Beckett 7600 manual In-1 Installation Instructions

Page 9

2-in-1 Installation Instructions

This is very important for successful control operation.

1.Remove the existing immersion well. Clean the threads in the boiler port tapping. Follow all applicable safety codes, rules and guidelines for removing/ installing immersion wells.

2.Apply pipe sealant to the 2-in-1 sensor threads and install it securely into the port. BECKETT RECOMMENDS ONLY TO USE TEFLON TAPE OR RECTORSEAL NO. 5 PIPE SEALANT.

3.Tighten with 1-1/8” open end or box wrench. Pipe wrenches, pliers, and adjustable wrenches will damage/round-off the hex.

4.Securely install the AquaSmart control to the sensor. Plug the 2-in-1 Sensor RJ connector (phone jack style) into the receptacle (Item a, Figure 6) on the control.

5.Route the 36” green wire through the AquaSmart bottom rectangular slot (Item c, Figure 6). Securely install the fork connector of the 36” ground wire and the ground wire from the 2-in-1 sensor under the ground screw at the bottom of the control (Item b, Figure 6).

6.Thoroughly clean the pipe surface and securely tighten the pipe clamp on the water inlet pipe to the boiler as close to the boiler as possible.

7.Route the 36” green ground wire to the pipe clamp then cut to proper length, if necessary.

8.Strip the wire and insert the stripped end into hole on the pipe clamp (item d, Figure 7). Tighten retaining screw against the wire making sure that you have good contact.

9.Complete control wiring and fill the appliance with water to the pressure required, according to appliance manufacturer’s instructions. Make sure all air is purged from the system and there are no leaks. Turn on power to the appliance and observe one call for heat cycle with shut off at set temperature.

Test the Low Water Cut-off (LWCO) Safety Function

WARNING! Avoid touching or shorting the live terminals during this test.

Turn electric power ON to energize AquaSmart control. Perform the following tests to verify the LWCO function.

For AquaSmart 7600A: Remove the green sensor lead from the ground screw. The sensor should cause the AquaSmart display to indicate, “LOCKOUT – LOW WATER”. If it does not, replace the sensor.

For AquaSmart 7600B: Remove the green sensor lead from the ground screw and remove both the B1 and B2 (24 Vac) leads from their terminals. The sensor should cause the AquaSmart display to indicate, “LOCKOUT – LOW WATER”. If it does not, replace the sensor.

Attach wires and tighten terminal screws securely when testing is complete.

Figure 6 - Sensor lead & ground screw connections

a

c

b

Figure 7 - Ground Clamp and Grounding Wire

d

Figure 8 - Sensor Water Detection Method

AquaSmart

Boiler Control

 

2-IN-1 SENSOR

 

Ground Screw

Water Not Present

 

 

Water Present

Ground Wire

 

 

Pipe Clamp

Incomplete

Complete

Circuit

Circuit

 

Water Inlet

 

 

The AquaSmart 2-in-1 Sensor uses the “conduction” method to detect whether water is present in the boiler. This is done by using the water in the boiler itself to “conduct” a signal and complete an electrical circuit. It is necessary that the ground wire from the sensor be bonded to the boiler wall (not the jacket - unless the jacket is bonded to the boiler wall). When water is not present, there is no “conduction” and the circuit is incomplete.

For the AquaSmart we recommend that a grounding pipe clamp be mounted to the water inlet pipe, and that a ground wire be bonded from the pipe clamp to the green terminal inside the AquaSmart control. The 2-in-1 sensor green “ground wire” shall also be bonded to the green terminal in the AquaSmart control.

AquaSmart Boiler Control Manual

9

Image 9
Contents Description / Applications Features Table of ContentsElectrical Shock Hazard Technical SpecificationsElectrical Ratings Environmental RatingsInstallation MountingSensor/Immersion Well Mounting Surface Mounting Burn, Scald, Explosion, and Equipment Malfunction Hazard AquaSmart Models and Cross-Reference GuideFrom previous Installing the Temperature Sensor Removing the Control to be Replaced Electrical shock hazardBurn and Scald Hazard 8 hex Explosion Burn and Scald HazardsThis is very important for successful control operation In-1 Installation InstructionsInstalling the AquaSmart Control WiringImmersion Well or 2-in-1 Sensor Appliance SurfaceSome Thermostats Are Polarity Sensitive Wiring the AquaSmart ControlWater Flow Control Wiring7600A/B multi-zone connections Control Wiring Option 2 Circulator-On Delay on All Zones Taco Honeywell Control Wiring Option 1 7600B onlyTaco Honeywell Control Wiring Option 2 7600A onlyDHW With Indirect Domestic Hot Water DHW Limit Zone Relay Circulator Control Wiring Option 3 Utilizing a Zone Panel On Next Honewell Taco Temperature Low Limit Temperature High LimitTemperature High Limit Differential Programming Basic FunctionsChanging the Heat Manager Settings Temperature Low Limit DifferentialProgramming Additional Options Viewing the Boiler Cycle HistoryKey for steps B3 & B5 Changing the Circulator SettingsChanging Domestic Hot Water Priority Dhwp Setting Selecting Fahrenheit or Celsius Temperature DisplayChanging Low Water Cut-Off Lwco Setting AquaSmart Boiler Control Manual Control Checkout Procedure AquaSmart OperationSystem Action AquaSmart Response How a Boiler Control Works Display Boiler Status Mode TroubleshootingHeatManager Technology LockoutFinal Checklist ServiceAccessories Page Mounting Template Limited Warranty Information