1.AFE, MINI, AND OCTO START-UP PROCEDURES

A.INTRODUCTION

(1)The operator must make reference to Figure 1 Typical Nozzle Layout when following these instructions. Prior to startup, ensure the following:

(a)All components have been visually checked for proper connections.

(b)All supply and feed lines have been cleaned.

(c)The on/off valve of the primary water pressure control section is OFF.

(d)Water at 25 psig pressure from the main supply is ON.

(e)The on/off valve of the primary air pressure control section is OFF.

(f)The air compressor is running and providing a minimum of 90 psig.

(g)The control panel switch is OFF.

(h)The 24 VAC transformer is plugged into a 110 VAC source and the control panel power indicator light is illuminating.

(i)The humidistat is set at 100% relative humidity.

B.COMPRESSED AIR SUPPLY

(1)The clean out valves on the ends of the supply pipes must be closed.

(2)The on/off valve of the primary air pressure control section is opened to the ON position. The handle should be in line with the pipe (as opposed to 90 degrees to it).

(3)The control panel switch is turned to the ON position.

(4)Adjust the air pressure regulator in the control panel to about 70 psig to obtain maximum water throughput for each nozzle for this startup test.

(5)There should an audible hissing sound as the compressed air works its way through the piping to the nozzles. If this is not detected and air can not be felt by hand directly in front of the nozzle orifice, then air is not being provided to the system. Check the compressed air line back to the compressor for other valves that may not be open.

(6)The air pressure regulator knob in the primary air pressure control section is to be adjusted until its gauge indicates 90 psig.

(7)Most significant air pressure leaks can be detected by sensing the air flow with the hand or by spraying on soapy water to observe the growth of bubbles around the leak. If an AFE nozzle is sucking some air rather than 100% water through the water pipes, the nozzles will sputter/spit and behave irregularly as opposed to a steady production of uniform mist. A thorough survey should be conducted to identify and fix leaking joints.

C.WATER SUPPLY

(1)The clean out valves on the ends of the water supply pipes must be closed.

(2)The on/off valve of the primary water pressure control section is turned ON. The handle should be in line with the pipe (as opposed to 90 degrees to it).

10-30

Page 30 2008-04-11

Image 37
Contents Airfog SeriesTM Proprietary Notice Liability Notice Table of Contents SHUT-DOWN Procedure List of Figures List of Tables This page Intentionally Left Blank Introduction Introduction General Airfog Technical Considerations Older Nortec Airfog System Components 10-00 This page Intentionally Left Blank Installation Nozzle System Layout InstallationTypical Nozzle Layout for Wall Mounted System Multi Zone Layout Introduction CleaningSupply Feed Lines Mounting of NozzlesWater and Air Line Pressure Control Saddle Clamp Installation Connecting NozzlesPilot Operated AIR Regulator Vacuum Valve10-10 Vacuum Valve Operation Primary AIR Pressure Control Electrical WiringPrimary Water Pressure Control Control PanelPrimary Air Pressure Control Section Pilot Lines Schematic Plumbing LayoutThis page Intentionally Left Blank Mini & Octo Installation AFE Mini Systems AFE Self Contained Airfog SystemsMini Installations AFE Octo Systems Installation ProcedureOcto Layout with Interfaces 10-20 Ceiling Mounting of Octo Four Octo Units with a Single Control Panel START-UP Procedure Water Supply Compressed AIR SupplySelf Cleaning Cycle Adjustment Setting the System for Normal Operation Capacity Output vs. Vacuum Valve Adjustment This page Intentionally Left Blank 10-40 SHUT-DOWN ProcedureAFE, MINI, and Octo Shut Down Procedures 10-50 MaintenanceMaintenance Unscheduled Maintenance 10-50 10-60 TroubleshootingTroubleshooting 10-60 This page Intentionally Left Blank 10-70 Spare PartsSpare Parts Octo Exploded View Octo This page Intentionally Left Blank Item # Description QTY Vacuum Valve Exploded View Item # Description Octo Mini Standard Control Panel Exploded View AFE This page Intentionally Left Blank Warranty Authorized Agent