Beckett 7600 manual Programming Basic Functions, Fire, Explosion, and Burn Hazards

Page 25

Programming Basic Functions

the following screen:

Electrical Shock Hazard.

Can cause severe injury, death, or equipment damage.

Live line voltage wires and connections will be exposed while programming the AquaSmart. Take care to touch only the AquaSmart keypad while programming the control.





Press “ENTER (RESET)” if the value is correct, or “CANCEL (BACK)” if it is not.

Fire, Explosion, and Burn

Hazards.

Can cause severe injury, death, or equipment damage.

Do not set the operating limits of the control outside of those listed by the appliance manufacturer.

Figure 18 - AquaSmart Keypad

To ensure smooth appliance operation, the AquaSmart requires a separation between the High and Low limits no less than the greater differential plus 5°F. For example: If the HIGH LIMIT is set to 180°F, the HIGH DIFF to 20°F, and the LOW DIFF to 10°F, the control will not allow a LOW LIMIT above 155°F (180°F - 20°F [the greater of the two differentials] - 5°F = 155°F).

A. Temperature High Limit

1.In any mode or screen other than an OPTION sub- menu, press the “HIGH LIMIT” key.

2.The following screen will be displayed:





The temperature displayed is the current setting. Use the and keys to select the desired setting. Tap the button to increase or decrease the temperature by 1°, or hold it to increase or decrease the temperature by 5° at a time. The control will not allow you to select out-of-range values.

3.Press the “ENTER (RESET)” key.

4.The control will ask you to confirm the setting with

B. Temperature Low Limit

1.In any mode or screen other than an OPTION sub- menu, press the “LOW LIMIT” key.

2.The following screen will be displayed:





The temperature displayed is the current setting. Use the “▲” and “▼” keys to select the desired setting. Tap the button to increase or decrease the temperature by 1°, or hold it to increase or decrease the temperature by 5° at a time. The control will not allow you to select out-of-range values. For cold-start operation, turn the low limit off by pressing the down arrow key repeatedly until OFF is displayed.

IMPORTANT: To prevent flue gas condensation and reduce fatigue caused by thermal cycling on conventional (non-condensing) boilers, the LOW LIMIT set point should be 150° F or above.

NOTE: Appliance manufacturer’s temperature requirements supersede this recommendation.

3.Press the “ENTER (RESET)” key.

4.The control will ask you to confirm the setting with the following screen:





Press “ENTER (RESET)” if the value is correct, or “CANCEL (BACK)” if it is not.

C. Temperature High Limit Differential

1.In any mode or screen other than an OPTION sub- menu, press the “HIGH DIFF” key.

2.The following screen will be displayed:





The temperature displayed is the current setting. Use the “▲” and “▼” keys to select the desired setting. Tap the button to increase or decrease the temperature by 1°, or hold it to increase or decrease the temperature by 5° at a time. The control will not allow you to select out-of-range values.

AquaSmart Boiler Control Manual

25

Image 25
Contents Description / Applications Features Table of ContentsElectrical Shock Hazard Technical SpecificationsElectrical Ratings Environmental RatingsMounting InstallationSensor/Immersion Well Mounting Surface Mounting Burn, Scald, Explosion, and Equipment Malfunction Hazard AquaSmart Models and Cross-Reference GuideFrom previous Removing the Control to be Replaced Electrical shock hazard Installing the Temperature SensorBurn and Scald Hazard 8 hex Explosion Burn and Scald HazardsThis is very important for successful control operation In-1 Installation InstructionsInstalling the AquaSmart Control WiringImmersion Well or 2-in-1 Sensor Appliance SurfaceSome Thermostats Are Polarity Sensitive Wiring the AquaSmart ControlWater Flow Control Wiring7600A/B multi-zone connections Control Wiring Option 2 Circulator-On Delay on All Zones Taco Honeywell Control Wiring Option 1 7600B onlyTaco Honeywell Control Wiring Option 2 7600A onlyDHW With Indirect Domestic Hot Water DHW Limit Zone Relay Circulator Control Wiring Option 3 Utilizing a Zone Panel On Next Honewell Taco Temperature Low Limit Temperature High LimitTemperature High Limit Differential Programming Basic FunctionsChanging the Heat Manager Settings Temperature Low Limit DifferentialProgramming Additional Options Viewing the Boiler Cycle HistoryKey for steps B3 & B5 Changing the Circulator SettingsSelecting Fahrenheit or Celsius Temperature Display Changing Domestic Hot Water Priority Dhwp SettingChanging Low Water Cut-Off Lwco Setting AquaSmart Boiler Control Manual AquaSmart Operation Control Checkout ProcedureSystem Action AquaSmart Response How a Boiler Control Works Display Boiler Status Mode TroubleshootingHeatManager Technology LockoutService Final ChecklistAccessories Page Mounting Template Limited Warranty Information