Herrmidifier Co 6000 Non-FaultActivated Problems, Problem / Symptom, Reason - Correction

Page 15

Non-Fault Activated Problems:

Problem / Symptom

Reason - Correction

24 VAC circuit breaker trips as soon as power switch is turned “on”.

Check the wiring at the 24 VAC breaker for a short or loose

 

connection.

 

Disconnect the contractor coil from the circuit and repeat. If 24-volt

 

breaker doesn’t blow, replace the contractor.

 

Replace the main circuit board.

24 VAC circuit breaker trips after the unit is turned on for about 15

Disconnect fill valve from electrical circuit. If circuit breaker doesn’t

seconds.

trip, replace the fill valve.

 

Replace the main circuit board

24 VAC Circuit breaker trips whenever the drain valve activates

Disconnect drain valve from electrical circuit. If circuit breaker doesn’t

 

trip, replace the drain valve.

 

Remove the drain valve and insure that it is clean and free of any

 

obstructing mineral deposits.

 

Replace the main circuit board.

Humidifier turned on but will not operate. Power lamp is “off”.

Check power supply.

 

Check circuit breaker.

 

Check connector J1 on the circuit board and insure that it is plugged

 

into the circuit board properly and that no wires are loose.

 

Insure that there is 24 VAC between pole #9 and #11 connector J1. If

 

not, check wiring.

 

Place jumper between controls terminal strip #1 and #2. If unit

 

operates, check controls settings and wiring (control stat, limit stat, air

 

proving switch.)

 

Check door interlock.

Unit turned “on”. Contractor pulled in, but no water is entering the

Check external shutoff valves and open if closed.

cylinder.

Check strainer and fill valve for clogs. Turn adjusting screw (fig. 9,

 

page 10)

 

Check fill valve coil to determine if it is receiving 24 VAC. If so, replace

 

the valve.

 

Check for break in wiring.

Excessive arcing in cylinder

Check drain valve and insure that when it activates it drains freely.

 

Clean if necessary. Replace valve if defective.

 

Check water supply. If it is softened, increase the drain threshold pot,

 

“% adj.” (R18), up to 92%. (See Figure 12)

 

Use high conductivity settings if water supply is very hard, >750

 

micromho.

 

Unit filling slower or at the same rate as the water is boiling, causing

 

over concentration and foaming. Check restriction in fill line. Adjust

 

the metering fill valve to allow greater flow of water. ( See Figure 9)

 

Have water analyzed. If iron content is greater than .1 mg/1, a filter

 

will have to be used.

 

Consult factory with water analysis

Unit fills to the cylinder full condition and remains cold.

Check between Test Point #3 and ground with a multimeter set on

 

VDC scale. Confirm the circuit board is seeing low current flow (<2.8

 

VDC). Proceed to next step.

 

If on initial fill, unit reaches less than 70% of rated capacity (2.8 VDC

 

on Test Point #3), adjust the drain threshold pot, “% adj.” (R18), down

 

2-3%. Manually drain the unit down completely and add ½ Alka

 

Seltzer tablet via the fill tee (GT-120). (See “Note” after item #9 on

 

page 10.) Restart the unit while monitoring the amp draw. Fill unit ¼

 

full and turn “off” for several minutes to allow tablets to dissolve.

 

Restart unit. If amperage rises rapidly, it may be necessary to dilute

 

the water. If amperage rises slowly, add another Alka-Seltzer tablet.

 

Check that drain valve is sealing properly.

 

Check the water conductivity and consult the factory.

Unit turned on a cycles for a short period of time. Then it stops in the

Check cylinder fill interface connections.

middle of a fill cycle and won’t reset until boiling stops.

Check cylinder connections (See Figure #11)

 

Check items in next troubleshooting tip concerning foaming.

 

Check amperage between cylinder full electrode and cylinder full

 

interface terminal #1. If it is greater than 7.0 mA AC is is, take a fill

 

water sample and consult the factory.

 

 

15

Image 15
Contents Installation Operation Service 6000 SeriesElectronic Steam Humidifiers SECTION VI SUGGESTED SPECIFICATIONS TABLE OF CONTENTSSECTION III INSTALLATION INSTRUCTIONS SECTION V TROUBLESHOOTING GUIDESECTION I WARRANTY Warranty SECTION II UNIT OPERATION Basic Operation Conductivity Key FeaturesAdjustable Setpoints FaultsAllowable Operating Conditions Engineering and ApplicationSECTION III INSTALLATION INSTRUCTIONS Mounting Remove foam packing from top of tankPlumbing Distributor Mounting Instructions Steam DistributionBlower Version 6000-1,2 DUCTED VERSION 6000-3,4Control Circuit Connections WiringFigure Supply Power Electrical CharacteristicsSECTION IV OPERATING INSTRUCTIONS Start-upInstructionsChecklist completion date ChecklistChecklist completed by Humidifier Installer CompanyExtended Shutdown MaintenanceTo remove the cylinder Figure 11A Figure 11BHigh Conductivity Settings SECTION V TROUBLESHOOTING GUIDECircuit Board Settings Standard SettingsFill System Fault Problem / SymptomSee - NON-FAULTACTIVATED FAULT ACTIVATED PROBLEMSNon-FaultActivated Problems Problem / SymptomReason - Correction Non-FaultActivated Problems - Cont’d Problem / SymptomReason - Correction Blower Version Wiring Diagram6000-1and Blower Version Exploded View 6000-1and Blower Version Parts List 6000-1and Ducted Version Exploded View 6000-3and Ducted Version Parts List 6000-3and Ducted Version Wiring Diagram 6000-3and Part 3 --Execution SECTION VI SUGGESTED SPECIFICATIONSSuggested Specifications Part I-Scope Part II -Scope