FireplaceXtrordinair 36 DV EFIII 2Finalizing the Installation, Fine Tuning the EMBER-FYRE Burner

Page 32

3 2Finalizing the Installation

8Turn the flame adjust knob to its highest position - the flames should be approximately 10" tall. Check the flame on low position. The flames should burn off of each burner hole. If the heater does not work correctly, contact your dealer for a remedy.

FINE TUNING THE EMBER-FYRE™ BURNER

Each installation is affected by altitude, vent configuration, and fuel quality. Because of this, the restrictor and air shutter may need to be fine tuned to each installation. Follow the hints below to fine-tune the burner for optimum performance and aesthetics.

Restrictor Hints:

Set the restrictor to the position suggested in the vent configuration table (see pages 20-23). Turn the heater on and allow it to reach full temperature (15 min.). If the flames indicate there is excessive draft due to altitude or climate, you may wish to adjust the restrictor to a more restrictive position (higher number). Active, flickering short flames are an indication of excessive draft. If the flames lift off of the burner holes, this indicates not enough draft (restrictor is set too high). After adjustments are made the unit must be cooled down to room temperature and restarted to make sure that the restriction is not so severe that the pilot will drop out when it is restarted. If the pilot does drop out reduce the restriction until it will operate continuously.

Air Shutter Hints:

For more glow, open the air shutter, however, this will make the flames more blue.

For yellow flames, close the air shutter, however, this may create less glow.

Correct

Lifting Flames

Ghosting Flames

Flickering Flames

 

Burner Ports

 

 

Burner

(holes)

 

 

The flames should burn right off the top of the burner ports (if they are too blue, adjust the air control).

Lifting flames indicate insufficient draft (restrictor is set too high).

Ghosting flames indicate

Flickering, short flames

insufficient air (restrictor set too

indicate excessive draft

high, air shutter shut down, or

(move air shutter to a higher

other venting error).

position).

Warning: If the vent configuration is installed incorrectly the vent may cause the flames inside the heater to lift or “ghost” – a dangerous situation. Inspect the flames after installation to insure proper performance. If the vent configuration is correct, yet the flames are lifting or ghosting, shut off gas to the heater and contact the dealer for information on remedying the problem.

9Give this manual to the home owner and fully explain the operation of this heater.

Travis Industries

4040708

1 0 0 - 0 1 1 6 0

Image 32
Contents If YOU Smell GAS Travis Industries 4040708 0 0 1 1 6 2IntroductionIntroduction Important Information Table of Contents Safety Precautions If YOU Smell GASThis Manual Natural Gas Propane 6Features and SpecificationsFeatures Installation Options Packing List Additional Items Required Installation WarningsInstallation Overview Clearances Fireplace Placement RequirementsMinimum Framing Dimensions Corner Installations Raised FireplacesHearth Requirements Floor Mounted FireplacesFacing Requirements Facing Over 1 ThickFacing Detail TOP ViewModifying the Face Angle for Rectangular Faces Installation forFace Dimensions Facing and Hearth Examples Side ViewDV Fireplace Non-Combustible Mantels Mantel RequirementsCombustible Mantels Vent Requirements Altitude ConsiderationsUse of 8 Diameter Pipe Part Numbers for 6-5/8 Diameter VentVent Installation Horizontal Vent RequirementsApproved Vent Configurations Restrictor PositionElbows Measuring Vent LengthsZero or Two 45 Offsets Horizontal Terminations using 6-5/8 Diameter Vent 0feet 5feet 10feet 12max 10 max FeetFeet 5feet 10feet 15feet 20feet 25max 40 max Horizontal Terminations using 8 Diameter Vent Termination Requirements see the illustration below Gas Line Requirements FuelGas Line Connection Gas Inlet PressureElectrical Connection Finalizing the Installation Re-Attaching the Glass Frame8Finalizing the Installation Glass Frame Removal Spring Pin InstallationTop Front View Side View 0Finalizing the InstallationStep Correct 2Finalizing the Installation Fine Tuning the EMBER-FYRE BurnerLocation of Controls See explanation below Operation3Before You Begin 4Operation Starting The Pilot FlameTurning the Fireplace On and Off Adjusting the Flame HeightStarting the Fireplace for the First Time Adjusting the Blower Speed Optional Power Heat Duct6Operation Normal Operating SoundsMaintaining Your Fireplaces Appearance Maintenance3Yearly Service Procedure Maintenance TroubleshootingWhat Prevents Gas Buildup How this Fireplace WorksWhat Turns the Main Burners On and Off Replacement Parts List 0MaintenanceWiring Diagram Safety Label Minimum Clearances to Combustibles2Limited 7 Year Warranty Years 1 & 2 Coverage Parts & LaborBurner Replacement LP Conversion InstructionsOptional Equipment for qualified installers only Slotted Screwdriver Or T-20 Torx Power Heat Duct Wall or Ceiling Mounting Optional Equipment for qualified installers only Wiring Diagram Follow the directions below to wire the blower box Maintenance Instructions 2Index

36 DV EFIII specifications

The FireplaceXtrordinair 36 DV EFIII is a remarkable direct vent gas fireplace that blends innovative technology with aesthetic appeal, making it an ideal addition to any modern living space. Renowned for its exceptional design and performance, this fireplace provides both warmth and ambience while ensuring efficiency and safety.

One of the standout features of the 36 DV EFIII is its impressive heating capacity. It boasts a maximum output of up to 28,000 BTUs, providing sufficient heat to effectively warm large areas while maintaining energy efficiency. This model is equipped with a powerful fan system that circulates warm air throughout the room, enhancing comfort levels even in colder months.

The FireplaceXtrordinair 36 DV EFIII incorporates advanced technology, including a state-of-the-art electronic ignition system. This feature allows for quick and easy startups without the hassle of traditional matches or lighters. Additionally, the unit is designed with a modulating gas valve, which adjusts the flame height to optimize both heat output and fuel consumption, resulting in impressive energy savings.

The fireplace is also designed with versatility in mind. It offers customizable options, including various decorative media, such as traditional logs, rocks, or contemporary glass, allowing homeowners to create the desired aesthetic that complements their interior design. The 36 DV EFIII is available with multiple front styles and finishes, ensuring it integrates seamlessly with any décor.

Safety is paramount with the FireplaceXtrordinair 36 DV EFIII, featuring a sealed combustion system that draws air from outside the home, reducing the risk of indoor pollution. The direct vent design ensures that all exhaust is expelled outside, providing a clean and safe burning experience.

Another notable characteristic of the 36 DV EFIII is its easy maintenance. The unit is designed for straightforward cleaning, with an accessible glass front that can be easily removed for periodic maintenance. This convenience makes it an attractive option for homeowners looking for a user-friendly fireplace solution.

In conclusion, the FireplaceXtrordinair 36 DV EFIII is a premium direct vent gas fireplace that combines elegance, efficiency, and safety. With its impressive heating capabilities, customizable features, and advanced technology, it stands out as an excellent choice for anyone looking to enhance their home with a high-quality fireplace.