SECTION II UNIT OPERATION
Basic Operation
Controlled humidification requires a very precise control system. The 6000 utilizes a solid state control to monitor performance and maintain humidity. The humidifier evaluates the operation and alerts the operator to problem conditions and prevents undesirable operation.
On initial
If the water is not conductive enough to allow the unit to reach full load amps (full capacity) on the initial fill; the cylinder full light will indicate a full cylinder condition. The unit will operate in this mode with repetitive fill and boil cycles unit the unit has concentrated enough minerals in the water to reach the rated amp level.
Once full load amp (FLA) has been reached, the fill valve will shut off. The unit will now compare the rate of change of amp draw to a time cycle.
If the water in the cylinder is mineral laden and hence very conductive, a dram cycle will be initiated.
After the dram cycle and or the time cycle is completed, the unit will refill and start the process over.
These cycles will repeat until:
•The call for humidity is removed.
•The cylinder is used up.
•A fault condition occurs.
On initial
As the electrodes in the cylinder are coated with minerals, the water level will slowly increase to the cylinder full level. Concentration will no longer allow the unit to reach FLA. After a period of time, the cylinder will display the red “Service" light indicating the need to change the cylinder.
4