Beckett 7600 AquaSmart Operation, Control Checkout Procedure, System Action AquaSmart Response

Page 30

AquaSmart Operation

Table 4 – Typical operation with default settings (Circulator set “ON TT”)

System Action

AquaSmart Response

 

 

 

○ Burner is turned on until the water temperature reaches the low

Temperature falls below low limit

limit plus the low differential.

○ ZC is turned off until the water temperature reaches the low limit

 

 

plus the low differential.

 

 

 

○ Burner is turned on as long as the water temperature is below

Thermostat call for heat

the high limit.

○ Circulator is turned on after circulator-on delay if the low limit is

 

 

satisfied.

 

 

Thermostat is satisfied

○ Burner is turned off.

○ Circulator is turned off after circulator-off delay

 

 

 

ZR call for heat

○ Burner is turned on as long as the water temperature is below

the high limit.

 

 

 

ZR is satisfied

○ Burner is turned off.

 

 

Temperature reaches high limit

○ Burner is turned off until the water temperature falls below the

high limit minus the high differential.

 

 

 

Circulator is inactive for 3 days

○ Circulator is turned on for 2 seconds to help prevent seizure.

 

 

 

○ Burner, Circulator, and ZC are turned off until the control is

AquaSmart locks out

reset. The lockout condition may reset automatically or require

 

a manual reset. See lockout section for more information.

 

 

B1 has been energized for 1 hour or

○ Circulator and ZC are turned on to help prevent system freeze-

AquaSmart has been locked out for 1 hour

up by circulating the boiler water to all zones.

 

 

 

○ If DHWP is set on T-T and there is a T-T call for heat, ZC is held

Priority call for heat

off for up to 20 minutes to give the DHW zone priority.

○ If DHWP is set on ZR and there is a ZR call for heat, C1 is held

 

 

off for up to 20 minutes to give the DHW zone priority.

 

 

Control Checkout Procedure

These procedures are typical for the default configuration of the control.

1.Wire and configure the AquaSmart as required by the application.

2.NOTE: Do not apply a thermostat call for heat to the AquaSmart at this time. Allow the burner to heat the water to above the low limit, plus the low limit differential. The display should read “HEATING WTR” on the LCD display (B1 should be energized and C1 and ZC should be off).

3.When the water is sufficiently heated, the burner will turn off and the display should read “STANDBY”. Now ZC should be energized and B1 and C1 should be off.

4.Apply a call for heat from the thermostat. The burner and circulator should now also turn on (B1, C1, and ZC should now all be energized). Allow the AquaSmart to heat the water to the high limit. During this step the display should read “HEATING WTR or “HEATING DHW”.

5.Once the high limit is reached, the burner should turn off (C1 and ZC should now be energized, and B1 should be off). The display should now read “CIRCULATING”.

6.Set the thermostat back, so that it is no longer calling for heat. The circulator should turn off (now ZC should be energized and B1 and C1 should be off). The display should now read “STANDBY”.

Do not leave the installation site if the AquaSmart

operation did not match the descriptions in any of the above steps. Make all necessary adjustments until the correct operation is verified. The above procedure helps to verify that the high and low limits are working properly and that the thermostat is wired correctly to the control.

30

Image 30
Contents Description / Applications Table of Contents FeaturesElectrical Ratings Technical SpecificationsElectrical Shock Hazard Environmental RatingsInstallation MountingSensor/Immersion Well Mounting Surface Mounting AquaSmart Models and Cross-Reference Guide Burn, Scald, Explosion, and Equipment Malfunction HazardFrom previous Installing the Temperature Sensor Removing the Control to be Replaced Electrical shock hazardBurn and Scald Hazard Explosion Burn and Scald Hazards 8 hexIn-1 Installation Instructions This is very important for successful control operationImmersion Well or 2-in-1 Sensor WiringInstalling the AquaSmart Control Appliance SurfaceWiring the AquaSmart Control Some Thermostats Are Polarity SensitiveControl Wiring Water Flow7600A/B multi-zone connections Control Wiring Option 2 Circulator-On Delay on All Zones Control Wiring Option 1 7600B only Taco HoneywellControl Wiring Option 2 7600A only Taco HoneywellDHW With Indirect Domestic Hot Water DHW Limit Zone Relay Circulator Control Wiring Option 3 Utilizing a Zone Panel On Next Honewell Taco Temperature High Limit Differential Temperature High LimitTemperature Low Limit Programming Basic FunctionsProgramming Additional Options Temperature Low Limit DifferentialChanging the Heat Manager Settings Viewing the Boiler Cycle HistoryChanging the Circulator Settings Key for steps B3 & B5Changing Domestic Hot Water Priority Dhwp Setting Selecting Fahrenheit or Celsius Temperature DisplayChanging Low Water Cut-Off Lwco Setting AquaSmart Boiler Control Manual Control Checkout Procedure AquaSmart OperationSystem Action AquaSmart Response How a Boiler Control Works HeatManager Technology TroubleshootingDisplay Boiler Status Mode LockoutFinal Checklist ServiceAccessories Page Mounting Template Limited Warranty Information