Wiring
All field wiring should be routed up through the knockout in the bottom panel or in the back of the unit.
Figure 7
Supply Power.
1.Insure that minimum circuit ampacity is 15 amps.
2.Terminals are provided in the electrical compartment for field connection of the main power supply legs (single phase) and a ground wire.
3.Install external overcurrent protection and provide wiring in accordance with the NEC, state and local codes.
4.Power supply must be “clean”: free of spikes, surges
and sags: +10%,
Electrical Characteristics
Capacity | Steam Output | ||
Lbs. / hr | 4 |
| 8 |
Kg / hr | 1.8 |
| 3.7 |
|
| Input kW | |
| 1.33 |
| 2.66 |
Volts/Ph: |
| Amps | |
120/1 | 11.8 |
| N/A |
230/1 | 5.9 |
| 11.8 |
Control Circuit Connections
WARNING!
Do Not install any controls inside the Herrmidifier 6000 cabinet. Installations of any extraneous devices inside the electrical compartment rnay cause erratic behavior of the circuitry and will VOID the warranty.
6000-1,2
The 6000 units with
6000-3,4
The control wiring for the ducted version is to be connected to the 5 pole controls terminal strip located in the low voltage compartment. Terminals #1 and #2 are for connecting the control and high limit humidistats as well as the air proving switch in series (all included). If desired, terminals #3 and #4 are relay contacts to energize your fan relay (Relay contact rating 12 Amps at 125 VAC, 8 Amps at 250 VAC). With this optional wiring, on a call for humidity, the humidifier will close the interlock relay and energize the fan blower. The air- proving switch must not be used if the fan interlock is utilized. All control wiring should be 22 AWG or larger (See figure 8). Consult with the factory if you have any special wiring requirements.
Figure 8