How a Boiler Control Works

Figure 19 - Cold Start Operation (Low Limit ► OFF)

150

175

200

125

225

100

250

75

275

High Temperature Differential

(Adjustable 5° to 45°F)

Starts the burner when temperature drops to the HIGH LIMIT DIFFERENTIAL setting.

High Temperature Limit

(Adjustable 100° to 240°F)

Shuts burner off at HIGH LIMIT set point.

Example Shown:

High Limit = 200°

Differential = 20°

During a call for heat, the burner will be shut off at 200° and be turned back on at 180° (200°-20°). The circulator will continue to operate until the call for heat is satisfied.

50300

Figure 20 - Warm Start Operation (Low Limit ► ON) (To maintain domestic hot water temperature)

Low Temperature Differential

(Adjustable 10° to 45°F)

Shuts burner off when temperature rises to the LOW LIMIT DIFFERENTIAL setting.

High Temperature Differential

(Adjustable 5° to 45°F)

Starts the burner when temperature drops to the HIGH LIMIT DIFFERENTIAL setting.

Low Temperature Limit

(Adjustable 100° to 220°F)

Starts the burner at LOW LIMIT set point.

Example Shown:

Low Limit = 140°

Differential = 10°

During the OFF cycle with no call for heat, the burner is turned on at 140° to maintain the boiler water temperature and is shut off at 150° (140°+10°).

175

150 200

125225

100

250

75

275

High Temperature Limit

(Adjustable 100° to 240°F)

Shuts burner off at HIGH LIMIT set point.

Example Shown:

High Limit = 200°

Differential = 20°

During a call for heat, the burner will be shut off at 200° and be turned back on at 180° (200°-20°). The circulator will continue to operate until the call for heat is satisfied.

50300

AquaSmart Boiler Control Manual

31

Image 31
Contents Description / Applications Features Table of ContentsEnvironmental Ratings Technical SpecificationsElectrical Shock Hazard Electrical RatingsMounting InstallationSensor/Immersion Well Mounting Surface Mounting Burn, Scald, Explosion, and Equipment Malfunction Hazard AquaSmart Models and Cross-Reference GuideFrom previous Removing the Control to be Replaced Electrical shock hazard Installing the Temperature SensorBurn and Scald Hazard 8 hex Explosion Burn and Scald HazardsThis is very important for successful control operation In-1 Installation InstructionsAppliance Surface WiringInstalling the AquaSmart Control Immersion Well or 2-in-1 SensorSome Thermostats Are Polarity Sensitive Wiring the AquaSmart ControlWater Flow Control Wiring7600A/B multi-zone connections Control Wiring Option 2 Circulator-On Delay on All Zones Taco Honeywell Control Wiring Option 1 7600B onlyTaco Honeywell Control Wiring Option 2 7600A onlyDHW With Indirect Domestic Hot Water DHW Limit Zone Relay Circulator Control Wiring Option 3 Utilizing a Zone Panel On Next Honewell Taco Programming Basic Functions Temperature High LimitTemperature Low Limit Temperature High Limit DifferentialViewing the Boiler Cycle History Temperature Low Limit DifferentialChanging the Heat Manager Settings Programming Additional OptionsKey for steps B3 & B5 Changing the Circulator SettingsSelecting Fahrenheit or Celsius Temperature Display Changing Domestic Hot Water Priority Dhwp SettingChanging Low Water Cut-Off Lwco Setting AquaSmart Boiler Control Manual AquaSmart Operation Control Checkout ProcedureSystem Action AquaSmart Response How a Boiler Control Works Lockout TroubleshootingDisplay Boiler Status Mode HeatManager TechnologyService Final ChecklistAccessories Page Mounting Template Limited Warranty Information