LIMITS SETUP

!IMPORTANT:

1.Before the initial limits setup, a Positive Stop MUST be installed at the close position. This will be used as a reference to relearn the limit positions if the gate has been operated manually while released or if the EPS2 Cable has been disconnected.

2.In the event of a complete power failure, including battery backup, the

limit positions may have may been cleared and will need to be reset as described.

STEP 1

Connect the “Motor Harness” to the

1a

1b

Control Board.

 

 

a.“OPEN LEFT” Connector if the gate opens to the Left, when viewed from inside.

b.“OPEN RIGHT” Connector if the gate opens to the Right, when viewed from inside.

STEP 2

Move the gate to the desired close position then press and hold the “Close Limit” button until the LED is solid.

STEP 3

Move the gate to the desired open position then press and hold the “Open Limit” button until the LED is solid.

“Close Limit” LED flashes if the close limit is not set.

STEP 4

Run the gate in the close direction to search for the installed Positive Stop.

This will be used as a reference.

2 0

“Open Limit” LED flashes if the open limit is not set.

!NOTE: For this 1st cycle, the gate will run slowly past the set close limit, contact the Positive Stop and reverse back.

VIKING TECHNICAL SUPPORT 1.800.908.0884

Image 22
Contents Instructions Viking Q-7 Slide Gate Operator Vehicular Gate Operator Revision Q7NXMN10.E December Parts Diagram DescriptionOperator References EMI Board Connector Control Board ReferencesTable of Contents Important Safety Instructions Important Safety InformationImportant Installation Instructions Important Installation Instructions Maintenance General Safety PrecautionsUL325 Gate Operator Classifications GlossaryPhoto Beam non-contact sensor Installation Secondary Entrapment ProtectionManual Release Edge Sensor contact sensor InstallationWhen manual operation is required To resume normal operationAudible Alarm Reset Switch Installation Manual Reset for the Audible AlarmSingle Phase 50Hz / 60Hz SpecificationsLocate Control Buttons Gate Operator Installation Concrete Pad InstallationPositive Stop Installation Suggested Positive Stop TypesOperator Positioning Technical TIP Before completing the installation procedure StepTips for proper ground installation Electrical InstallationHigh Voltage Supply Option Electrical Installation Solar Supply OptionLimits Setup To Readjust the Close Limit To Readjust the Open LimitCable Requirements MASTER/SLAVE SetupTwo Wire Communication MS1 MS2Wireless Communication Options Required ADD-ONTimer Hold Open Timer Control Board SetupInitial Settings ODSAuto Open Power Failure Option Last Open Power Failure OptionObstruction Sensor Primary Entrapment Protection ODS Obstruction Detection SensorViking Lock Mode Viking HeaterThis page Left Blank Intentionally COM + Accessory ConnectionsRe-Open Photo Beam vehicular Safety Check for proper operationOpen-Stop-Close Radio Receiver TypicalOpen Only Guard Station Anti-Tailgate, Open Commands & Guard StationOpen Commands ATG Anti-TailgateViking Loop Rack Accessory Connections Guidelines for Loop InstallationMagnetic Lock, Lock Solenoid Power for the LocksMagnetic Lock Lock Solenoid Synchronization with B-12 Barrier Arm B-12 Synchronization OptionTroubleshooting LED ReferencesTroubleshooting LCD MSG Meaning LCD Display ReferencesTroubleshooting Error Messages Solutions CheckAccess Control Connections Power ConnectionsGeneral Appendix aRelays In General Technical TIP Viking usesCommon Radio Receivers Connections Panels Appendix CSolar Applications Batteries & FuseViking Expansion Products Viking Konnect Diagnostic Tool On-site remoteViking Konnect Master/Slave Kit Secure and reliable OUR Continuous Commitment to Excellence Standard Features