PB Heat Gas Boiler manual Exhaust Vent and AIR Intake Pipe Installation

Page 23

VENTING, INLET AIR AND CONDENSATE

4.The minimum combined equivalent length is 16 equivalent feet.

5.The maximum combined equivalent length can be extended by increasing the diameter of the vent pipe. However, the transitions should begin a minimum of 15 equivalent feet from the boiler.

a.Transitions should always be made in vertical sections of pipe to prevent the condensate from pooling in the vent pipe.

b.Use a 3" x 2" reducing coupling to transition from the PI-T50 and PI-T80 boiler connections to a 3" vent.

c.Use a 4" x 3" reducing coupling to transition from the PI-80, PI-140, and PI-199 boiler connections to 4" vent.

d.The maximum equivalent length for the increased diameter vent pipes is 125 feet.

e.If the transition occurs at a distance greater than 15 equivalent feet from the boiler, the maximum equivalent length will be reduced. See Table 5.2. Standard Vent Pipe is 2” and Oversized Vent Pipe is 3” for PI-T50 and PI-T80. Standard Vent Pipe is 3” and Oversized Vent Pipe is 4” for PI- 80 through PI-199.

Table 5.2: Maximum Equivalent Vent Length for Oversized Vent Pipe

Transition

TEL of

TEL of

Maximum

Point

Standard 2”

Oversized 3”

TEL of all

(ft from

or 3” Vent

or 4” Vent

Vent Pipe (ft)

boiler)

Pipe (ft)

Pipe (ft)

 

 

 

 

 

15

30

95

125

 

 

 

 

20

40

77-1/2

117-1/2

 

 

 

 

25

50

60-1/2

110-1/2

 

 

 

 

30

60

43

103

 

 

 

 

35

70

26

96

 

 

 

 

40

80

8-1/2

88-1/2

 

 

 

 

None

85

0

85

 

 

 

 

TEL = Total Equivalent Length

E.EXHAUST VENT AND AIR INTAKE PIPE INSTALLATION

1.On the PI-T50 and PI-T80 the 2" exhaust vent connection is located on the top, right side of the boiler and the air intake is on the top, left side. See Figure 10.1. The air intake connection is intended for a slip fit. No sealant or adhesive is required.

2.On the PI-80, PI-140, and PI-199 Boilers the 3” exhaust vent connection is located on the rear of the boiler and the air intake is higher and toward the left side when the boiler is viewed from the front. See Figure 10.2. The air intake connection is intended for a slip fit. No sealant or adhesive is required.

3.Use only solid PVC, CPVC, or ABS schedule 40 or 80 pipe. FOAM CORE PIPING IS NOT APPROVED.

4.Remove all burrs and debris from joints and fittings.

5.All joints must be properly cleaned, primed, and cemented. Use only cement and primer approved for use with the pipe material. Cement must conform to ASTM D2564 for PVC or CPVC pipe and ASTM D2235 for ABS pipe.

WARNING

All joints of positive pressure vent systems must be sealed completely to prevent leakage of flue products into the living space.

6.Horizontal lengths of exhaust vent must slope back towards the boiler not less than ¼" per foot to allow condensate to drain from the vent pipe. If the vent pipe must be piped around an obstacle that causes a low point in the pipe, a drain pipe must be connected to allow condensate to drain.

7.All piping must be fully supported. Use pipe hangers at a minimum of 4 foot intervals to prevent sagging of the pipe where condensate may form.

8.Do not use the boiler to support any piping.

9.A screened straight coupling is provided with the boiler for use as an outside exhaust termination.

10.A screened inlet air tee is provided with the boiler to be used as an outside intake termination.

11.The following are optional intake air/exhaust vent terminations available from your PB Heat, LLC distributor for use with Pinnacle boilers.

Table 5.3: Vent Termination Kits

 

Stock

Description

Code

2" PVC Concentric Vent Termination Kit

91469

 

 

3" PVC Concentric Vent Termination Kit

91403

 

 

2" Stainless Steel Vent Termination Kit

91465

 

 

3" Stainless Steel Vent Termination Kit

91402

 

 

4" Stainless Steel Vent Termination Kit

91401

 

 

12.Refer to Figure 5.3 to 5.10 for sidewall venting and Figures 5.11 to 5.14 for vertical venting.

