Herrmidifier Co 6000 Key Features, Adjustable Setpoints, Faults, Conductivity, Average Life

Page 5
Key Features

Key Features

Adjustable Setpoints

Capacity

• Range = 50-100%

• Preset at 100% for 6000-1,3,4 Preset at 50% for 6000-2

Low Drain Threshold

• Range = 50-100%

• Preset at 90%

Cycle Time

• Range = 60-300 seconds

• Preset at 60 seconds

Faults

Overcurrent

138% of Rated Current

System Shutdown

Fill System

Fill valve open for 6 hours without achieving capacity setpoint or cylinder full

System Shutdown

End of Cylinder Life

6 hours of operation while on cylinder full without achieving capacity setpoint

System Shutdown (See Pg. 14 for Manual Override)

Conductivity*

Average Life**

Micromhos

Expectancy – Hrs.

(approx.)

(approx.)

100

2000

135

1900

170

1800

250

1300

500

800

750

650

1000

500

*If the conductivity of your supply water is less than 100 micromho, consult Herrmidifier for specific circuit board

adjustments and replacement tank information (GT-176-1).

Unit performance may be affected.

Operation on water of less than 60 micromho is not recommended.

**Your actual cylinder life may be higher or lower depending on the exact composition of your water supply.

5

Image 5
Contents Electronic Steam Humidifiers Installation Operation Service6000 Series SECTION III INSTALLATION INSTRUCTIONS TABLE OF CONTENTSSECTION V TROUBLESHOOTING GUIDE SECTION VI SUGGESTED SPECIFICATIONSSECTION I WARRANTY Warranty SECTION II UNIT OPERATION Basic Operation Adjustable Setpoints Key FeaturesFaults ConductivityAllowable Operating Conditions Engineering and ApplicationPlumbing SECTION III INSTALLATION INSTRUCTIONS MountingRemove foam packing from top of tank Blower Version 6000-1,2 Steam DistributionDUCTED VERSION 6000-3,4 Distributor Mounting InstructionsFigure Supply Power WiringElectrical Characteristics Control Circuit ConnectionsSECTION IV OPERATING INSTRUCTIONS Start-upInstructionsChecklist completed by ChecklistHumidifier Installer Company Checklist completion dateTo remove the cylinder MaintenanceFigure 11A Figure 11B Extended ShutdownCircuit Board Settings SECTION V TROUBLESHOOTING GUIDEStandard Settings High Conductivity SettingsSee - NON-FAULTACTIVATED Problem / SymptomFAULT ACTIVATED PROBLEMS Fill System FaultReason - Correction Non-FaultActivated ProblemsProblem / Symptom Reason - Correction Non-FaultActivated Problems - Cont’dProblem / Symptom Blower Version Wiring Diagram6000-1and Blower Version Exploded View 6000-1and Blower Version Parts List 6000-1and Ducted Version Exploded View 6000-3and Ducted Version Parts List 6000-3and Ducted Version Wiring Diagram 6000-3and Suggested Specifications Part I-Scope SECTION VI SUGGESTED SPECIFICATIONSPart II -Scope Part 3 --Execution