Page 20

Figure 16 (continued) - 7600A/B multi-zone connections with Indirect Domestic Hot Water (DHW)

*Additional zones can be added by duplicating the plumbing and wiring of zone 3.

CONTINUED FROM PREVIOUS PAGE

Control Wiring (Option 2): Circulator-On Delay on All Zones

1.Set “DHWP OFF” (default, see programming section for instructions)

2.Set “C1 on ZR” (see programming section for instructions)

3.Circulator-on delay will affect all zones. Circulator-off delay will have no effect.

4.DHW zone will not have priority over heating zones.

SK10024

TW

TR

L2 L1 C1 C2 ZC ZR B1 B2

7600A:

120 VAC BURNER OR GAS IGNITION SYSTEM

7600B:

24 VAC GAS IGNITION SYSTEM

NEUTRAL WHITE

120VAC

HOT FIELD/MFR. BLACK

SUPPLIED

SERVICE

SWITCH

CIRCULATOR

120 VAC

P4*

6 ZONE RELAY

5

4

3

2/N T

1/H T

CIRCULATOR

120 VAC

P3

6 ZONE RELAY

5

4

3

2/N T

1/H T

CIRCULATOR

120 VAC

P2

6 ZONE RELAY

5

4

3

2/N T

1/H T

CIRCULATOR

120VAC P1

6 ZONE RELAY

5

4

3

2/N T

1/H T

ZONE

3*

LOW VOLTAGE THERMOSTAT

ZONE

2

LOW VOLTAGE THERMOSTAT

ZONE

1

LOW VOLTAGE THERMOSTAT

DHW

LIMIT

CONTROL

CONTINUED ON NEXT PAGE ►

20

Image 20
Contents Description / Applications Table of Contents FeaturesTechnical Specifications Electrical Shock HazardElectrical Ratings Environmental RatingsSensor/Immersion Well Mounting Surface Mounting InstallationMounting AquaSmart Models and Cross-Reference Guide Burn, Scald, Explosion, and Equipment Malfunction HazardFrom previous Burn and Scald Hazard Installing the Temperature SensorRemoving the Control to be Replaced Electrical shock hazard Explosion Burn and Scald Hazards 8 hexIn-1 Installation Instructions This is very important for successful control operationWiring Installing the AquaSmart ControlImmersion Well or 2-in-1 Sensor Appliance SurfaceWiring the AquaSmart Control Some Thermostats Are Polarity SensitiveControl Wiring Water Flow7600A/B multi-zone connections Control Wiring Option 2 Circulator-On Delay on All Zones Control Wiring Option 1 7600B only Taco HoneywellControl Wiring Option 2 7600A only Taco HoneywellDHW With Indirect Domestic Hot Water DHW Limit Zone Relay Circulator Control Wiring Option 3 Utilizing a Zone Panel On Next Honewell Taco Temperature High Limit Temperature Low LimitTemperature High Limit Differential Programming Basic FunctionsTemperature Low Limit Differential Changing the Heat Manager SettingsProgramming Additional Options Viewing the Boiler Cycle HistoryChanging the Circulator Settings Key for steps B3 & B5Changing Low Water Cut-Off Lwco Setting Changing Domestic Hot Water Priority Dhwp SettingSelecting Fahrenheit or Celsius Temperature Display AquaSmart Boiler Control Manual System Action AquaSmart Response Control Checkout ProcedureAquaSmart Operation How a Boiler Control Works Troubleshooting Display Boiler Status ModeHeatManager Technology LockoutAccessories Final ChecklistService Page Mounting Template Limited Warranty Information