(3)If the timer were set as in the above examples, the system would run for 4 hours, shut off for 2 minutes, run for another 4 hours, shut off for 2 minutes, and so on and so forth.
NOTE
The humidistat takes precedence over the timer for shutting down the system. If the humidistat reaches its set point, it will shut the system off regardless of the timer to prevent over humidifying the space.
(4)The factory default setting for the timer is 2 minutes of off time (cleaning time) after every 8 hours of operation. Using settings that result in an off time of less than 10 seconds are not recommended. As well, using settings that result in an on time of less than 15 minutes are not recommended.
E.SETTING THE SYSTEM FOR NORMAL OPERATION
(1)Once the
(a)Close and lock all covers including the control panel covers.
(b)Tighten the lock nuts on the primary air and water regulators.
(c)Set the humidistat to the desired level.
(2)The AirFog humidification system is now ready to operate normally.
Page 32