumping OptionsQUALIFIED INSTALLERS ONLY Initial InstallationELECTRICAL REQUIREMENTS Initial Installation NEVER USE AN OPEN FLAME FOR LEAK TESTINGGAS LINE CONNECTION TO TEST VALVE PRESSURESWARNING DO NOT INSTALL LINER IF UNIT IS HOT Secondary InstallationImportant installation notes LOG SET ASSEMBLY Secondary InstallationFigure 35. First Stage Log Set Installation Figure 36. Second Stage Log Set InstallationFigure 38. Fourth Stage Log Set Installation Secondary InstallationFigure 39. Fifth Stage Log Set Installation Figure 40. Final Log Set ArrangementFigure 42 The DV50DX burning with a good flame Secondary Installationscrews and the control panel Secondary InstallationProblem TroubleshootingSolution Possible CauseReference Parts List - ComponentsDescription PartDV50DX - Components Parts DiagramNovember Options Parts List- OptionsPart Number TO THE DEALER WarrantyTO THE DISTRIBUTOR Installation Data Sheet