Wayne JSU50 operating instructions Operation, Maintenance

Page 4

Operating Instructions and Parts Manual

JSU50

Installation (Continued)

Do not use both a check valve and foot valve in your system. This could

significantly reduce the performance of the pump.

Drilled Well

1.Install a foot valve on the first section of pipe (Figure 10).

To pump

Well

 

 

Seal

NOTE: When a lake is used for the water supply, make sure the suction pipe is deep enough to be submerged at all times. Slope the pipe upward toward the pump to eliminate trapping air. The pipe must be removed during winter months or protected against freezing.

 

Protect the pipe

! WARNING

from damage by

 

swimmers and boaters.

Operation

priming pump

Do not run pump

Maintenance

Disconnect power supply and release all pressure from system before attempting

to install, service, relocate, or perform any maintenance. Lock the power disconnect in the open/off position. Tag the power disconnect to prevent unexpected application of power. Serious injury or death could result.

Maintain adequate ventilation for the pump motor. The motor bearings are permanently lubricated at the factory. Additional lubrication is not required.

Foot

Valve

Well Casing

dry. Fill with water before starting motor. Damage to pump seals will result and void warranty.

After pump installation is complete, the pump must be primed.

1.

Remove the priming plug.

2.

Fill pump and piping completely full

 

of water.

3.

Replace the priming plug.

4.

Open faucet to vent system.

draining pump

Drain openings are provided on all models. To drain the pump:

1.Disconnect power to the pump

2.Remove the drain fitting and priming plug.

3.Drain all piping to a point below the frost line.

draining tank

Figure 10 - Well Seal

2.Lower the pipe into the well.

3.Add pipe until the foot valve is 10 feet below the lowest anticipated water level.

Leaking joints or couplings will allow air to leak into the pipe and cause poor pump operation. Make sure to use pipe joint compound or plumbers seal tape on all pipe connections.

Locate foot valve at least 2 feet from

the bottom of the well so sand or sediment is not drawn into the system.

4.After proper depth is reached, install a well seal or pitless adapter to support the pipe.

5.Slope the horizontal pipe upward toward the pump to eliminate trapping air.

Dug Well, Cistern, Lake And Spring Installation

1.Install a foot valve on the inlet pipe and lower into the water.

Locate foot valve at least 2 feet

from the bottom of the well so sand or sediment is not drawn into the system.

5.

Start the motor. Water will be

 

pumped within a few minutes. If

 

pump does not deliver water within

 

5 minutes, shut off motor and return

 

to step 1.

6.

Let the system operate for several

 

minutes to flush out the pipes.

7.

Close the faucet and allow pump

 

to build pressure in the tank. When

 

pressure reaches cut-out setting, the

 

motor will stop.

The system is now operating and will cycle on demand.

If the pump does not operate after repeated attempts, check the following:

1.Vertical distance of pump to water must not exceed 25 feet.

2.Suction piping must be air tight.

3.Be sure valves are open if used in discharge or suction piping.

Never run the pump with a closed

or clogged discharge. The water inside the pump could boil and damage the pump.

The use of a foot valve is strongly recommended. This allows the suction line to be filled during the priming process, greatly decreasing priming times.

Conventional tanks can be drained by opening an outlet at the lowest point in the system. Remove a plug or the air volume control to vent the tank.

Pre-charged tanks force virtually all of the water from the tank when the system pressure is released. No draining is necessary.

water-logged tanks

conventional TANKS

When a tank system has an inadequate ratio of air and water, the pump will start and stop often and erratically.

1.Disconnect electrical power to pump.

2.Open the lowest faucet in the system to release all pressure.

3.Prime the pump.

4.Reconnect power.

As the pump refills the tank, the air volume control supplies the tank with the correct air to water ratio. The pump will then shut off at desired pressure.

If tank water-logs again, examine air volume control and replace if necessary.

www.waynepumps.com

4

Image 4
Contents Safety Guidelines General Safety InformationInstallation DescriptionPump piping installation Operating Instructions and Parts ManualSuction piping Discharge piping FigureElectrical connections Operating Instructions & Parts ManualConnection to water source Maintenance OperationRecommended Fusing & Wiring Data 60 HZ Motors Friction loss chartAir pressure check for pre- charged tanks Troubleshooting Chart Water Supplies OperatingInstructions & Parts ManualFor Replacement Parts, Call Déballage Directives de SécuritéGénéralités Sur La Sécurité PRoposition 65 DE CalifornieInstallation Suite Branchement a la source d’eau Connexion Électrique11-Fr Amorçage de la pompe Fonctionnement12-Fr Entretien Tableau de dépannage 14-FrDe Pièces 15-Fr Instructions D’utilisation et ManualInstructions D’utilisation et Manual de PiècesJSU50 16-FrDescripción Para DesempacarMedidas de Seguridad Informaciones Generales de SeguridadInstalación Continúa ConexiÓn al suministro de agua ConexiÓnes elÉctricas19-Sp CÓmo cebar la bomba Funcionamiento20-Sp Mantenimiento Cómo drenar la bombaCÓmo drenar el tanque Tanques inundadosTabla de Identificación de Problemas 22-Sp23-Sp Piezas Capa FreaticaManantial CisternaNo Envie Estos Datos a WAYNE. Conserve esto sólo como datos 24-Sp