ACCESSORY CONNECTIONS

Guidelines for Loop Installation

1. Prevent sharp corners in the geometry of the loop sensor.

2. Install the appropriate number of turns for your loop geometry based on the loop perimeter. Use Table C (below) as a guide.

3. Use XLP (cross-linked-polyethylene) type of wire. This wire reduces the effects of moisture and other environmental events in altering the functionality of the vehicular loop detector.

4. Twist the lead wire at least 6 turns per foot.

5. Use BACKER-ROD to minimize damage to the loop detector wire prior to using the sealant.

6. Place the loop detector wire and adjust the sensitivity of the vehicular loop detector unit in a way to minimize the effects of the gate over the loop detector wire.

! IMPORTANT! Some of the following parameters may affect the proper functionality of the vehicular loop detector.

Consult the manufacturer of the vehicular loop detector and/or loop wire.

• Gate size

• Number of turns in the loop sensor wire

• Distance of the loop sensor wire to the gate at either at the open or close position

Table C - Recommended Number of Turns

Perimeter (ft.)

Number of Turns

 

10

5

 

20

4

 

30-40

3

 

50-100

2

Dimension “A” - 5’ for Single Gate 6’ for Dual Gate

VIKING TECHNICAL SUPPORT 1.800.908.0884

3 3

 

 

Image 35
Contents Instructions Viking Q-7 Slide Gate Operator Vehicular Gate Operator Revision Q7NXMN10.E December Description Parts DiagramOperator References Control Board References EMI Board ConnectorTable of Contents Important Installation Instructions Important Safety InformationImportant Safety Instructions Important Installation Instructions General Safety Precautions MaintenanceGlossary UL325 Gate Operator ClassificationsSecondary Entrapment Protection Photo Beam non-contact sensor InstallationTo resume normal operation Edge Sensor contact sensor InstallationWhen manual operation is required Manual ReleaseManual Reset for the Audible Alarm Audible Alarm Reset Switch InstallationLocate Control Buttons SpecificationsSingle Phase 50Hz / 60Hz Concrete Pad Installation Gate Operator InstallationSuggested Positive Stop Types Positive Stop InstallationOperator Positioning Step Technical TIP Before completing the installation procedureHigh Voltage Supply Option Electrical InstallationTips for proper ground installation Solar Supply Option Electrical InstallationLimits Setup To Readjust the Open Limit To Readjust the Close LimitMS1 MS2 MASTER/SLAVE SetupTwo Wire Communication Cable RequirementsRequired ADD-ON Wireless Communication OptionsODS Control Board SetupInitial Settings Timer Hold Open TimerLast Open Power Failure Option Auto Open Power Failure OptionODS Obstruction Detection Sensor Obstruction Sensor Primary Entrapment ProtectionViking Heater Viking Lock ModeThis page Left Blank Intentionally Check for proper operation Accessory ConnectionsRe-Open Photo Beam vehicular Safety COM +Open Only Radio Receiver TypicalOpen-Stop-Close ATG Anti-Tailgate Anti-Tailgate, Open Commands & Guard StationOpen Commands Guard StationViking Loop Rack Guidelines for Loop Installation Accessory ConnectionsMagnetic Lock Lock Solenoid Power for the LocksMagnetic Lock, Lock Solenoid Barrier Arm B-12 Synchronization Option Synchronization with B-12LED References TroubleshootingTroubleshooting LCD Display References LCD MSG MeaningTroubleshooting Error Messages Check SolutionsPower Connections Access Control ConnectionsTechnical TIP Viking uses Appendix aRelays In General GeneralCommon Radio Receivers Connections Batteries & Fuse Appendix CSolar Applications PanelsViking Konnect Master/Slave Kit Secure and reliable Viking Konnect Diagnostic Tool On-site remoteViking Expansion Products OUR Continuous Commitment to Excellence Standard Features