Enviro DV50DX owner manual Operating Instructions, Never Use An Open Flame For Leak Testing

Page 7
NEVER USE AN OPEN FLAME FOR LEAK TESTING

Operating Instructions

PILOT LIGHT:

1.Turn off the gas to the fireplace. If not recently done, remove the glass and let the unit air out for at least five (5) minutes to clear out any gas. Turn on gas to the heater. Leak test all joints with soapy water. NEVER USE AN OPEN FLAME FOR LEAK TESTING.

2.Start the pilot by pressing the gas control knob and turning it to PILOT. While holding the gas control knob in, press the piezo ignitor several times until the pilot light starts. Hold the gas control knob in for thirty

(30)seconds. Check that the pilot has fully engulfed the thermocouple assembly (see Figure 3).

3.Start the main burner by turning the gas control knob to ON and then turn the rocker switch to ON. Check that all burner ports have flame.

4.Leak test all gas joints again.

����������

������������

Figure 3. Pilot flame.

VENTURI ADJUSTMENT:

The venturi adjustment lever is centered above the control panel.

The venturi allows the amount of air coming into the fireplace to be adjusted in order to accommodate different climates and venting arrangements. Start the pilot and then the burner. Make sure the pilot flame is burning normally and none of the burner ports are plugged. Let the fireplace burn for roughly fifteen (15) minutes and then examine the flames.

The ideal flame will be blue at the base and light orange above (see Figure 42). The flames should be of medium height. If the flames look like this, no venturi adjustment is needed. If the flames are fairly short and mostly blue, the fireplace is getting too much air. Therefore, the air shutter should be closed (push in) slightly until the correct flames are achieved. Flames that are very orange, with tall dark stringy tips are not getting enough air. Open (pull out) the venturi until the flames clean up. If the venturi is opened, then closed all the way, and the correct flames cannot be attained, turn off the gas and contact the dealer.

Figure 4. Venturi Adjustment Lever

Warning: Incorrect venturi adjustment may lead to improper combustion, which is a safety hazard. Contact the dealer if there is any concern about the venturi adjustment.

NEVER USE AN OPEN FLAME FOR LEAK TESTING

7

Image 7
Contents Do not try to light any appliance WHAT TO DO IF YOU SMELL GASDV50DX Open windows/extinguish any open flameFOR YOUR SAFETY Safety PrecautionsGENERAL Table of Contents VENTED GAS FIREPLACE HEATER DV50DX NG/LPG Codes And ApprovalsThis ENVIRO DV50DX Fireplace INSTALLATION OPTIONS SpecificationsPILOT LIGHTING INSTRUCTIONS Operating InstructionsFOR YOUR SAFETY READ BEFORE LIGHTING INSTRUCTIONSOperating Instructions NEVER USE AN OPEN FLAME FOR LEAK TESTINGTO TURN GAS FIREPLACE OFF Operating InstructionsCLEANING THE FIREBOX Maintenance And ServiceROUTINE MAINTENANCE CLEANING THE GLASSFigure 8. Glass Removal Handle Maintenance And ServiceCLEANING DECORATIVE SURFACES GLASS DOOR REMOVALStep Maintenance And ServiceStep StepQUALIFIED INSTALLERS ONLY Initial InstallationFigure 11. Dimensions for a corner installation Initial InstallationQUALIFIED INSTALLERS ONLY CORNER INSTALLATIONFigure 14. Raised Fireplace with Raised Hearth Initial InstallationQUALIFIED INSTALLERS ONLY FIREPLACE SURROUNDQUALIFIED INSTALLERS ONLY Initial InstallationTop of unit to horizontal framing 12 5/16” 313 mm QUALIFIED INSTALLERS ONLY Initial InstallationQUALIFIED INSTALLERS ONLY Initial Installationmm of clearance are necessary. See Figure Figure 20. Possible Vent Configurations Initial InstallationQUALIFIED INSTALLERS ONLY VENT CONFIGURATIONS AND RESTRICTOR SETTINGSQUALIFIED INSTALLERS ONLY Initial Installationthe possibility of a fire QUALIFIED INSTALLERS ONLY Initial InstallationStep 4. Assemble QUALIFIED INSTALLERS ONLY Initial InstallationSTEP 10. Twist-lockthe vent cap Figure 25 Use of Wall Straps Initial InstallationQUALIFIED INSTALLERS ONLY Figure 26 Multi-StoryVent Pipe InstallationFigure 27. Heat Dumping Options Initial InstallationQUALIFIED INSTALLERS ONLY DUCTINGQUALIFIED INSTALLERS ONLY Initial InstallationELECTRICAL REQUIREMENTS TO TEST VALVE PRESSURES NEVER USE AN OPEN FLAME FOR LEAK TESTINGInitial Installation GAS LINE CONNECTIONWARNING DO NOT INSTALL LINER IF UNIT IS HOT Secondary InstallationImportant installation notes Figure 36. Second Stage Log Set Installation Secondary InstallationLOG SET ASSEMBLY Figure 35. First Stage Log Set InstallationFigure 40. Final Log Set Arrangement Secondary InstallationFigure 38. Fourth Stage Log Set Installation Figure 39. Fifth Stage Log Set InstallationFigure 42 The DV50DX burning with a good flame Secondary Installationscrews and the control panel Secondary InstallationPossible Cause TroubleshootingProblem SolutionPart Parts List - ComponentsReference DescriptionDV50DX - Components Parts DiagramNovember Options Parts List- OptionsPart Number TO THE DEALER WarrantyTO THE DISTRIBUTOR Installation Data Sheet