Viking Access Systems Q7 manual Troubleshooting

Page 39
3 7

TROUBLESHOOTING

LED References

Use the table below to identify the corresponding “TS Ref#” and refer to page 38-41 for

further troubleshooting.

 

Pg 41

#

LED

Status

Meaning

TS Ref#(s)

9

“C Loop”

OFF

Normal Condition.

 

 

 

SOLID

Control Board is receiving an input from a device connected to the

9, 10

 

 

 

C Loop terminal (pgs 32, 42).

10

“Open”

OFF

Normal Condition.

 

 

 

SOLID

Control board is receiving an input for a device connected to any of

9, 10

 

 

 

the following input terminals: Exit, Fire, Strike or Open (pgs 31, 42).

11

“STOP”

OFF

Normal Condition.

 

 

 

SOLID

Control Board is receiving an input from a device connected to the

9, 10

 

 

 

Stop terminal (pgs 31, 42).

12

“Close”

OFF

Normal Condition.

 

 

 

SOLID

Control Board is receiving an input from a device connected to the

9, 10

 

 

 

Close terminal (pgs 31, 42).

13

“Siren”

OFF

Normal Condition.

 

 

 

SOLID

Second consecutive obstruction has been detected. (pg 26).

11, 13, 1, 2

 

 

FLASHING

Batteries are critically low.

1, 2

14

“Aux. Pwr”

OFF

No voltage output on these terminals at the moment.

 

 

 

SOLID

There is 24VDC output on these terminals at the moment.

 

15

“Diagnose”

OFF

Normal Condition.

 

 

 

FLASHING

Errors have been detected; Check LCD Display for ERR messages (pg 40).

 

16

“Close Limit”

OFF

Gate is not at the close limit position.

 

 

 

SOLID

Gate is at the close limit position.

 

 

 

FLASHING

Close limit position has been erased or not set (pg 20-21).

6

17

“Open Limit”

OFF

Gate is not at the open limit position.

 

 

 

SOLID

Gate is at the open limit position.

 

 

 

FLASHING

Open limit position has been erased or not set (pg 20-21).

6

18

“ODS”

OFF

Normal Condition.

 

 

 

SOLID

Obstruction has been detected. (pg 26).

11, 13, 1, 2

 

 

FLASHING

Overload has been detected. (pg 26).

11, 13, 1, 2

19

“Timer”

OFF

The close timer is turned OFF or gate is not at the open limit if the timer is

 

 

 

 

turned ON. (pg 24).

 

 

 

SOLID

Gate is at Open Limit, Timer is turned ON and counting down to close. (pg

 

 

 

 

24).

 

 

 

FLASHING

Gate is at Open Limit, Timer is turned ON but is not timing out due to a

9, 10

 

 

 

conflicting command. (pg 24).

20

“AC VOLTAGE OUTPUT”

SOLID

Normal Condition.

 

 

 

OFF

There is no output voltage from the Modular Power Box.

2

21

“PROTECTION WORKING” SOLID

Normal Condition.

 

 

 

OFF

EMI Board is damaged and circuit is not protected . Replace EMI Board.

 

22

“AC VOLTAGE INPUT”

SOLID

Normal Condition.

 

 

 

OFF

Incoming power to Modular Power Box is not sufficient.(pg 18).

1

23

“AC POWER”

SOLID

Normal Condition for High Voltage installations.

 

 

 

OFF

High Voltage is not supplied to the Power Box Assembly (pg 18).

1

VIKING TECHNICAL SUPPORT 1.800.908.0884

Image 39
Contents Instructions Viking Q-7 Slide Gate Operator Vehicular Gate Operator Revision Q7NXMN10.E December Description Parts DiagramOperator References Control Board References EMI Board ConnectorTable of Contents Important Safety Information Important Safety InstructionsImportant Installation Instructions Important Installation Instructions General Safety Precautions MaintenanceGlossary UL325 Gate Operator ClassificationsSecondary Entrapment Protection Photo Beam non-contact sensor InstallationTo resume normal operation Edge Sensor contact sensor InstallationWhen manual operation is required Manual ReleaseManual Reset for the Audible Alarm Audible Alarm Reset Switch InstallationSpecifications Single Phase 50Hz / 60HzLocate Control Buttons Concrete Pad Installation Gate Operator InstallationSuggested Positive Stop Types Positive Stop InstallationOperator Positioning Step Technical TIP Before completing the installation procedureElectrical Installation Tips for proper ground installationHigh Voltage Supply Option Solar Supply Option Electrical InstallationLimits Setup To Readjust the Open Limit To Readjust the Close LimitMS1 MS2 MASTER/SLAVE SetupTwo Wire Communication Cable RequirementsRequired ADD-ON Wireless Communication OptionsODS Control Board SetupInitial Settings Timer Hold Open TimerLast Open Power Failure Option Auto Open Power Failure OptionODS Obstruction Detection Sensor Obstruction Sensor Primary Entrapment ProtectionViking Heater Viking Lock ModeThis page Left Blank Intentionally Check for proper operation Accessory ConnectionsRe-Open Photo Beam vehicular Safety COM +Radio Receiver Typical Open-Stop-CloseOpen Only ATG Anti-Tailgate Anti-Tailgate, Open Commands & Guard StationOpen Commands Guard StationViking Loop Rack Guidelines for Loop Installation Accessory ConnectionsPower for the Locks Magnetic Lock, Lock SolenoidMagnetic Lock Lock Solenoid Barrier Arm B-12 Synchronization Option Synchronization with B-12LED References TroubleshootingTroubleshooting LCD Display References LCD MSG MeaningTroubleshooting Error Messages Check SolutionsPower Connections Access Control ConnectionsTechnical TIP Viking uses Appendix aRelays In General GeneralCommon Radio Receivers Connections Batteries & Fuse Appendix CSolar Applications PanelsViking Konnect Diagnostic Tool On-site remote Viking Expansion ProductsViking Konnect Master/Slave Kit Secure and reliable OUR Continuous Commitment to Excellence Standard Features