•Move the lower part of the side panels (figure 12.3).
•Pull the control panel. When completely pulled out, the panel can rotate 45° downward.
D
D
Figure 12.1
Removing Front Panel:
• Remove the front panel by removing screws A and sliding the front panel up and away from the boiler
For the electrical connection to the boiler use electric wires which conform to local regulations.
12.2Connection to the electricity supply:
•Connect the electrical supply cable coming from the fused spur isolation switch to the power supply terminal block of the boiler (as shown in figure 12.5) keeping the same connections for the live wire and the neutral wire.
To fused spur isolation switch
L
3 2 1
Service Man's Switch
N
Power supply terminal block
120 VAC
15 AMP BREAKER
Fire - O - Matic
WARNING
Note: Do not connect live wires to thermostat terminals
External controls terminal block
Figure 12.5
• Connect the earth wire(yellow/green). Boiler must be wired directly to earth ground on breaker panel.
12. Electrical Connections/Wiring Cont. | |
RIVA HEAT ONLY MANUAL - REV A | 23 |