21

Image 23
Contents Peerless Pinnacle Table of Contents Special Attention Boxes Using this ManualInstallation Sequence Combustion and Ventilation AIR PreinstallationGeneral Accessibility Clearances Codes & RegulationsAccessibility Clearances Floor Standing Units Floor Mounted Boilers Boiler SET-UPGeneral Wall Hung BoilersSystem Components Water Piping and ControlsOperating Parameters Boiler Inputs and Outputs Net I=B=R Output Model Btu/hr kW Piping Symbol KeyGrundfos Circulator Flow Rate and Pressure Drop Boiler ModelFeet meters Recommended Circulators BoilerPinnacle Circulator Sizing Graph System Piping Freeze ProtectionOne Boiler, Primary/Secondary with Two Zones Zone Circulator Water Piping and Controls Water Piping and Controls Water Piping and Controls Three Boilers, Primary/Secondary with Four Zones Zone Valves Special Applications Boiler in conjunction with a Chilled Water System Feet Pipe GAS Supply Piping InstallationGAS Piping Fuel Line SizingGas Supply Piping Sediment Trap GAS Supply Piping OperationMain GAS Valve Operation Recommended Vent CO² Settings Firing Gas Type RateExhaust Vent / AIR Intake Pipe Location Approved Materials for Exhaust Vent and Intake AIR PipeFitting Equivalent Length Table Fitting Description Exhaust Vent and Intake AIR Pipe SizingVent Termination Kits Stock Description Code Exhaust Vent and AIR Intake Pipe InstallationVENTING, Inlet AIR and Condensate PI-T50 & PI-T80 Sidewall Venting with 2 Pipe 2 Vent Kit With 2 Pipe With 2 Pipe Concentric Vent Kit Venting with 3 Pipe Venting with 3 Pipe Concentric Vent KitBoiler Removal from Common Venting System Condensate Drain InstallationExhaust Tapping for Vent Sample Sequence of Operation WiringElectrical Boiler Control Board Wiring Schematic Control Functions Safety InterlocksStatus Menu Description Code Installer Menu Parameter FunctionCompleting the Installation START-UP ProceduresLighting and Operating Procedures For Your Safety Read Before OperatingCHECK-OUT Procedure Boiler Fault TroubleshootingBoiler Error Fault Code Description Corrective Action P125 Control Board Fault CodesAnnually Before Start of Heating Season MaintenanceGeneral with Boiler in USE Weekly with Boiler in USEGAS Leaks Reset thermostats Important Make Boiler Dimensions Boiler Dimensions & RatingsPI-80/PI-140/PI-199 Dimensions Sch 40 PVC LbsRepair Parts Repair Parts P125 Control Board Quick Reference Appendix A. WHAT’S NEW with the P125 Control BoardAdvantages of the P125 Control Board Figure A.2Comparative Control Board Sequence of Operation P125 Control Board VS. WHA Control Board ComparisonPeerless Pinnacle

Gas Boiler specifications

PB Heat Gas Boilers are renowned for their efficiency, reliability, and advanced technology, making them a popular choice for residential heating needs. With a range of models available, these boilers cater to various heating requirements while maintaining high performance and energy efficiency.

One of the standout features of PB Heat Gas Boilers is their exceptional efficiency ratings. Most models are designed to achieve AFUE (Annual Fuel Utilization Efficiency) ratings of over 90%, ensuring minimal energy waste and lower utility bills for homeowners. This high efficiency not only translates to cost savings but also contributes to a reduced carbon footprint, making PB Heat boilers a sustainable choice for environmentally conscious consumers.

PB Heat utilizes cutting-edge technologies to enhance the performance of their gas boilers. One such technology is the dual-stage gas valve, which allows for better modulation of gas flow, enabling the boiler to adapt to varying heating demands. This feature ensures consistent comfort while minimizing unnecessary energy consumption. Additionally, many PB Heat models come equipped with smart controls that can be easily integrated with home automation systems, giving homeowners the ability to monitor and adjust their heating remotely for maximum convenience and efficiency.

Durability and ease of maintenance are also key characteristics of PB Heat Gas Boilers. Constructed from high-quality materials, these boilers are designed to withstand the rigors of day-to-day operation. Features such as a corrosion-resistant heat exchanger contribute to the longevity of the unit, while easily accessible components simplify routine maintenance tasks, reducing downtime and service costs.

PB Heat Gas Boilers are available in various configurations, including wall-mounted and floor-standing models, catering to different space and installation requirements. This versatility allows homeowners to choose a solution that best fits their living environment while ensuring optimal heating performance.

In conclusion, PB Heat Gas Boilers represent a blend of advanced technology, energy efficiency, and robust construction. With their high efficiency ratings, smart control options, and durable design, these boilers provide reliable heating solutions for homes of all sizes. Choosing a PB Heat Gas Boiler means investing in a product that not only delivers comfort but also aligns with energy-saving and sustainability goals.