Lochinvar 51 Field wiring, Installation must comply with, Line voltage connections

Page 50

Installation & Operation Manual

8Field wiring

￿WARNING ELECTRICAL SHOCK HAZARD – For your safety, turn off electrical power

supply before making any electrical connections to avoid possible electric shock hazard. Failure to do so can cause severe personal injury or death.

3.

Wire the boiler pump as shown in FIG. 8-2.

4.

When connecting a domestic hot water (DHW) pump,

 

connect the wiring to the line voltage terminal strip as

 

shown in FIG. 8-2.

5.

To activate a system pump, wire as shown in FIG. 8-2. If the

NOTICE

￿CAUTION

Wiring must be N.E.C. Class 1.

If original wiring as supplied with boiler must be replaced, use only type 105°C wire or equivalent.

Boiler must be electrically grounded as required by National Electrical Code ANSI/NFPA 70 – latest edition.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

motor is larger than 1/8 hp or 1.8 amps, you must isolate

with a relay.

Figure 8-2Line Voltage Field Wiring Connections

Figure 8-1Remove Bezel

REMOVE BEZEL

Installation must comply with:

1.National Electrical Code and any other national, state, provincial, or local codes, or regulations.

2.In Canada, CSA C22.1 Canadian Electrical Code Part 1, and any local codes.

Line voltage connections

1.Remove bezel as shown in FIG. 8-1.

2.Connect 120 vac power wiring to the line voltage terminal strip in the junction box, as shown in FIG. 8-2.

2.Provide and install a fused disconnect or service switch (15 amp recommended) as required by the code (see FIG. 8-2).

50

Low voltage connections

1.Route all low voltage wires through the knockouts in the bottom front right side, just under the control panel, as shown in FIG. 8-3.

2.Connect low voltage wiring to low voltage connection board as shown in FIG. 8-4 on page 53 of this manual and the boiler wiring diagram.

