Page 11

Explosion Hazard. Can Cause Severe Injury, Death

or Property Damage.

Use this product only in systems with a pressure relief valve.

Wiring the AquaSmart Control

Consult the appliance wiring diagrams to check the manufacturer’s specifications.

Refer to Figure 12 through Figure 17 for some typical wiring diagrams.

Verify the wires are still labeled correctly and make connections to the appropriate terminals on the control wiring terminal strip.

Provide disconnect means and overload protection as required on power supply.

Connect control conduit bracket to earth ground using the supplied grounding screw.

B1 terminal is a 1/4 in. tab terminal (quick connect).

Some Thermostats Are

Polarity Sensitive

Reversed polarity could cause erratic cycling of the boiler control.

yConnect the red thermostat wire (from the RH or R terminal of the thermostat) to the TR terminal on the control.

yConnect the white thermostat wire (from the W terminal of the thermostat) to the TW terminal on the control.

Figure 11 - TR, B2, & Vent Damper Connections

TR

6-Position Vent

Damper Receptacle

B2

Observe proper polarity when wiring L1 and L2. If polarity is reversed, a

call for heat on the ZR input may not be recognized.

7600B only: TERMINALS TR (Z or hot) and B2 (TV or ground) offer a

24-volt supply for operating other 24 VAC equipment on the boiler. IMPORTANT: TO PREVENT DAMAGE TO

THE CONTROL, DO NOT OVERLOAD THE TRANSFORMER. The AquaSmart is equipped with a 30VA transformer. Make sure that the total load, including the burner circuit and TR & B2 connections do not exceed 30VA. See Figure 11.

How to calculate VA - Add all AMP ratings of 24VAC components in this circuit and multiply sum by 24 volts. (Example: .4 + .4 + .2 + .2 = 1.2A x 24V = 28.8 VA)

When powering multiple circulators from the C1 and C2 terminals, take extra care not to exceed the output’s reading. If the sum

of the full load amps of all the circulators exceeds the output’s rating, use the C1 and C2 terminals to power the coil of a multiple-pole contactor; the contacts of which can be wired to switch L1 to each circulator.

To wire a vent damper to the 7600B, first remove jumper plug from 6-

position receptacle and then connect 6-pin connector of the vent damper to the receptacle. See Figure 11. Once the 7600B is operated with a vent damper, it will not function without one (even if the jumper plug is replaced).

Water Flow Symbols Key (Figures 12 through 17)

-Air Vent

-Air Separator

-Expansion Tank

-Isolation Valve

-Pressure Regulator

Z- Zone Valve

-Check Valve

-Circulator

AquaSmart Boiler Control Manual

11

Image 11
Contents Description / Applications Features Table of ContentsEnvironmental Ratings Technical SpecificationsElectrical Shock Hazard Electrical RatingsSensor/Immersion Well Mounting Surface Mounting InstallationMounting Burn, Scald, Explosion, and Equipment Malfunction Hazard AquaSmart Models and Cross-Reference GuideFrom previous Burn and Scald Hazard Installing the Temperature SensorRemoving the Control to be Replaced Electrical shock hazard 8 hex Explosion Burn and Scald HazardsThis is very important for successful control operation In-1 Installation InstructionsAppliance Surface WiringInstalling the AquaSmart Control Immersion Well or 2-in-1 SensorSome Thermostats Are Polarity Sensitive Wiring the AquaSmart ControlWater Flow Control Wiring7600A/B multi-zone connections Control Wiring Option 2 Circulator-On Delay on All Zones Taco Honeywell Control Wiring Option 1 7600B onlyTaco Honeywell Control Wiring Option 2 7600A onlyDHW With Indirect Domestic Hot Water DHW Limit Zone Relay Circulator Control Wiring Option 3 Utilizing a Zone Panel On Next Honewell Taco Programming Basic Functions Temperature High LimitTemperature Low Limit Temperature High Limit DifferentialViewing the Boiler Cycle History Temperature Low Limit DifferentialChanging the Heat Manager Settings Programming Additional OptionsKey for steps B3 & B5 Changing the Circulator SettingsChanging Low Water Cut-Off Lwco Setting Changing Domestic Hot Water Priority Dhwp SettingSelecting Fahrenheit or Celsius Temperature Display AquaSmart Boiler Control Manual System Action AquaSmart Response Control Checkout ProcedureAquaSmart Operation How a Boiler Control Works Lockout TroubleshootingDisplay Boiler Status Mode HeatManager TechnologyAccessories Final ChecklistService Page Mounting Template Limited Warranty Information