PB Heat Gas Boiler manual Approved Materials for Exhaust Vent and Intake AIR Pipe

Page 21

VENTING, INLET AIR AND CONDENSATE

5. VENTING, INLET AIR AND CONDENSATE

A.GENERAL

1.Install the boiler venting system in accordance with these instructions and with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, CAN/CGA B149, and/or applicable provisions of local building codes.

2.This boiler is a direct vent appliance and is listed as a Category IV appliance with Underwriters Laboratories, Inc.

WARNING

This vent system will operate with a positive pressure in the pipe. Do not connect vent connectors serving appliances vented by natural draft into any portion of mechanical draft systems operating under positive pressure.

WARNING

Follow these venting instructions carefully. Failure to do so may result in severe personal injury, death, or substantial property damage.

B.APPROVED MATERIALS FOR EXHAUST VENT AND INTAKE AIR PIPE

1.Use only Non Foam Core venting material. The following materials are approved for use as vent pipe for this boiler:

a.Non Foam Core PVC (Polyvinyl Chloride) Pipe conforming to ASTM D-1784 Class 12454-B (formerly designated Type 1, Grade 1).

b.Non Foam Core CPVC (Chlorinated Polyvinyl Chloride) Pipe conforming to ASTM D-1784 Class 23447-B (formerly designated Type IV, Grade 1).

c.Non Foam Core ABS (Acrylonitrile-Butadiene- Styrene) Pipe conforming to ASTM D3965 Class 3-2-2-2-2.

WARNING

Do not use Foam Core Pipe in any portion of the exhaust piping from this boiler. Use of Foam Core Pipe may result in severe personal injury, death, or substantial property damage.

2.Cellular foam core piping may be used on air inlet piping only. Never use cellular foam core material for exhaust piping.

C.EXHAUST VENT / AIR INTAKE PIPE LOCATION

1.Determine exhaust vent location:

a.The vent piping for this boiler is approved for zero clearance to combustible construction.

b.See Figure 5.1 for an illustration of clearances for location of exit terminals of direct-vent venting systems.

c.This boiler vent system shall terminate at least 3 feet (0.9 m) above any forced air intake located within 10 ft (3 m). Note: this does not apply to the combustion air intake of a direct-vent appliance.

d.Provide a minimum of 1 foot distance from any door, operable window, or gravity intake into any building.

e.Provide a minimum of 1 foot clearance from the bottom of the exit terminal above the expected snow accumulation level. Snow removal may be necessary to maintain clearance.

f.Provide 4 feet horizontal clearance from electrical meters, gas meters, gas regulators, and relief equipment. In no case shall the exit terminal be above or below the aforementioned equipment unless the 4 foot horizontal distance is maintained.

g.Do not locate the exit terminal over public walkways where condensate could drip and/or freeze and create a nuisance or hazard.

h.When adjacent to a public walkway, locate exit terminal at least 7 feet above grade.

i.Do not locate the exit termination directly under roof overhangs to prevent icicles from forming.

j.Provide 3 feet clearance from the inside corner of adjacent walls.

2.Determine air intake pipe location.

a.Provide 1 foot clearance from the bottom of the air inlet pipe and the level of maximum snow accumulation. Snow removal may be necessary to maintain clearances.

b.Do not locate air intake pipe in a parking area where machinery may damage the pipe.

c.Maximum distance between air intake and exhaust vent is 6 feet (1.8 m). Minimum distance between exhaust vent and air intake on single Pinnacle is 8" (0.2 m) center-to-center. Minimum distance between vents and intakes on multiple Pinnacles is 8" (0.2 m) center-to-center. See Figure 5.2.