Figure 8-3Routing Field Wiring

LOW VOLTAGE

CONNECTION BOARD

LOW VOLTAGE

WIRING KNOCKOUTS

LINE VOLTAGE

JUNCTION BOX

LINE VOLTAGE

WIRING KNOCKOUTS

Image 50
Contents Models 51 Contents When servicing boiler Please read before proceedingKnight Wall Mount Boiler How it works Stainless steel heat exchangerModels 51 Ratings Knight Wall Mount Boiler =B=R RatingDetermine boiler location Installation must comply withCloset and alcove installations Before locating the boiler, check1Closet Installation Minimum Required Clearances Wall mounting location Provide air openings to roomVent and air piping Prevent combustion air contaminationAreas likely to have contaminants When using an existing vent system to install a new boilerProducts to avoid When removing a boiler from existing common vent system Gas conversions Prepare boilerRemove boiler from wood pallet Mounting to a metal studded wall Mounting the boilerMounting to a concrete wall Mounting to a wood studded wallGeneral venting Direct venting options Sidewall VentDirect venting options Vertical Vent Direct venting options Vertical Vent, Sidewall AirInstalling vent and air piping Install vent and combustion air pipingRequirements for installation in Canada PVC/CPVC Vent piping materialsApproved Stainless Steel Vent Manufacturers PVC/CPVC air intake/vent connectionsAir inlet pipe materials MakeBoiler Stainless steel ventBoiler Flue Boiler Flue Intake Air AdapterVent and air system Stainless steel air intake/vent connectionsRemoving from existing vent Vent, air piping and terminationOptional room air Model Kit Number KIT30051 Air contaminationVent/air termination sidewall If using the alternate sidewall terminationSidewall direct venting Vent Size2AClearance to Gravity Air Inlets Termination and fittings Prepare wall penetrationsPrepare wall penetrations Alternate Field Supplied Option Multiple vent/air terminationsDescription and usage Sidewall termination installationSidewall termination optional concentric vent 8Concentric Vent Dimensional Drawing Sidewall termination optional concentric vent models10Concentric Vent Sidewall Attachment Multiventing sidewall terminationsVertical direct venting Vent/air termination verticalPrepare roof penetrations 2Vertical Terminations with Multiple BoilersVertical termination installation Vertical termination optional concentric ventMultiventing vertical terminations Minimum Combustion AIR TypicalAlternate vertical concentric venting Concentric Venting ArrangementExisting vent as a chase AIR Inlet Flue Exhaust Seal CAP Existing Flue OutletHydronic piping Near boiler piping components Near boiler piping connections Circulator sizingArmstrong ModelMinimum Pipe Pump Size Grundfos Model Grundfos Variable speed pump setupVariable speed pump option UP26-96 FC/VS IFC VS Stratos 1.25 3 x3Single Boiler Single Temperature Zoned with Circulators Number of Units 5Single Boiler Multiple Temperatures Multiple Boilers Multiple Temperatures Model 8Single Boiler Zoned with Valves Model 10Single Boiler Non-Zoned Primary/Secondary Piping Connecting gas supply piping Gas connectionsNatural gas Propane GasLength of Pipe in Straight Feet for 1/2 PSI Natural Gas Pipe Capacity ChartCheck inlet gas supply Gas valve replacement Gas PressureLine voltage connections Field wiringInstallation must comply with Low voltage connectionsFlow switch Outdoor temperature sensorLouver proving switch ThermostatSystem supply sensor Alarm contactsWiring of the cascade Boiler management systemInstallation Condensate disposal Condensate drainCheck/control water chemistry Freeze protection when usedStart-up Fill and test water systemInspect/fill condensate system Clean/Inspect Trap AssemblyCheck for gas leaks Check thermostat circuits Inspect/check condensate lines and fittingsIf boiler does not start correctly Final checks before starting the boilerStart the boiler Check system and boiler2Operating Instructions Set space heating operation Natural Gas PropaneSet domestic hot water DHW operation Verify DHW modeConfiguration of the cascade Operating information GeneralProtection features Boiler temperature regulation Outdoor reset operation, if used CascadeSequence of operation Operation DisplayUser Access modesInstaller Knight wall mount boiler control module 1Control PanelCall for Heat Information Right Select no Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check control settings Check ignition ground wiringCheck all boiler wiring Check expansion tankReview with owner Check flame signalCleaning boiler heat exchanger Oiled bearing circulatorsDiagrams PC Interface2Wiring Diagram Page Page

51 specifications

Lochinvar 51 is an innovative and robust residential boiler system designed for high-efficiency heating needs. A popular choice among homeowners, the Lochinvar 51 stands out in the market due to its advanced features and eco-friendly technologies.

One of the main features of Lochinvar 51 is its compact design, making it ideal for installation in limited space environments such as attics or closets. Despite its small footprint, it boasts a powerful heating capacity, suitable for varying home sizes. The boiler operates with a modulating gas burner that allows it to adjust its heat output according to the demand, ensuring efficiency and comfort throughout the day.

The Lochinvar 51 employs a cutting-edge heat exchanger made from stainless steel, which is highly durable and resistant to corrosion. This design not only enhances the boiler's performance but also increases its lifespan. The unit offers impressive AFUE (Annual Fuel Utilization Efficiency) ratings, showcasing its capability to convert a significant portion of fuel into usable heat, thus minimizing energy waste and reducing heating costs.

Technologically, the Lochinvar 51 is equipped with advanced control systems that facilitate precise temperature management. The intuitive interface allows homeowners to easily set their desired temperature and monitor the system’s performance. Additionally, the integration of outdoor reset technology helps optimize energy consumption by adjusting the water temperature based on outside weather conditions, leading to further energy savings.

Safety features are also paramount in the Lochinvar 51. It includes built-in safeguards that monitor pressure and temperature, automatically shutting down the system in case of any irregularities. This not only protects the boiler but also ensures peace of mind for users.

Moreover, Lochinvar 51 supports compatibility with smart home systems, providing homeowners with remote control capabilities via mobile devices. This innovative feature enhances user convenience, allowing for easy adjustments and monitoring of the heating system from anywhere.

In conclusion, the Lochinvar 51 is an exceptional choice for homeowners looking for a reliable, efficient, and technologically advanced heating solution. With its impressive heating capacity, durable design, and innovative control features, it sets a high standard in residential boiler performance, making it a top contender in today’s market.