AquaSmart Models and Cross-Reference Guide
Table 1a - Direct Replacements
Honeywell
Beckett
Replacement
Notes
|
| Must confirm that 7600 VA rating is adequate to meet VA requirements of system. | |
L7148F (All) | 7600B | Make sure 7600 B1 output does not exceed 1.25A @ 24VAC (30 VA). | |
L8148E (All) | 7600 outputs are not rated for 240 VAC. | ||
| |||
|
| B2, TW and TR terminals replace TV, T and Z, respectively. | |
|
|
| |
L8124A (All) | 7600A | 7600 outputs are not rated for 240 VAC. | |
L8124C (All) | |||
|
| ||
L7124A/C (All) |
|
| |
L7148A (All) | 7600A | The 7600 has no Honeywell EnviraCOMTM Communications port. | |
L7224A/C/U (All) | The diagnostic LED lights are replaced by the 7600’s display. | ||
| |||
L7248A/C (All) |
|
| |
|
| 7600 outputs are not rated for 240 VAC. | |
L8148A (All) | 7600A | B1 terminal on 7600 utilizes a 1/4” quick connect. | |
|
| Set low limit on 7600 to OFF. | |
L8124E 1016 | 7600B | 7600 outputs are not rated for 240 VAC. | |
L8148E 1265 | B2, TW and TR terminals replace TV, T and Z, respectively. | ||
| |||
L8124M (All) | 7600A | For replacement with the 7600: Turn low limit off so the circulator is controlled directly by the thermostat and ZC is constantly powered. | |
L8151A | 7600A | 7600 outputs are not rated for 240 VAC. | |
Remote mount sensor cable needed (Part No. 52120) | |||
|
| ||
|
|
|
Hydrolevel
Beckett
Replacement
Notes
3100
3150
7600B | Not a suitable replacement if Low Water Cutoff (LWCO) functionality of the 3100 is used. | |
7600A | Not a suitable replacement if Low Water Cutoff (LWCO) functionality of the 3150 is used. | |
|
|
Carlin
Beckett
Replacement
Notes
90524A
7600A
Make sure 7600 outputs do not exceed 7.4A.
Available operating limit and differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing. The diagnostic LED lights are replaced by the 7600’s display.
White Rodgers
Beckett
Replacement
Notes
7600A | Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. | |||
7600A |
|
| ||
7600A | Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. | |||
| Available operating limit and differential ranges are not equivalent. Compare the settings to the AquaSmart ranges before replacing. | |||
| ||||
7600B |
|
| ||
|
| |||
|
|
| ||
7600A | Not a suitable replacement if SPDT switch action is required; only | |||
Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. | ||||
|
| |||
|
|
|
| |
|
|
|
|
Burn, Scald, Explosion, and Equipment Malfunction Hazard
Replacement of the following controls must be done only by a qualified service agency or technician who is trained and experienced in the use of boiler controls.
Carefully follow these guidelines and the directions provided by the manufacturer of the control being replaced.
Note: Beckett assumes no liability for incorrect installation or replacement.
Table 1b - Functional Replacement (Advanced Wiring Needed)
Honeywell
Beckett
Replacement
Notes
L4006A (All) | 7600A or 7600B | Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. | |
L4006G 1022 | 7600 will require an additional wire (L2) for operation. Short | ||
(Based on System | |||
L4006H 1004 | Set low limit on 7600 to OFF. | ||
Voltage | |||
L4008A (All) | Available operating limit and/or differential ranges may not be equivalent. Compare the settings to the AquaSmart ranges before replacing. | ||
Requirements) | |||
L4080B/D | To use with a millivolt system, an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit. | ||
| |||
|
|
| |
| 7600A or 7600B | Requires the addition of a | |
L4006E (All) | Make sure 7600 outputs do not exceed 7.4A @ 120 VAC. 7600 outputs are not rated for 240 VAC. | ||
(Based on System | 7600 will require an additional wire (L2) for operation. Short | ||
L4008E (All) | |||
Voltage | Set low limit on 7600 to OFF. | ||
L4080F/G | |||
Requirements) | Available operating limit and/or differential ranges may not be equivalent. Compare the settings to the AquaSmart ranges before replacing. | ||
| |||
|
| To use with a millivolt system, an appropriate voltage relay with isolated gold plated contacts must be added to switch the millivolt circuit. | |
|
|
|
AquaSmart Boiler Control Manual