Figure 17 (continued) - 7600A/B alternate multi-zone connections with Indirect Domestic Hot Water (DHW)

*Additional zones can be added by duplicating the plumbing and wiring of zone 3, adding additional transformers as needed.

CONTINUED FROM PREVIOUS PAGE

Control Wiring (Option 1): 7600B only

1.Set “DHWP on ZR” (see programming section for instructions)

2.Set “C1 on BOTH” (see programming section for instructions)

3.Circulator-on delay will affect all zones. Circulator-off delay will have no effect.

4.Up to two 24 VAC zone valves can be powered with the 7600B. Add an additional transformer as shown for every two or less valves over the original two.

5. Ensure there are no jumpers between the terminals of the zone valves.

ZONE 3*

 

LOW VOLTAGE

 

THERMOSTAT

SK10038

TW

TR

L2 L1 C1 C2 ZC ZR B1 B2

NEUTRAL WHITE

120 VAC

BLACK

HOT FIELD/MFR. SUPPLIED SERVICE SWITCH

GENERAL

CIRCULATOR

CIRCULATOR

120 VAC

DHW ZONE 24 VAC ZONE VALVE

Honeywell

V8043F

TR TH

MTR

ZONE 1

LOW VOLTAGE

THERMOSTAT

ZONE 1

24VAC ZONE VALVE

Honewell

V8043F

TR

TH

TH/

 

 

TR

MTR

T

Z

TV

24 VAC GAS

IGNITION SYSTEM

ZONE 3*

24 VAC ZONE VALVE

Honewell

V8043E, V8044E

TH/

Y

MTR

Y

TR

 

 

 

RR

ZONE 2

LOW VOLTAGE

THERMOSTAT

ZONE 2

24VAC ZONE VALVE

Taco 550

1

MTR

32

6ZONE RELAY

5

4DHW LIMIT

3CONTROL

2/N T

1/H T

40 VA TRANSFORMER

CONTINUED ON NEXT PAGE ►

AquaSmart Boiler Control Manual

23

Image 23
Contents Description / Applications Features Table of ContentsEnvironmental Ratings Technical SpecificationsElectrical Shock Hazard Electrical RatingsSensor/Immersion Well Mounting Surface Mounting InstallationMounting Burn, Scald, Explosion, and Equipment Malfunction Hazard AquaSmart Models and Cross-Reference GuideFrom previous Burn and Scald Hazard Installing the Temperature SensorRemoving the Control to be Replaced Electrical shock hazard 8 hex Explosion Burn and Scald HazardsThis is very important for successful control operation In-1 Installation InstructionsAppliance Surface WiringInstalling the AquaSmart Control Immersion Well or 2-in-1 SensorSome Thermostats Are Polarity Sensitive Wiring the AquaSmart ControlWater Flow Control Wiring7600A/B multi-zone connections Control Wiring Option 2 Circulator-On Delay on All Zones Taco Honeywell Control Wiring Option 1 7600B onlyTaco Honeywell Control Wiring Option 2 7600A onlyDHW With Indirect Domestic Hot Water DHW Limit Zone Relay Circulator Control Wiring Option 3 Utilizing a Zone Panel On Next Honewell Taco Programming Basic Functions Temperature High LimitTemperature Low Limit Temperature High Limit DifferentialViewing the Boiler Cycle History Temperature Low Limit DifferentialChanging the Heat Manager Settings Programming Additional OptionsKey for steps B3 & B5 Changing the Circulator SettingsChanging Low Water Cut-Off Lwco Setting Changing Domestic Hot Water Priority Dhwp SettingSelecting Fahrenheit or Celsius Temperature Display AquaSmart Boiler Control Manual System Action AquaSmart Response Control Checkout ProcedureAquaSmart Operation How a Boiler Control Works Lockout TroubleshootingDisplay Boiler Status Mode HeatManager TechnologyAccessories Final ChecklistService Page Mounting Template Limited Warranty Information