Problem / Symptom | Probable Cause | Reason - Correction | |
Overcurrent | Dead short between electrodes. | Replace the steam cylinder. Check | |
The alarm condition occurs when an |
| resistance between electrodes with | |
overcurrent situation (>138% of rated |
| power “off” | |
current) has occurred and the |
|
| |
humidifier has shut down to prevent | Restricted or blocked drain. | Clean and inspect drain system. | |
any damage. This alarm indicates that |
|
| |
Restricted fill system | Clean and inspect the fill system. | ||
there has been a significant reduction | |||
in resistance between the main legs of |
| Check for restriction or loss of supply | |
the supply power and the humidifier |
| pressure. | |
has been shut down to prevent | Incoming water conductivity is outside | Consult the factory for options. | |
damage and should be serviced | the range of normal circuit board |
| |
before it is restarted. Overcurrent LED | settings. |
| |
CR 17 (Figure 12) is illuminated. |
|
| |
Check amp draw to unit during start- | Manually drain the unit and restart. | ||
| |||
| up. If amp draw greatly exceeds rated |
| |
| amp draw, the drain threshold pot, |
| |
| labeled “% adj.” (R18), must be |
| |
| increased 2% to increase the |
| |
| frequency and duration of drains to |
| |
| reduce the conductivity inside the |
| |
| cylinder. |
| |
End of Cylinder | End of cylinder life – Cylinder life is | For emergency use, you may restart | |
This alarm condition occurs if the | typically between 500 and 2000 hours, | the humidifier with the capacity | |
humidifier is unable to reach full output | depending on incoming water supply. | setpoint, R39, at a lower level to allow | |
over a | (See unit operation section for typical | operation until a replacement steam | |
constantly switching between “fill” and | cylinder life expectancy chart on Pg. | cylinder can be obtained. To clear the | |
“cylinder full” modes. This alarm | 5). | fault, turn the main disconnect to the | |
indicates a need to change the |
| unit “off” and then back “on”. | |
cylinder that the water supply is low in | If incoming water supply is less than | See – | |
conductivity that the water supply is | 100 micromho, the unit may not be | PROBLEMS GUIDE – “Unit fills to the | |
low in conductivity, or that a foaming | able to pass the rated current through | cylinder full condition and remains | |
condition exists: | the water. | cold” | |
| Foaming condition exists. | Flush and fill the steam cylinder | |
|
| several times and restart. If it persists, | |
|
| you must filter or treat the water to | |
|
| remove the foaming agent. See circuit | |
|
| board settings on previous page if | |
|
| supply water is softened. See NON – | |
|
| FAULT ACTIVATED PROBLEMS | |
|
| GUIDE – “Water foaming inside the | |
|
| cylinder” | |
Fill System Fault | Loss of or restricted water supply | Check fill system. | |
This alarm condition occurs when the |
|
| |
fill valve has been energized for a 6- | Leaking drain system. | Check drain system. | |
hour timeframe. The humidifier has |
|
| |
Defective drain valve. | Repair and replace as required. | ||
been shutdown to prevent any | |||
Defective fill valve. | Repair and replace as required. | ||
damage. | |||
|
|
NOTE: The three fault conditions outlined above will cause the humidifier to shut down and the service light on the front of the unit to illuminate. To clear these faults, the main power must be turned “off” and back “on” again.
Unit Detected Faults: (Red “Service” Light On)
14