Key Features
Adjustable Setpoints
Capacity
• Range =
• Preset at 100% for
Low Drain Threshold
• Range =
• Preset at 90%
Cycle Time
• Range =
• Preset at 60 seconds
Faults
Overcurrent
•138% of Rated Current
•System Shutdown
Fill System
•Fill valve open for 6 hours without achieving capacity setpoint or cylinder full
•System Shutdown
End of Cylinder Life
•6 hours of operation while on cylinder full without achieving capacity setpoint
•System Shutdown (See Pg. 14 for Manual Override)
Conductivity* | Average Life** |
Micromhos | Expectancy – Hrs. |
(approx.) | (approx.) |
100 | 2000 |
135 | 1900 |
170 | 1800 |
250 | 1300 |
500 | 800 |
750 | 650 |
1000 | 500 |
*If the conductivity of your supply water is less than 100 micromho, consult Herrmidifier for specific circuit board
adjustments and replacement tank information
Unit performance may be affected.
Operation on water of less than 60 micromho is not recommended.
**Your actual cylinder life may be higher or lower depending on the exact composition of your water supply.
5