19

Image 21
Contents Peerless Pinnacle Table of Contents Using this Manual Installation SequenceSpecial Attention Boxes General Accessibility Clearances PreinstallationCodes & Regulations Combustion and Ventilation AIRAccessibility Clearances Floor Standing Units General Boiler SET-UPWall Hung Boilers Floor Mounted BoilersWater Piping and Controls Operating ParametersSystem Components Boiler Inputs and Outputs Net I=B=R Output Model Btu/hr kW Piping Symbol KeyFeet meters Flow Rate and Pressure Drop Boiler ModelRecommended Circulators Boiler Grundfos CirculatorPinnacle Circulator Sizing Graph System Piping Freeze ProtectionOne Boiler, Primary/Secondary with Two Zones Zone Circulator Water Piping and Controls Water Piping and Controls Water Piping and Controls Three Boilers, Primary/Secondary with Four Zones Zone Valves Special Applications Boiler in conjunction with a Chilled Water System GAS Piping GAS Supply Piping InstallationFuel Line Sizing Feet PipeGas Supply Piping Sediment Trap GAS Supply Piping OperationMain GAS Valve Operation Recommended Vent CO² Settings Firing Gas Type RateExhaust Vent / AIR Intake Pipe Location Approved Materials for Exhaust Vent and Intake AIR PipeFitting Equivalent Length Table Fitting Description Exhaust Vent and Intake AIR Pipe SizingVent Termination Kits Stock Description Code Exhaust Vent and AIR Intake Pipe InstallationVENTING, Inlet AIR and Condensate PI-T50 & PI-T80 Sidewall Venting with 2 Pipe 2 Vent Kit With 2 Pipe With 2 Pipe Concentric Vent Kit Venting with 3 Pipe Venting with 3 Pipe Concentric Vent KitCondensate Drain Installation Exhaust Tapping for Vent SampleBoiler Removal from Common Venting System Wiring ElectricalSequence of Operation Boiler Control Board Wiring Schematic Control Functions Safety InterlocksStatus Menu Description Code Installer Menu Parameter FunctionCompleting the Installation START-UP ProceduresLighting and Operating Procedures For Your Safety Read Before OperatingCHECK-OUT Procedure Troubleshooting Boiler ErrorBoiler Fault Fault Code Description Corrective Action P125 Control Board Fault CodesGeneral with Boiler in USE MaintenanceWeekly with Boiler in USE Annually Before Start of Heating SeasonGAS Leaks Reset thermostats Important Make Boiler Dimensions Boiler Dimensions & RatingsPI-80/PI-140/PI-199 Dimensions Sch 40 PVC LbsRepair Parts Repair Parts Appendix A. WHAT’S NEW with the P125 Control Board Advantages of the P125 Control BoardP125 Control Board Quick Reference Figure A.2Comparative Control Board Sequence of Operation P125 Control Board VS. WHA Control Board ComparisonPeerless Pinnacle

Gas Boiler specifications

PB Heat Gas Boilers are renowned for their efficiency, reliability, and advanced technology, making them a popular choice for residential heating needs. With a range of models available, these boilers cater to various heating requirements while maintaining high performance and energy efficiency.

One of the standout features of PB Heat Gas Boilers is their exceptional efficiency ratings. Most models are designed to achieve AFUE (Annual Fuel Utilization Efficiency) ratings of over 90%, ensuring minimal energy waste and lower utility bills for homeowners. This high efficiency not only translates to cost savings but also contributes to a reduced carbon footprint, making PB Heat boilers a sustainable choice for environmentally conscious consumers.

PB Heat utilizes cutting-edge technologies to enhance the performance of their gas boilers. One such technology is the dual-stage gas valve, which allows for better modulation of gas flow, enabling the boiler to adapt to varying heating demands. This feature ensures consistent comfort while minimizing unnecessary energy consumption. Additionally, many PB Heat models come equipped with smart controls that can be easily integrated with home automation systems, giving homeowners the ability to monitor and adjust their heating remotely for maximum convenience and efficiency.

Durability and ease of maintenance are also key characteristics of PB Heat Gas Boilers. Constructed from high-quality materials, these boilers are designed to withstand the rigors of day-to-day operation. Features such as a corrosion-resistant heat exchanger contribute to the longevity of the unit, while easily accessible components simplify routine maintenance tasks, reducing downtime and service costs.

PB Heat Gas Boilers are available in various configurations, including wall-mounted and floor-standing models, catering to different space and installation requirements. This versatility allows homeowners to choose a solution that best fits their living environment while ensuring optimal heating performance.

In conclusion, PB Heat Gas Boilers represent a blend of advanced technology, energy efficiency, and robust construction. With their high efficiency ratings, smart control options, and durable design, these boilers provide reliable heating solutions for homes of all sizes. Choosing a PB Heat Gas Boiler means investing in a product that not only delivers comfort but also aligns with energy-saving and sustainability goals.